Drawing Number
<br />ES -2
<br />02 of 09
<br />r n 1 „
<br />POWER SOURCE: OWNERS E.C. TO PROVIDE (1) 2 X 4 n X 2/8 STANDARD OUTLET BOX
<br />1 u
<br />POWER SOURCE: OWNERS r E.C. TO PROVIDE (1) 4 " X 4 u X 2/e STANDARD OUTLET BOX
<br />DMP XR20
<br />(120 VAC, 60 HZ, 20 AMP UNSWITCHED) FOR SUPPLIED TRANSFORMER AS CLOSE TO
<br />DIGITAL VIDEO RECORDER (DVR) WITH QUADRAPLEX RECEPTACLE (120 VAC, 60 HZ, 20 AMP UNSWITCHED) WITHIN 10' -0"
<br />GENERAL NOTE
<br />DMP XR40
<br />CABINET AS POSSIBLE. DISTANCE NOT TO EXCEED 50' -0" FROM CABINET.
<br />OF UNIT. ALL RECEPTACLES MUST BE ON THE SAME POWER PHASE.
<br />DMP XR500
<br />OWNER'S E.C. TO PROVIDE (2) 2" X 4" X 2' /s" STANDARD OUTLET BOXES FOR PERIPHERAL
<br />E.C. TO PROVIDE (1) 6" X 6" X 4" MINIMUM SIZE PULL BOX FOR COLLECTION OF COAX
<br />1. PER DIEBOLD SPECIFICATIONS AND THE NATIONAL ELECTRICAL CODE, PURCHASER MUST MAKE ALL WALL AND LINING
<br />�'�
<br />DEVICES AT 5Y ON CENTER 4' -3" ABOVE FINISHED FLOOR.
<br />CABLES.
<br />PENETRATIONS; INSTALL ALL CONDUIT, OUTLET BOXES, JUNCTION BOXES, JUNCTION BOX COVERS, 110 -120 VOLT 60 HZ
<br />ELECTRICAL POWER WITH
<br />P R 0 D U C l
<br />MOUNT CABINET FROM REAR MOUNTING HOLES.
<br />RS 232 LOCAL ACCESS, ETHERNET, AND /OR DIAL UP MODEM REQUIRED FOR RETRIEVAL
<br />SEPARATE INSULATED GROUND WIRE; OBTAIN ALL PERMITS AND ALL LEASED WIRES INCLUDING
<br />ENCLOSURE MODEL: 350-17 X 13'/2" X 3Y2"
<br />TRANSMISSION.
<br />TELEPHONE LINES FOR REMOTE CONNECTIONS; AND REMOVE AND /OR RELOCATE ANY FIXTURES OR OBSTACLES TO PERMIT
<br />INSTALLATION
<br />A P P 11 C A l 10 N
<br />350- - 17'/2' X 13'/2' X 3 3 /a"
<br />RACK MOUNT DVR AS PROVIDED. SOME DVR UNITS CAN BE WALL MOUNTED AS
<br />OF DIEBOLD EQUIPMENT. IN THE EVENT OF A CONFLICT BETWEEN DIEBOLD SPECIFICATIONS AND LOCAL OR
<br />341 - 12 X 016" X 2 %"
<br />REQUIRED.
<br />STATE LAWS OR THE NATIONAL ELECTRICAL CODE, LOCAL OR STATE LAWS OR THE NATIONAL ELECTRICAL CODE SHALL GOVERN.
<br />S E R V 1 C E S
<br />NOTE: OWNER'S E.C. TO PROVIDE COLD WATER PIPE EARTH GROUND.
<br />DVR SIZE AND WEIGHT VARIES DEPENDING ON MANUFACTURER. WEIGHTS RANGE FROM
<br />WHEN WIRING IS RUN IN HOLLOW SPACES SUCH AS ABOVE SUSPENDED CEILINGS AND SUCH HOLLOW SPACES ARE USED FOR
<br />2. ENVIRONMENTAL AIR - HANDLING PURPOSES, THE WIRING MUST EITHER BE LISTED FOR SUCH PURPOSES
<br />6 LBS TO 30 LBS.
<br />OR BE INSTALLED IN
<br />ELECTRICAL METALLIC TUBING, FLEXIBLE METALLIC TUBING, INTERMEDIATE METAL CONDUIT, RIGID METAL CONDUIT, METAL
<br />❑
<br />KEYPAD
<br />POWER SOURCE: 12 VDC FROM ALARM PANEL
<br />POWER SOURCE: OWNER'S E.C. TO PROVIDE (1) 21/8" X 4" X 1 1/8" STANDARD OUTLET BOX
<br />SURFACE RACEWAY OR WIREWAY WITH METAL COVERS WHERE ACCESSIBLE OR FLEXIBLE METAL CONDUIT. (SEE SECTION
<br />CANTON OFFICE
<br />E.C. TO PROVIDE (1) 4" X 4" X 21/8" STANDARD OUTLET BOX FOR MOUNTING. INSTALL
<br />MONITOR (120 VAC, 60 HZ, 20 AMP, UNSWITCHED) WITHIN T -0" OF UNIT.
<br />300 -22 (C) NATIONAL ELECTRICAL CODE).
<br />OUTLET BOX CENTERED T -9" TO FINISHED FLOOR. (MEETS ADA REQUIREMENTS)
<br />3. EXISTING ALARM AND CAMERA WIRING MUST BE REPLACED IF ANY OF THE FOLLOWING CONDITIONS EXIST
<br />818 Mulber Road SE
<br />TYPICALLY DESK MOUNTED, HOWEVER KITS CAN BE PURCHASED FOR ALTERNATE
<br />Dept. E
<br />POWER SOURCE: OWNER'S E.C. TO PROVIDE (1) 2" X 4" X 2'/8' STANDARD OUTLET BOX
<br />INSTALLATIONS -WALL OR CEILING MOUNT.
<br />B. THE EXISTING WIRING DOES NOT HAVE THERMAL PLASTIC INSULATION
<br />Canton, OH 44707
<br />EXTENDED POWER SUPPLY
<br />(120 VAC, 60 HZ, 20 AMP UNSWITCHED) FOR SUPPLIED TRANSFORMER AS CLOSE TO
<br />SIZE AND WEIGHT VARIES BY MANUFACTURER. WEIGHT CAN BE 65 LBS OR MORE
<br />C. THE EXISTING WIRING DOES NOT HAVE SUFFICIENT CONDUCTORS
<br />(FOR 48 AND 80 HOURS)
<br />CABINET AS POSSIBLE. DISTANCE SHOULD NOT EXCEED 50' -0" FROM CABINET.
<br />D. THE EXISTING WIRING SIZE DOES NOT MEET DIEBOLD SPECIFICATIONS
<br />MOUNT CABINET FROM REAR MOUNTING HOLES.
<br />POWER SOURCE: 12 VDC OR 24 VAC PROVIDED BY THE VIDEO POWER SUPPLY. SPLIT
<br />E. THE EXISTING CAMERA AND HOLD -UP DEVICE WIRING ARE RUN IN THE SAME SHIELDED CABLE BUNDLE
<br />DALLAS OFFICE
<br />ENCLOSURE MODEL: 350-17 X 13' X 3Y2"
<br />CAMERA
<br />CAMERA M -1 CABLE - COAX PORTION TO DVR AND (2) CONDUCTOR TO POWER SUPPLY.
<br />*AN EXCEPTION TO THIS RULE MAY BE MADE PROVIDING THE EXISTING WIRING IS IN PROPERLY GROUNDED METALLIC CONDUIT,
<br />350A - 17 X 133 '/z" X 3' /a"
<br />OWNER'S E.C. TO PROVIDE (1) 2 GANG FLUSH MOUNTED OUTLET 80X BEHIND EACH
<br />IS NO UNSHIELDED CAMERA WIRING IN THE SAME CONDUIT WITH ALARM WIRING AND THE WIRING MEETS ALL OTHER
<br />1221 South Beltline Road
<br />341 - 12 X 6 X 2%8'
<br />CAMERA (RECOMMENDED HEIGHT) ABOVE FINISHED FLOOR. COVERPLATE
<br />STANDARDS LISTED ABOVE. SHOULD REWIRING BE REQUIRED AT A LATER DATE TO PREVENT FALSE ALARMS WHICH ARE CAUSED
<br />Suite 700
<br />WITH BUSHED O OPENING FOR THIS BOX.
<br />BY DEFECTIVE WIRING OR RADIO FREQUENCY INTERFERENCE, SUCH REWIRING WILL BE THE RESPONSIBILITY OF THE PURCHASER.
<br />Coppell, TX 75019
<br />APPROXIMATE WEIGHT: 28 LBS.
<br />CEILING MOUNT: ABOVE FINISHED CEILING CLOSE TO MOUNTING BRACKET.
<br />INTERIOR WALL MOUNT: CENTERED ABOVE WALL BRACKET.
<br />4. ALL WIRING INCLUDING POWER, LOW VOLTAGE CONTROL AND VIDEO AS SPECIFIED:
<br />MAXIMUM DISTANCE BETWEEN ANY CAMERA AND RECORDER IS 1000' WITH COAX CABLE.
<br />MAXIMUM DISTANCE BETWEEN CAMERA AND POWER IS 350' WITH 22AWG.
<br />E]
<br />OWNER'S E.C. TO PROVIDE AND INSTALL (1) 4" X 4" X 2 JUNCTION BOX WITH COVER
<br />SAFE & CHEST ALARM
<br />AND TAMPER SWITCH BEHIND SAFE AND WITHIN 16" OF CONDUIT STUB OUT, RACK
<br />EXTERIOR WALL MOUNT: WEATHER PROOF BOX(ES) ABOVE WALL BRACKET - (1) FOR
<br />MAXIMUM DISTANCE BETWEEN CAMERA AND POWER IS 750' WITH 18AWG.
<br />ORLANDO OFFICE
<br />PROTECTION KIT
<br />BOX OR NIPPLE (VERIFY CHEST MODEL). E.C. TO PROVIDE RIGID OR FLEX METAL
<br />CAMERA WIRING, (1) FOR OPTIONAL HEATER POWER IF REQUIRED. MINIMUM OF 8' -6" TO
<br />12' -0" ABOVE FINISHED GRADE.
<br />ALL CABLE RUNS BETWEEN CAMERA AND RECORDER MUST BE "HOME RUN" WITH COAX CABLE.
<br />43 Skyline Drive
<br />CONDUIT FROM JUNCTION BOX TO STUB OUT, RACK BOX OR NIPPLE.
<br />WHERE A RUN LONGER THAN 1000' IS NEEDED, VIDEO AMPLIFIERS ARE REQUIRED.
<br />Suite 1051
<br />�
<br />POWER SOURCE: OWNERS E.C. TO PROVIDE (1) 2/8 X 4 X 1 /e „ STANDARD OUTLET BOX
<br />�
<br />5. ALL CONDUIT ENTERING A VAULT WILL BE RESTRICTED TO 1 MAXIMUM AND SHALL HAVE TWO (2) 90 BENDS WITHIN THE VAULT
<br />Lake Mary, FL 32746
<br />STEEL ENCASED: OWNER'S E.C. TO PROVIDE AND INSTALL (1) 1" DIAMETER CONDUIT
<br />AFTER HOUR DEPOSITORY
<br />FROM ALARM CONTROL PANEL TO 4" X 4" X 21/8' ALARM JUNCTION BOX (BY E.C.)
<br />VIDEO POWER SUPPLY (120 VAC, 60 HZ, 20 AMP, UNSWITCHED) DUPLEX RECEPTACLE WITHIN 6 -0 " OF UNIT.
<br />WALL STRUCTURE. ARRANGEMENT OF BENDS SHALL BE SO THAT DRAINAGE IS TO THE EXTERIOR OF THE VAULT. WHEN
<br />PROTECTION KIT
<br />MOUNTED IN AREA NEAR STEEL SHROUD OR ON TOP OF RECEIVING CHEST WITH
<br />DEPENDING ON MANUFACTURER UNIT MAY BE EITHER RACK OR SURFACE MOUNTED.
<br />PENETRATING AN EXISTING POURED IN PLACE VAULT, THE MAXIMUM HOLE SIZE IS 172 ". WHEN PENETRATING A MODULAR VAULT
<br />❑
<br />ADAPTER FOR FLEX CONDUIT.
<br />THE MAXIMUM HOLE SIZE IS 2" HOWEVER, MULTIPLE HOLES ARE PERMITTED AS LONG AS THEY ARE AT LEAST 7" APART.
<br />RETAIL OFFICE
<br />CONCRETE ENCASED: OWNER'S E.C. TO PROVIDE AND INSTALL (1) 1" DIAMETER
<br />SIZE AND WEIGHT VARIES BY MANUFACTURER. WEIGHTS RANGE FROM 6 LBS. TO 20 LBS.
<br />6. ONLY WIRE MEETING THE SPECIFICATIONS SET FORTH IN THE DIEBOLD ELECTRONIC SECURITY AND SURVEILLANCE CABLE
<br />261 Cedar Hill Rd.
<br />CONDUIT FROM ALARM CONTROL PANEL STUBBED OUT INTO AREA OF 6" REINFORCED
<br />SCHEDULE (FILE NO. 170 -100) MAY BE USED.
<br />Bldg. C -Ste. 8 -12
<br />CONCRETE WITH ADAPTER FOR FLEX CONDUIT. 1" DIAMETER CONDUIT ELBOW
<br />7. WHEN BUILDING HAS EMERGENCY AND /OR STANDBY POWER SYSTEM, ALL BUILDING POWER REQUIRED FOR DIEBOLD EQUIPMENT
<br />Marlborough, MA 01752
<br />WELDED TO SAFE WITH 1" DIAMETER FLEX CONDUIT AND ADAPTERS TO TERMINAL
<br />SHALL BE CONNECTED TO THAT SYSTEM.
<br />RACK BOX. TERMINAL RACK BOX (BY DIEBOLD), BUT INSTALLED BY OWNER' E.C.
<br />8. SMOKE DETECT ORS ARE TO BE USED AS INTRUSION AND VANDALISM DETECTORS ONLY. THEY ARE NOT INTENDED FOR LIFE
<br />SAFETY PROTECTION OR TO MEET LOCAL OR NATIONAL FIRE CODES.
<br />THIS DRAWING I S THE PROPERTY OF DIEBOLD INCORPORATED
<br />( c) COPYRIGHT2007 Diebold. Inc. All Rights Reserved
<br />An unpublished Work.
<br />ATM PROTECTION KIT
<br />OWNER'S E.C. TO PROVIDE (1) 4" X 4" X 2%" JUNCTION BOX WITH COVER AND TAMPER
<br />SWITCH ON HINGE SIDE OF ATM CHEST WITHIN 6-0" OF CONNECTION PLATE IN AN
<br />9. MOUNTING HEIGHTS FOR RECEPTACLES PER STATE, LOCAL OR NATIONAL ELECTRICAL CODE.
<br />ACCESSIBLE AREA. BOX CAN BE FLUSH MOUNTED WITH CONCEALED CONDUIT FOR
<br />10. SHELVES OR CABINET TO HOUSE VIDEO COMPONENTS BY OWNER.
<br />This document is intended solely for the purpose of
<br />providing information to aid in the preparation of a site for
<br />NEW CONSTRUCTION OR SURFACE MOUNTED WITH EXPOSED CONDUIT FOR EXISTING
<br />3
<br />11. CAMERA RECEPTACLE REQUIREMENTS MAY BE REDUCED BY USING A 12 VDC POWER DISTRIBUTION MODULE (60 WATTS MAX,
<br />he installation of Diebold equipment. It may include
<br />CONSTRUCTION. OWNER'S E.C. TO RUN 3 /s" LIQUID TIGHT FLEX METAL CONDUIT OR /a"
<br />r
<br />2.5 AMPS) NOTE: EACH HAS TWO SETS OF TERMINAL BLOCKS FOR MULTIPLE CAMERA CONNECTIONS.
<br />openings equipment specifications, clearances/service
<br />areas electrical requirements and preferred installation
<br />RIGID CONDUIT FROM JUNCTION BOX TO CABLE CONNECTING PLATE.
<br />methods. Diebold Product Application Services (PAS)
<br />TRANSACTION CAPTURE BY ETHERNET REQUIRES (1) CAT 5 CABLE FROM ATM TO
<br />DIEBOLD INSTALLERS
<br />designers are not licensed architects /engineers but may
<br />offer recommendations relating to Diebold product
<br />NETWORK CONNECTION. LOCAL TRANSACTION CAPTURE REQUIRES 1
<br />( ) C CABLE FROM
<br />placement/installation. The customers architect is solely
<br />ATM TO DVR. THERE WILL ALWAYS BE A CAT 5 REQUIRED, THE C CABLE IS ONLY NEEDED
<br />responsible for final construction design, permitting or
<br />IF TRANSACTION CAPTURE IS DONE LOCALLY.
<br />12. LOCATION OF DEVICES AND CAMERAS ARE NOT TO INTERFERE WITH PARTITION WALLS, INTERIOR LIGHTING, SWITCHES ETC.
<br />inspections required by local authorities for approval.
<br />13. THE FOLLOWING WORK RELATED TO ELECTRONIC SECURITY EQUIPMENT WILL BE COMPLETED BY DIEBOLD INSTALLERS
<br />OWNER'S E.C. TO PROVIDE (1) 2'/8' X 4" X 1 1/8' STANDARD JUNCTION BOX WITH COVER
<br />...INSTALLATION AND ADJUSTMENT OF ALL DIEBOLD FURNISHED EQUIPMENT UNLESS OTHERWISE SPECIFIED
<br />Revisions:
<br />DOOR CONTACT
<br />ABOVE CEILING, STUB CONDUIT INTO SECURE SIDE OF DOOR OPENING. RADIO
<br />...CAMERA MOUNTING BRACKETS, AS WELL AS THE TESTING AND ADJUSTMENT OF CAMERAS AND ENTIRE SYSTEM AS REQUIRED
<br />FREQUENCY DEVICE POWERED BY INTERNAL BATTERY.
<br />...ACTUAL AIM OF CAMERAS AND PASSIVE INFRARED DEVICES. DEVICES SHOWN ON PLAN ARE FOR ILLUSTRATION PURPOSES
<br />NOTE: MOUNT DOOR CONTACT OR WIRELESS TRANSMITTER 2" TO 5" FROM TOP EDGE
<br />...MOUNTING AND CONNECTION OF ALL CAMERAS TO CABLES AND CONNECTION OF CABLES TO SYSTEM
<br />OF SWING SIDE OF DOOR (OPPOSITE HINGE SIDE)
<br />LOW VOLTAGE CABLE REQUIREMENTS
<br />MOUNTING REQUIREMENT FOR SUSPENDED CEILING OR STEEL LINING: OWNER'S E.C. TO
<br />SOUND DETECTOR INTERFACE
<br />PROVIDE (1) 4" X 4" X 2'/8' JUNCTION BOX SURFACE MOUNTED ON VAULT CEILING PANEL
<br />WITH RIGID OR FLEX METAL CONDUIT TO 2'/8" X 4" X 11%" JUNCTION BOX SURFACE
<br />14. ALL WIRING SHALL BE TAGGED AT ALL JUNCTION POINTS AND SHALL TEST FREE FROM BREAKS, GROUNDS, SHORTS AND /OR
<br />MOUNTED ON SUSPENDED CEILING. SOUND DETECTOR INTERFACE MOUNTS TO
<br />CROSSES BETWEEN CONDUCTORS. DO NOT LABEL CONDUITS.
<br />JUNCTION BOX ON SUSPENDED CEILING.
<br />15. ALARM AND CAMERA WIRING CAN NOT BE RUN IN THE SAME CONDUIT WITH 120 VOLT AND ABOVE POWER WIRING, LOW VOLTAGE
<br />ALTERNATE MOUNTING REQUIREMENT: SURFACE MOUNT SOUND DETECTOR INTERFACE
<br />WIRING OF 30 VOLTS AND ABOVE OR TELEPHONE LINES.
<br />TO VAULT CEILING PANEL. USE WIREMOLD TO RUN CABLES.
<br />16. MINIMUM OF 2' -0" WIRE STUB -OUT AT ALL JUNCTION BOXES DESIGNATED FOR CONNECTION OF DEVICES, CABINETS, OR FOR
<br />SPLICING, UNLESS OTHERWISE SPECIFIED.
<br />MOUNTING REQUIREMENT FOR SUSPENDED CEILING OR STEEL LINING: OWNER'S E.C.
<br />SOUND DETECTOR
<br />TO PROVIDE (1) 2'/e" X 4" X 1 1/8" JUNCTION BOX FOR EACH SOUND DETECTOR, SURFACE
<br />MOUNTED ON VAULT CEILING PANEL WITH RIGID OR FLEX METAL CONDUIT TO2Ya "X4"
<br />OWNERS ELECTRICAL CONTRACTOR (E .C.) TO
<br />X 1 Ye" JUNCTION BOX SURFACE MOUNTED ON SUSPENDED CEILING. SOUND DETECTOR
<br />MOUNTS TO JUNCTION BOX ON SUSPENDED CEILING.
<br />...PROVIDE ALL POWER.
<br />ALTERNATE MOUNTING REQUIREMENT: SURFACE MOUNT SOUND DETECTOR TO VAULT
<br />...PROVIDE ALL CONDUITS AND ELECTRICAL BOXES FOR ALARM AND VIDEO DEVICES. THEY ARE ALSO TO DETERMINE ACTUAL SIZE
<br />CEILING PANEL. USE WIREMOLD TO RUN CABLES.
<br />AND ROUTING OF CONDUIT TQ SUIT LOCAL CONDITIONS, AS WELL AS DETERMINE THE NEED FOR LARGER CONDUIT SIZES BASED
<br />NOTE: SOUND DETECTOR ADD ON KIT REQUIRED FOR DEAD AIR SPACE WITH A
<br />ON NATIONAL ELECTRICAL CODE STANDARDS. THE MINIMUM CONDUIT SIZE ALLOWED IS %" AND THE MAXIMUM CONDUIT SIZE
<br />SUSPENDED CEILING.
<br />ALLOWED IS 1 FOR ALARM CABLES. ALL CONDUIT RUNS SHALL HAVE SWEEPING BENDS AND ANY RUNS 1`FiAT MAY FORM A
<br />WATER TRAP MUST BE PROVIDED WITH DRAINAGE HOLES.
<br />Z
<br />OWNER'S E.C. TO PROVIDE (1) 4" X 4" X 21/8' JUNCTION BOX WITH FLAT COVER ABOVE
<br />...DETERMINE THE SIZE REQUIRED AND PROVIDE AND INSTALL A MAIN PULL BOX IN AN ACCESSIBLE AREA. CABLES FROM
<br />VAULT DOOR PROTECTION KIT
<br />DOOR HEADER PANEL.
<br />DEVICES DO NOT TERMINATE AT THIS BOX THEY ARE PULLED THROUGH TO THE MAIN ALARM PANEL.
<br />O
<br />MODULAR VAULT: STUB OUT 1 /2" CONDUIT IN DOOR HEADER PANEL
<br />...VERIFY ALL NATIONAL, STATE AND LOCAL CODES FOR MULTI -STORY BUILDING COMPLIANCE AND PROVIDE ALL NECESSARY
<br />POURED VAULT: OWNER'S E.C. TO INSTALL A JUNCTION BOX FLUSH MOUNTED INSIDE
<br />OPENINGS AND FILLS FOR FLOOR TO FLOOR WIRING TO MEET CODE,
<br />VAULT ABOVE VAULT DOOR OPENING. CENTER OF BOX 4" TO LEFT OF CENTER OF VAULT
<br />...PROVIDE PULL STRINGS FOR ALL CONDUIT RUNS.
<br />DOOR OPENING AND 4" ABOVE VAULT DOOR OPENING HEADER. (2) %" METAL CONDUITS
<br />...PROVIDE ENOUGH RECEPTACLES TO SUPPLY POWER TO THE MONITOR, SWITCHER, STEPDOWN TRANSFORMERS AND ONE
<br />Q O
<br />FROM JUNCTION BOX STUBBED OUT 1" THROUGH HEADER WITH STANDARD THREADS.
<br />SPARE. ALL RECEPTACLES FOR VIDEO EQUIPMENT MUST BE ON THE SAME POWER PHASE.
<br />...PROVIDE A 6" SQUARE JUNCTION BOX FOR VIDEO CABLES.
<br />0
<br />' ; _J LL
<br />INOVONICS FA401, FA404 POWER PROVIDED BY ALARM PANEL OR AUXILIARY POWER SUPPLY VIA KEYPAD BUS.
<br />INOVONICS FA416, FA
<br />MOUNTING RECOMMENDATIONS: WHEN POSSIBLE MOUNT RECEIVER CENTRAL TO
<br />...PROVIDE ALL DEVICES LOCATED IN FIRE RATED AREAS WITH CONDUIT STUB -UPS AND PULL STRINGS TO EXTERIOR OF FIRE RATED
<br />o
<br />FREQUENCY AGILE (FA) NOT COMPATIBLE
<br />TRANSMITTERS. MOUNT AWAY FROM LARGE METAL OBJECTS WHEN POSSIBLE.
<br />AREA.
<br />>.,. J
<br />J
<br />WITH ECHOSTREAM (EN) ALARM
<br />PERFORMANCE WILL BE IMPAIRED IF MOUNTED ON A METAL SURFACE.
<br />-J
<br />DEVICES
<br />UNIT CAN BE SCREW MOUNTED THROUGH HOLES IN CORNERS OF HOUSING BASE.
<br />}
<br />W o a
<br />3!c N N
<br />POWER PROVIDED BY ALARM PANEL OR AUXILIARY POWER SUPPLY. RADIO FREQUENCY
<br />360 PASSIVE INFRARED
<br />DEVICE POWERED BY INTERNAL BATTERY.
<br />ti
<br />FLUSH MOUNT: USE PROVIDED MOUNTING KIT
<br />SURFACE MOUNT: UNIT CAN BE SCREW MOUNTED THROUGH HOLES IN BACK PLATE
<br />NOTE: IF UNIT IS MOUNTED OUTSIDE OF RECOMMENDED HEIGHT RANGE OF 8' -0" TO 16'4"
<br />Project No D22109
<br />SENSITIVITY WILL BE REDUCED.
<br />Date 8 -25 -09
<br />POWER PROVIDED BY ALARM PANEL OR AUXILIARY POWER SUPPLY. RADIO
<br />PASSIVE INFRARED
<br />FREQUENCY DEVICE POWERED BY INTERNAL BATTERY.
<br />'awn By VLW
<br />FLUSH MOUNT: USE PROVIDED MOUNTING KIT
<br />Requested ByDIANE ZABIK
<br />SURFACE MOUNT: UNIT CAN BE SCREW MOUNTED THROUGH HOLES IN BACK PLATE
<br />OPTIMAL MOUNTING HEIGHT VARIES BETWEEN 6-10" AND 8' -0" DEPENDING ON
<br />Order No B# 687651
<br />MANUFACTURER.
<br />Scale AS NOTED
<br />POWER PROVIDED BY ALARM PANEL.
<br />Sheet Title
<br />ALARM LAMP SURFACE MOUNT ON VERTICAL WALL VISIBLE BY EMPLOYEES (KEEP SIGNAL AWAY
<br />FROM PUBLIC VIEW). MOUNTING HEIGHT WILL VARY DEPENDING ON SITE CONDITIONS,
<br />TYPICALLY 5' -0" ABOVE FINISHED FLOOR.
<br />ELECTRONIC
<br />SECURITY
<br />SPECS /NOTES
<br />Drawing Number
<br />ES -2
<br />02 of 09