FIRE INSPECTION REQUIREMENT NOTES= <br />(1) CERTIFIED FIRE EXTINGUISHERS SHALL BE <br />INSTALLED ACCORDANCE WITH NFPA 10 <br />AND SHALL BE INSTALLED WITHIN 75' OF <br />TRAVEL DISTANCE, <br />(2) PANIC HARDWARE SHALL BE ON EXIT <br />DOORS <br />(3) AN ASSEMBLY PERMIT WILL NEED TO BE <br />OBTAINED BY OCCUPANT, <br />(4) ENSURE FIRE RATED WALLS (ADJACENT UNITS) <br />ARE SEALED AT ROOF DECK AND ANY <br />PENETRATIONS ARE PROPERLY SEALED TO <br />MAINTAIN THE 1 HOUR FIRE RATING <br />(5) IF A/C UNITE ARE 2000 Cr-M'S OR MORE, DUCT <br />DETECTORS WILL BE REQUIRED WITH REMOTE <br />KEY SWITCH TO RESET UNITS <br />TOTAL AREA UNDER ROOF <br />11138 60, FT, <br />OCCUPANCY LOAD CALCULATIONS <br />JAZZERCISE AREA <br />1225 SQ, FT. / 50 GROSS = 25 PEOPLE <br />EXERCISE AREA WITH EQUIPMENT <br />6861 $0, FT, / 50 GROSS - 138 PEOPLE <br />ALL STORAGE AREAS <br />20,3 SQ, FT, / 300 GROSS = l PEOPLE <br />OFFICE AREAS (BUSINESS) <br />160 50, FT, / 100 GROSS - 2 PEOPLE <br />ALL RESTROOMS <br />165 50, FT, NOT IN OCCUPANCY LOAD <br />CALCULATIONS <br />RECEPTION AREA (BUSINESS) <br />200 SQ, FT, / 100 GROSS ■ 2 PEOPLE <br />MECHANICAL t ELECTRICAL AREAS <br />436 $0, FT, / 300 GROSS - 2 PEOPLE <br />TOTAL OCCUPANT LOAD 116 PEOPLE <br />TING 8" BLOCK WALL <br />OPEN TO BELOW <br />RAILING <br />EXISTING <br />STORAGE MEZZANINE <br />0 <br />1515 SQ. FT, <br />NO CHANGE TO TN(S AREA <br />NURSERY <br />542 SQ, FT, <br />EXISTING STAIRS DOWN TO <br />MAIN LEVEL AREA NOT SHOWN <br />, <br />, <br />, <br />EX15TING INTERIOR SECOND LEVEL 1=LOOR FLAN 311ro" = V O <br />i---- EXISTING 8" BLOCK WALL <br />CLOSET <br />n 54 SQ, FT, o <br />REMOVE EXISTING FRAME LVALL AT THIS AREA <br />EXISTING STEEL SUPPORT <br />COLUMNS, LOCATION IS <br />- - - - APPROXIMATE Cv <br />------- - - - - -- ---------------- - - - - -- ---- - - - - -- ----------------------------------------------------------------- <br />---------------------------------------------------------------------- 0------------------------------- ---o------- - - - - -- <br />41' O" <br />V <br />z <br />9 <br />m <br />F <br />U1 <br />U <br />z <br />a <br />O <br />lX � <br />A � <br />z <br />U <br />z <br />O <br />JAZZERCISE AREA <br />1224 80, FT, / 50 GROSS ■ 25 PEOPLE <br />NEW FULL HEIGHT WALLS BUTT TIGHT <br />TO BOTTOM OF EXISTING DROP CEILING <br />16" TALL WALLS --- \ <br />TREADMILL AREA I I TREADMILL AREA <br />TREADMILL AREA <br />INCLUDED IN EXERCISE (I INCLUDED IN EXERCISE I I INCLUDED IN EXERCISE <br />AREA WITH EQUIPMENT AREA WITH EQUIPMENT AREA WITH EQUIPMENT <br />HALLWAY <br />186 SQ, FT, <br />OPENING <br />6'O "X6'8" INTERIOR DOOR <br />WITH BALL CATCH LATCH <br />SYSTEM, EACH DOOR TO <br />BE ACTIVE <br />EXERCISE AREA WITH EQUIPMENT <br />6861 6Q, Ft, <br />RAILING <br />STORAGE <br />492 SQ, FT, <br />ELECTRICAL ROOM TO HAVE <br />EXISTING STAIRS UP TO O H OU R <br />EE TE D WALL AND <br />CLOSET STORAGE MEZZANINE AREA CUSTOM DOOR TO FIT 48 X82 <br />NOT SHOWN R.O., VERIFY IN FIELD, DOOR <br />28 50, FT, Z ETO HAVE PANIC HARDWARE <br />EXISTING 8" BLOCK WALL <br />EXISTING <br />MECHANICAL ROOM <br />375 SQ, Ft, <br />EXISTING ELECTRICAL PANELS <br />EXCEED REQUIREMENTS FOR <br />NEW TENANT. <br />�z <br />O <br />U <br />�u� <br />a <br />o u . <br />�a=LLJ <br />�$ °a <br />�Qaq <br />a <br />t�oa7 <br />ELECTRICAL RM <br />3'0" X 6'8" ONE HOUR [ 63 SQ, FT, <br />FIRE RATED HOLLOW <br />METAL DOOR 4 FRAME <br />WOMENS <br />41,5" 3'011 4V 211 <br />O r . <br />Lo <br />3' 4 <br />4 ��„ <br />i <br />v <br />0 <br />c OI <br />R <br />It <br />23' O" <br />CUT FLOOR AS NEED TO INSTALL NEW PLUMBING DRAIN <br />LINES FROM NEW FIXTURES TO CONNECT TO EXISTING <br />DRAIN LINES, PATCH FLOOR <br />I w 3' 4" <br />'5z <br />Q <br />z� <br />P� <br />�o <br />i � t <br />34'6" <br />14' O" <br />0 O" <br />16' 1i 2 <br />3'0 "X6'S" <br />I • <br />RECEPTION AREA <br />200 3Q, FT, <br />EXISTING EXISTING <br />OFFICE OFFICE <br />160 So, FT, <br />I • <br />IT 10 <br />(1) DROP CEILING METAL GRID AND TILE SYSTEM ( NO CHANGE ) <br />(2) CEILING MOUNT FLUORESCENT LIGHT FIXTURES ( NO CHANGE ) <br />(3) RECEPTACLES EXISTING ( NO CHANGE ) <br />(4) LIGHTED EXIT SIGNS AND EMERGENCY LIGHTS SHOWN ARE <br />EITHER NEW OR EXISTING, ALL FIXTURES TO HAVE BATTERY <br />BACK UP. <br />(5) H.V.A.C. UNITS TO BE REPLACED. EXISTING DUCT SYSTEM TO <br />REMAIN. H,V.A.C, CONTRACTOR TO ADD VENTS AS NEEDED <br />IN NEW AREAS, <br />TING 8" BLOCK WALL <br />REVISED INt1 ERROR MAIN LEVEL r-LOOR PLAN 311 (o" = V O" <br />x <br />r <br />o <br />SO SQ, FT, <br />- <br />4 y2" 0 <br />EXISTING <br />EXISTING <br />5' Iy2„ <br />31 IV2 <br />MENS <br />8 „ <br />5yz <br />E o <br />LA 3' O" I <br />X <br />4�i" <br />cc <br />X <br />MENS <br />� <br />4' <br />in <br />3' O" <br />eENCu <br />ELECTRICAL ROOM TO HAVE <br />EXISTING STAIRS UP TO O H OU R <br />EE TE D WALL AND <br />CLOSET STORAGE MEZZANINE AREA CUSTOM DOOR TO FIT 48 X82 <br />NOT SHOWN R.O., VERIFY IN FIELD, DOOR <br />28 50, FT, Z ETO HAVE PANIC HARDWARE <br />EXISTING 8" BLOCK WALL <br />EXISTING <br />MECHANICAL ROOM <br />375 SQ, Ft, <br />EXISTING ELECTRICAL PANELS <br />EXCEED REQUIREMENTS FOR <br />NEW TENANT. <br />�z <br />O <br />U <br />�u� <br />a <br />o u . <br />�a=LLJ <br />�$ °a <br />�Qaq <br />a <br />t�oa7 <br />ELECTRICAL RM <br />3'0" X 6'8" ONE HOUR [ 63 SQ, FT, <br />FIRE RATED HOLLOW <br />METAL DOOR 4 FRAME <br />WOMENS <br />41,5" 3'011 4V 211 <br />O r . <br />Lo <br />3' 4 <br />4 ��„ <br />i <br />v <br />0 <br />c OI <br />R <br />It <br />23' O" <br />CUT FLOOR AS NEED TO INSTALL NEW PLUMBING DRAIN <br />LINES FROM NEW FIXTURES TO CONNECT TO EXISTING <br />DRAIN LINES, PATCH FLOOR <br />I w 3' 4" <br />'5z <br />Q <br />z� <br />P� <br />�o <br />i � t <br />34'6" <br />14' O" <br />0 O" <br />16' 1i 2 <br />3'0 "X6'S" <br />I • <br />RECEPTION AREA <br />200 3Q, FT, <br />EXISTING EXISTING <br />OFFICE OFFICE <br />160 So, FT, <br />I • <br />IT 10 <br />(1) DROP CEILING METAL GRID AND TILE SYSTEM ( NO CHANGE ) <br />(2) CEILING MOUNT FLUORESCENT LIGHT FIXTURES ( NO CHANGE ) <br />(3) RECEPTACLES EXISTING ( NO CHANGE ) <br />(4) LIGHTED EXIT SIGNS AND EMERGENCY LIGHTS SHOWN ARE <br />EITHER NEW OR EXISTING, ALL FIXTURES TO HAVE BATTERY <br />BACK UP. <br />(5) H.V.A.C. UNITS TO BE REPLACED. EXISTING DUCT SYSTEM TO <br />REMAIN. H,V.A.C, CONTRACTOR TO ADD VENTS AS NEEDED <br />IN NEW AREAS, <br />TING 8" BLOCK WALL <br />REVISED INt1 ERROR MAIN LEVEL r-LOOR PLAN 311 (o" = V O" <br />O� <br />3 <br />g <br />z�y <br />n 4e � <br />F � W <br />a <br />0 <br />0� <br />Qa <br />►- Q <br />d <br />O <br />mu <br />ZQ <br />z <br />SL)a <br />�3 <br />4 <br />Y <br />u <br />0 <br />J <br />m <br />iA <br />z <br />�y <br />N� <br />^ W <br />�QN <br />N.i <br />C�R Gp <br />y� <br />Q-0CW� M <br />M <br />hZ�p V <br />2oNoD C4 t W <br />�H°W <br />0 <br />F= <br />O � <br />Z Q <br />ID <br />-A <br />N O <br />a <br />z � o <br />z <br />Q <br />0 � <br />V A <br />O � ll1 <br />—U <br />0 <br />t <br />1-- <br />FIG <br />2 OF: .4 <br />RESTROOMS <br />\ <br />SO SQ, FT, <br />30 <br />EXISTING <br />EXISTING <br />WOMENS <br />MENS <br />0� <br />E o <br />O� <br />3 <br />g <br />z�y <br />n 4e � <br />F � W <br />a <br />0 <br />0� <br />Qa <br />►- Q <br />d <br />O <br />mu <br />ZQ <br />z <br />SL)a <br />�3 <br />4 <br />Y <br />u <br />0 <br />J <br />m <br />iA <br />z <br />�y <br />N� <br />^ W <br />�QN <br />N.i <br />C�R Gp <br />y� <br />Q-0CW� M <br />M <br />hZ�p V <br />2oNoD C4 t W <br />�H°W <br />0 <br />F= <br />O � <br />Z Q <br />ID <br />-A <br />N O <br />a <br />z � o <br />z <br />Q <br />0 � <br />V A <br />O � ll1 <br />—U <br />0 <br />t <br />1-- <br />FIG <br />2 OF: .4 <br />