Laserfiche WebLink
Zephyrhills Fire Rescue <br /> 6907 Dairy Road, Zephyrhills, FL 33542 <br /> Fire Marshal Bus (81 3) 780 -0041 <br /> Kerry Barnett Fax (813) 780 -0044 <br /> E-mail: k.barnett@fire.zephyrhi I ls. fl .us <br /> Plan Review #: 09 -110 <br /> Project: Fire Sprinkler Installation <br /> Number of Pages: 1 <br /> December 21, 2009 <br /> I have received and reviewed the plans for the installation of a fire sprinkler system <br /> located at 4241 Sky Dive Lane and will allow the project to move forward. Please note <br /> that this review does not eliminate any further requirements as the project continues <br /> moving forward. By receiving permit, contractor acknowledges to comply with the items <br /> listed below. Should anyone have any questions, please do not hesitate to contact the Fire <br /> Marshal's office. <br /> 1. Provide license to show company is certified to install the underground. <br /> 2. Provide spec /cut sheets on all (sprinkler heads, DCVA, FDC, piping, valves, <br /> etc...) this was noted on the previous review. <br /> 3. Tamper switches required on double backflow assembly. <br /> 4. FDC Sign to be posted at FDC location. Sign to be minimum 6' high with 6" <br /> red reflective letters "FDC" on white background. <br /> 5. Thrust blocking shall be used on underground. Blocking shall be formed in a <br /> wedge style. <br /> 6. Riser shall not be obstructed. Owner may want to install a chain link fence <br /> around riser to prevent obstruction and /or tampering. <br /> NOTE: #1 and #2 are required prior to work being started. Sheets can be faxed to number <br /> at top of this comment sheet. <br />