Laserfiche WebLink
INTREPID FIRE PROTECTION, LLC <br /> 314 EAST AZALEA AVE. <br /> TAMPA, FL 33612 <br /> HYDRAULIC CALCULATIONS FOR: <br /> ZEPHYRHILLS FIRE STATION #2 ATTIC AREA <br /> DATE: 1 -17 -2010 <br /> - DESIGN DATA - <br /> OCCUPANCY CLASSIFICATION: LIGHT HAZARD <br /> DENSITY: .10 gpm/sq. ft. <br /> AREA OF APPLICATION: 1130 SQ. FT. <br /> COVERAGE PER SPRINKLER: 120 s.£ <br /> NUMBER OF SPRINKLERS CALCULATED: 10 sprinlders <br /> TOTAL SPRINKLER WATER FLOW REQUIRED: 171.9 gpm <br /> TOTAL WATER REQUIRED (including hose): 429.1 gpm <br /> FLOW AND PRESSURE (@ Base of Riser.): 171.9 gpm @ 40.8 psi <br /> SPRINKLER ORIFICE SIZE: 1/2" (k = 5.6 ) <br /> JAMES M. CURTIS #37912 <br /> NAME OF CONTRACTOR: Intrepid Fire Protection LLC 8 di 99 - 11 AX 352 - - 1196 <br /> DESIGN/LAYOUT BY: PMC 010 <br /> h hills Fire Department <br /> 29775 I Y , FL <br /> AUTHORITY HAVING JURISDICTION: Ze 33523 <br /> 52 <br /> Zephyrhills p DADS CITY, FL 33523 <br /> CONTRACTOR CERTIFICATION NUMBER: 85858000012007 <br /> CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE # 329L746 ) <br /> HRS SYSTEMS, INC. ATLANTA, GA <br />