TFP151 Page 7 of 8
<br /> addition to the standards of any other - •
<br /> Care and authorities having jurisdiction. The in- Li
<br /> stalling contractor or sprinkler manu- w arranty
<br /> Maintenance facturer should be contacted relative to
<br /> any questions.
<br /> The Series TY B Sprinklers must be Products manufactured by Tyco Fire
<br /> maintained and serviced in accord- It is recommended that automatic Products are warranted solely to the
<br /> sprinkler systems be inspected, original Buyer for ten (10 inal Bu
<br /> ance with the following instructions: a qualified g y ( ) y ears
<br /> tested, and maintained b
<br /> Y q against defects in material and work -
<br /> NOTES Inspection Service. manship when paid for and properly
<br /> Before closing a fire protection system installed and maintained under normal
<br /> main control valve for maintenance use and service. This warranty will ex-
<br /> work on the fire protection system that pire ten (10) years from date of ship -
<br /> it controls, permission to shut down the ment by Tyco Fire Products. No war -
<br /> affected fire protection system must be ranty is given for products or
<br /> obtained from the proper authorities components manufactured by compa-
<br /> and all personnel who may be affected nies not affiliated by ownership with
<br /> by this action must be notified. Tyco Fire Products or for products and
<br /> Absence of an escutcheon, which is components which have been subject
<br /> to misuse, improper installation,
<br /> used to cover a clearance hole, may aped,
<br /> delay the time to sprinkler operation in sion, or which have not been installed,
<br /> a fire situation. maintained, modified or repaired in ac-
<br /> cordance with applicable Standards of
<br /> Sprinklers that are found to be leaking the National Fire Protection Associa-
<br /> or exhibiting visible signs of corrosion tion, and /or the standards of any other
<br /> must be replaced. Authorities Having Jurisdiction. Mate -
<br /> Automatic sprinklers must never be rials found by Tyco Fire Products to be
<br /> P defective shall be either repaired or
<br /> painted, plated, coated or otherwise replaced, at Tyco Fire Products' sole
<br /> altered after leaving the factory. Modi- option. Tyco Fire Products neither as-
<br /> fied sprinklers must be replaced. sumes, nor authorizes any person to
<br /> Sprinklers that have been exposed to assume for it, any other obligation in
<br /> corrosive products of combustion, but connection with the sale of products or
<br /> have not operated, should be replaced parts of products. Tyco Fire Products
<br /> if they cannot be completely cleaned shall not be responsible for sprinkler
<br /> by wiping the sprinkler with a cloth or system design errors or inaccurate or
<br /> by brushing it with a soft bristle brush. incomplete information supplied by
<br /> Care must be exercised to avoid dam- Buyer or Buyer's representatives.
<br /> age to the sprinklers - before, during, IN NO EVENT SHALL TYCO FIRE
<br /> and after installation. Sprinklers dam- PRODUCTS BE LIABLE, IN CON -
<br /> aged by dropping, striking, wrench TRACT, TORT, STRICT LIABILITY OR
<br /> twist/slippage, or the like, must be re- UNDER ANY OTHER LEGAL THE -
<br /> placed. Also, replace any sprinkler that ORY, FOR INCIDENTAL, INDIRECT,
<br /> has a cracked bulb or that has lost SPECIAL OR CONSEQUENTIAL
<br /> liquid from its bulb. (Ref. Installation DAMAGES, INCLUDING BUT NOT
<br /> Section). LIMITED TO LABOR CHARGES, RE-
<br /> Frequent visual inspections are rec- GARDLESS OF WHETHER TYCO
<br /> ommended to be initially performed for FIRE PRODUCTS WAS INFORMED
<br /> corrosion resistant coated sprinklers, ABOUT THE POSSIBILITY OF SUCH
<br /> after the installation has been com- DAMAGES, AND IN NO EVENT
<br /> pleted, to verify the integrity of the cor- SHALL TYCO FIRE PRODUCTS' LI-
<br /> rosion resistant coating. Thereafter, ABILITY EXCEED AN AMOUNT
<br /> annual inspections per NFPA 25 EQUAL TO THE SALES PRICE.
<br /> should suffice; however, instead of in- THE FOREGOING WARRANTY IS
<br /> specting from the floor level, a random MADE IN LIEU OF ANY AND ALL
<br /> sampling of close -up visual inspec- OTHER WARRANTIES EXPRESS OR
<br /> tions should be made, so as to better IMPLIED, INCLUDING WARRANTIES
<br /> determine the exact sprinkler condi- OF MERCHANTABILITY AND FIT -
<br /> tion and the long term integrity of the JVESS FOR A PARTICULAR PUR-
<br /> corrosion resistant coating, as it may POSE.
<br /> be affected by the corrosive conditions
<br /> present.
<br /> The owner is responsible for the in-
<br /> spection, testing, and maintenance of
<br /> their fire protection system and de-
<br /> vices in compliance with this docu-
<br /> ment, as well as with the applicable
<br /> standards of the National Fire Protec-
<br /> tion Association (e.g., NFPA 25), in
<br />
|