Laserfiche WebLink
. • <br /> • <br /> tsp t Y rti:,, 5 ZEPHYRHILLS FIRE DEPARTMENT <br /> _ Zephyrhills Florida 34248 <br /> -. 700 6th Avenue (813) 782 -8184 <br /> October 29, 1986 <br /> } i n Chief ACLF <br /> T. Fenton Page 1 of 3 <br /> . : !;; +,t Chief Casson, Inc. - Contractor <br /> };+ rt Hartwig Project Name: LTC Care Center <br /> Location: Dairy Road - Behind K -Mart <br /> 1. Need total sq. ft.under roof. ` 'l1 f - c Sy • <br /> 2. (a) Occupant load including staff. /6-V <br /> (b) Total number of beds. /es <br /> Sheet 2 (a) Each wing over 7,000 sq. ft. <br /> Need attic separation with 1 hr. fire rating (floor to underside of <br /> roof and extending out through oberhanger. <br /> (b) Need access panels to attic each side of rated seperations. <br /> ete- <br /> (c) One hour fire rated smoke walls (partitions) at each wing <br /> with automatic release smoke doors - all rate0 walls smoke <br /> and fire shall have 5/8" type X each side. Fire rating of <br /> of doors in rated walls and corridors? WLL. 2c. w►.y <br /> on <br /> 8 • <br /> (d) Kitchen hazard and maintenance hazard area - shall be 1 hr. <br /> fire rated. o <br /> (e) Where is sprinkler and control room? <br /> '77=3-64' <br /> Sheet 3 (a) Need fire rating(s) of all carpets - minimum class B <br /> flame spread. a <br /> 3 —e <br />