Laserfiche WebLink
HYDRAULIC CALCULATIONS <br /> FOR <br /> SUNBELT LIVING CENTER <br /> DESIGN AREA 1 $*1\ <br /> PASCO COUNTY, FLORIDA <br /> DATE: 11 -06 -96 <br /> DESIGN DATA: NURSING HOME DESIGN AREA 1 <br /> OCCUPANCY CLASSIFICATION: LIGHT HAZARD <br /> DENSITY: .10 GPM / SQ. FT. <br /> AREA OF APPLICATION: 1500 SQ. FT. <br /> MAXIMUM COVERAGE PER SPRINKLER: 225 SQ. FT. <br /> ACTUAL COVERAGE PER SPRINKLER: VARY SQ. FT. <br /> NUMBER OF SPRINKLERS CALCULATED: 12 SPRINKLERS <br /> TOTAL WATER REQUIRED AT CITY CONNECTION: 316 GPM @ 36 PSI <br /> ENGINEER OF RECORD: <br /> LEMING ASSOCIATES, INC. <br /> 22 W. LAKE BEAUTY DRIVE <br /> SUITE 307 <br /> ORLANDO, FLORIDA 32806 <br /> JOE BILLY LEMING, P.E. <br /> AUTHORITY HAVING JURISDICTION: CITY OF ORLANDO <br /> HYDRAULIC PLACARD INFORMATION <br /> LOCATION: NURSING HOME DESIGN AREA 1 <br /> NO. OF SPRINKLERS: 12 SPRINKLERS <br /> BASIS OF DESIGN: <br /> DENSITY: .10 GPM / SQ. FT. <br /> DESIGNED AREA OF DEMAND: 1500 SQ. FT. <br /> SYSTEM DEMAND: <br /> GPM REQUIRED AT BASE OF RISER : , 215.8 GPM <br /> PSI REQUIRED AT BASE OF RISER 35.4 PSI <br />