DIESE 00CLU 03 YAY NOT 8E REPROOLOLD P <br />*10A OR FAN MIRTIOVT E)"m NWfTO <br />APPROOL Al Win FESEIMM <br />RENOVATION SPECIFICATIONS AND INSTRUCTIONS FOR ELECTRICAL INSTALLATION WORK <br />1.0 GENERAL <br />1.1 BIDDERS QUALIFICATIONS AND INSTRUCTIONS: <br />1.1.1 QUALIFICATIONS: THE BIDDERS SHALL BE QUALIFIED, EXPERIENCED, AND <br />LICENSED ELECTRICAL CONTRACTORS. THEY MUST BE FAMILIAR WITH ALL <br />FEDERAL, STATE, AND LOCAL LAWS, ORDINANCES, RULES, AND REGULATIONS <br />THAT MAY, IN ANY MANNER, AFFECT THE TASK. THE BIDDERS SHALL HAVE <br />STRONG FINANCIAL POSITIONS TO PERFORM THE SPECIFIED TASK. <br />1.1.2 BIDDING INSTRUCTIONS: BEFORE SUBMITTING THE BID, THE BIDDERS MUST <br />REVIEW THE SPECIFICATIONS, PLANS, DRAWINGS, CODED AND GENERAL <br />NOTES AND ALL OTHER CONDITIONS AND REQUIREMENTS THAT MAY, IN <br />ANY MANNER AFFECT THE WORK UNDER CONTRACT. THEY SHALL VISIT THE <br />SITE OF THE PROPOSED PROJECT TO FAMILIARIZE <br />THEMSELVES WITH THE LOCAL CONDITIONS, FIRE RATING REQUIREMENTS, <br />AND THE NATURE OF THE PROJECT. THE PRICING SHALL BE BASED ON THESE <br />SPECIFICATIONS AND THE MATERIALS SHOWN ON THE DRAWING. SUBMISSION <br />OF THE BIDS SHALL BE CONSIDERED AS THE EVIDENCE THAT THE BIDDER IS <br />FAMILIARIZED TO ALL THE FACETS OF THE SPECIFIED PROJECT. <br />1.1.3 EXCEPTIONS: ANY EXCEPTIONS, OMISSIONS, DISCREPANCIES, AND DOUBTS <br />REGARDING PLANS, DRAWINGS, AND SPECIFICATIONS, IF ANY, SHALL BE <br />COMMUNICATED IN WRITING TO THE ARCHITECT OR TO THE ENGINEER, <br />WITHIN TEN (10) WORKING DAYS. NO ORAL COMMUNICATION REGARDING THE <br />EXCEPTIONS OR CHANGE SHALL BE ACCEPTED. BIDDERS SHALL BE NOTIFIED <br />WITHIN 10 (TEN) WORKING DAYS OF ANY CHANGES, IF MADE, DUE TO THE <br />ACCEPTANCE OF EXCEPTIONS. <br />1.1.4 MATERIAL TAKE OFF: <br />ALL MATERIAL TAKE OFFS, SHALL BE MADE USING THE LIGHTING AND <br />POWER CONDUIT AND WIRING DRAWINGS AND THEIR ASSOCIATED REFERENCES, <br />INCLUDING THE SPECIFICATIONS ON THIS DRAWING. ALL LIGHTING MATERIALS <br />INCLUDING FIXTURES, RECEPTACLES, SWITCHES, WIRES, PANELS AND RACEWAYS, <br />ETC. SHALL BE PURCHASED BY THE CONTRACTORS UNLESS NOTED OTHERWISE. <br />1.1. I PRICE: 5 8 R THE i PRICE HA D CE B 0 CE S LL INCLUDE A LABOR IA <br />ALL L BO 0 MATERIAL COST, <br />ALL NECESSARY INSURANCE AND PERMITS FEES AS REQUIRED TO INSTALL <br />THE COMPLETE ELECTRICAL SYSTEM IN COMPLIANCE WITH THE DESIGN REQ'TS. <br />1.1.6 SUCCESSFUL BIDDER: THE SUCCESSFUL BIDDER WILL BE REFERENCED AS THE <br />CONTRACTOR FROM THIS POINT ONWARDS THROUGHOUT THE REST OF THE <br />SPECIFICATION. <br />1.2 THE ELECTRICAL CONTRACTOR REQUIREMENTS AND INSTRUCTIONS: <br />1.2.1 THE CONTRACTOR SHALL USE EXPERIENCED AND SKILLED PERSONS TO <br />PERFORM ALL THE ELECTRICAL INSTALLATION WORK UNDER THE CONSTANT <br />SUPERVISION OF LICENSED ELECTRICIANS AND /OR LICENSED JOURNEYMAN <br />ELECTRICIANS. <br />11. 2.2 THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING <br />AND OBTAINING ALL REQUIRED PERMITS, PAYING ALL FEES, AND <br />PROVIDING ALL NECESSARY INSPECTIONS INCIDENTAL TO THE ELECTRICAL <br />PORTION OF THE WORK. <br />1.2.3 THE CONTRACTOR SHALL BE RESPONSIBLE FOR CARRYING NECESSARY <br />INSURANCE AS REQUIRED BY LAW TO PROTECT EMPLOYEES, OTHER PERSONS, <br />EQUIPMENT, MATERIAL AND ANY OTHER REQUIREMENTS. <br />1.2.4 THE INSTALLATION WORK SHALL COMPLY WITH ALL APPLICABLE STATE, <br />COUNTY, AND LOCAL BUILDING CODES. APPLICABLE CODES, AS A MINIMUM, <br />WILL INCLUDE THE LATEST EDITION OF THE FOLLOWING. THESE WILL BE <br />CONSIDERED PART OF THE SPECIFICATION OF THIS PROJECT. <br />A) UNIFORM BUILDING CODE OF THE APPLICABLE CITY AND COUNTY. <br />B) NATIONAL ELECTRIC CODE NFPA 70, 2002 <br />C) LIFE SAFETY CODE NFPA 101, 1997 <br />1.2.5 IN CASE OF SUBSTITUTIONS THE CONTRACTOR SHALL PROVIDE A WRITTEN <br />REQUEST TO THE ARCHITECT FOR HIS REVIEW . THE CONTRACTOR SHALL <br />IDENTIFY AR D T c' <br />DE FY CLE LY THE D ERENCE BE WEEN THE SPE ITEMS AND THE <br />SUBSTITUTE ITEMS, INCLUDING THE ECONOMIC IMPACT ON THE PROJECT. THE <br />SUBSTITUTE ITEM SHALL NOT BE ORDERED OR USED UNLESS APPROVED BY <br />THE ARCHITECT IN WRITING. <br />1.2.6 THE CONTRACTOR SHALL SUBMIT FIVE (5) SETS OF SHOP DRAWINGS FOR <br />SPECIFIED PRODUCTS AT ONE TIME WITHIN TEN (10) DAYS FROM THE <br />OFFICIAL NOTICE TO PROCEED. SHOP DRAWING SUBMITTAL SHALL BE MADE <br />FOR THE FOLLOWING MATERIALS AND SYSTEMS: <br />A) LIGHTING FIXTURES, DIMMERS, LAMPS, AND SAFETY SWITCHES, <br />B) TRANSFORMERS, SWITCH BOARDS, DISTRIBUTION PANELS , DISCONNECTS, <br />C) METER CENTERS, CIRCUIT BREAKERS, FUSES, MOTOR STARTERS IF PURCHASED <br />D) TIME CLOCK AND OTHER DEVICES <br />E) SCHEMATIC DIAGRAMS FOR THE ABOVE ITEMS <br />1.2.7 THE CONTRACTOR SHALL PROVIDE FOLLOWING DOCUMENTS BEFORE THE <br />CLOSING OF THE PROJECT AND PRIOR TO THE FINAL PAYMENT: <br />A) ONE YEAR WRITTEN WARRANTY FOR ANY DEFECT IN WORKMANSHIP, <br />B) TWO SETS OF MANUFACTURER'S OPERATIONAL AND MAINTENANCE <br />C) MANUFACTURER'S WARRANTIES AND WARRANTY CERTIFICATES. <br />0) TWO SETS OF REPRODUCIBLE OR RED MARKED UP PRINTS OF - AS-BUILT - <br />DRAWINGS, ONE FOR THE ARCHITECT AND ONE FOR THE OWNER OF THE <br />1.2.8 THE CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE THE NECESSARY <br />TEMPORARY ELECTRICAL POWER, AT HIS EXPENSE, AS REQUIRED BY HIS <br />TRADE AND BY THE GENERAL CONTRACTOR. <br />1.2.9 THE CONTRACTOR SHALL MAKE SURE ON A DAILY BASIS THAT ALL <br />UNNECESSARY MATERIALS AND TRASH CONTRIBUTED BY HIS TRADE ARE <br />REMOVED. <br />1.2.10 THE CONTRACTOR SHALL ROUTE ALL CONDUITS CONCEALED IN FLOOR, <br />WALLS, AND CEILING IN THE FINISHED AREAS. <br />c� <br />a <br />w <br />o � <br />u� <br />�a0 <br />HW� <br />aH <br />d�0 <br />M <br />M <br />W <br />� O <br />0�4 vi <br />>� a <br />�a <br />I� <br />,, o N <br />NMI M <br />1 0 1 i <br />1� <br />�if��s �ii111� <br />Hyde Park <br />Architects <br />1509 N EST SA ANN A1'ENUE <br />SUITE 270 <br />TAMPA FLORIDA 336062557 <br />813.251.6y09 <br />FAX 813. 250. 1G68 <br />HPAC;MAS(d,AOL -CGM <br />LIC NO AA F000096 <br />REVISED <br />DRAWN BY MOSAD <br />CHECKED BY NKG <br />DATE 05/10/02 <br />0 <br />U� <br />�U <br />w <br />u u <br />W r�i) <br />SCALE AS NOTED <br />GARG ENGINEERING <br />^r E N TER PRI S E S, I N C. <br />N P. E. L-CENSU 10322 SHADY CAK LANE, SEM{SoOLF FL. 53777 FILE 022702.CDJ020502 <br />43779 ELECIRICAL ! MECHANICAL E4GP%LERS <br />FHONE (727) 398 -4274 <br />r FAX (727) 394 -7015 <br />A5V4 OF M'S Z:,J .`10 K ^C FRCiUTY JF :.;RQ SHEET <br />Id ti� .W_ � �AU 1. A: (kU E-4/FOUR <br />2.0 PRODUCTS: <br />2.1 GENERAL: THE ELECTRICAL CONTRACTOR SHALL USE THIS EXISTING DEVICE, WIRES, <br />CONDUITS, PANELS ETC. AS MUCH AS POSSIBLE. THIS SECTION OF SPECIFICATIONS <br />SHALL BE USED TO PURCHASE ALL NEW REQUIRED MATERIAL AS SHOWN ON THE <br />ELECTRICAL PLANS. ALL NEW MATERIAL SHALL BE FREE FROM DEFECTS AND SHALL <br />CARRY "UL" LABEL. <br />2.2 CONDUCTORS: ALL INSULATED CONDUCTORS SHALL BE UNCOATED COPPER <br />OF 98% CONDUCTIVITY, 600 VOLT AC, TYPE THHN /THWN, DUAL RATED <br />AS NECESSARY TO MEET THE DESIGN REQUIREMENTS AND THE APPLICABLE <br />CODES. MW (FOR #4 AWG AND LARGER) AND THERMOPLASTIC WIRES <br />RATED 75 DEGREES CENTIGRADE OPERATION IN WET AND DRY LOCATIONS AND <br />90 DEGREE CENTIGRADE WITH IN ELECTRICAL DISCHARGE LIGHTING <br />EQUIPMENT MAY BE USED. CONDUCTORS NUMBER # 10 AM AND LOWER SHALL <br />BE SOLID COPPER AND #f8 AM AND ABOVE SHALL BE STRANDED COPPER. THE <br />MINIMUM SIZE OF WIRE SHALL BE # 12 AM FOR 20 AMP BREAKER, # 10 AM <br />FOR 30 AMP BREAKER, # 8 AM FOR 40 AMP BREAKER, ETC. <br />2.3 CABLE: SIGNAL CABLES, IF USED, SHALL BE COPPER AND SHALL MEET ALL UL <br />AND N.E.0 CODE REQUIREMENTS. METAL CLAD (TYPE MC), ARMORED (TYPE <br />AC) AND NON- METALLIC (NM) CABLES SHALL NOT BE USED. ALL CABLE <br />ASSEMBLIES SHALL CONTAIN CU GROUND CONDUCTOR. <br />2.4 CONDUITS: THE CONDUITS SHALL BE ELECTRICAL METALLIC TUBING (EMT) <br />AND HOT DIPPED GALVANIZED STANDARD STEEL AS MANUFACTURED BY <br />WHEATLAND OR EQUIVALENT. PVC CONDUITS, IF SPECIFIED, SHALL BE SCHEDULE <br />40, SUN RESISTANT FOR OUTSIDE APPLICATIONS AND SCHEDULE 80 FOR <br />UNDERGROUND APPLICATIONS AND SHALL BE MANUFACTURED BY CARLON OR <br />EQUIVALENT. MINIMUM SIZE OF CONDUIT SHALL BE 1/2" INSIDE DIAMETER. <br />2.5 OUTLET BOXES AND FITTINGS: OUTLET BOXES, FITTING CLAMPS AND <br />HANGERS ETC. SHALL BE GALVANIZED STEEL, RUST RESISTANT AND <br />COMPATIBLE WITH THE RACEWAY. OUTLET BOXES FOR FIXTURES, SWITCHES, <br />AND RECEPTACLES SHALL HAVE SMOOTH ROUND EDGES AND SHALL HAVE <br />COVER PLATES. BOXES SHALL BE "STEEL CITY" OR EQUIVALENT. FITTINGS <br />FOR EMT CONDUITS SHALL BE COMPRESSION TYPE. NO SET SCREW WILL BE USED. <br />UNUSED HOLES SHALL BE COVERED WITH APPROVED INSERT CAPS . <br />2.6 SWITCHES AND DIMMERS: SWITCHES AND DIMMERS SHALL BE TOTALLY ENCLOSED, <br />RATED AT 120/277 VOLTS AC, 20 AMPS, 2000 WATTS WITH IVORY TOGGLE AND <br />DEVICE PLATE. THESE SHALL BE QUIET OPERATION, COMMERCIAL GRADE AS <br />MANUFACTURED BY LEVITON, LUTRON OR EQUIVALENT. PLATES SHALL MATCH <br />THE SWITCHES, FURNISH IN GANGS AS NECESSARY. <br />2.7 RECEPTACLES: RECEPTACLE SHALL BE COMMERCIAL GRADE, 125 VOLTS AC, <br />AND 20 AMPERE RATING WITH GROUNDED POLE AND TWO CIRCUIT OPTION, AS <br />MANUFACTURED BY LEVITON OR EQUIVALENT. PLATES SHALL MATCH THE <br />RECEPTACLES. FURNISH IN GANGS AS NECESSARY. <br />2.8 DEVICE PLATES: PROVIDE DEVICE PLATE FOR EACH AND EVERY OUTLET BOX. <br />FURNISH IN GANGS AS NECESSARY. PLATES AND SCREWS SHALL BE IVORY <br />AND SHALL BE FROM THE SAME MANUFACTURER AS OF THE DEVICES. <br />2.9 BALLASTS: BALLASTS FOR FLUORESCENT FIXTURES SHALL BE RAPID START, <br />MAGNETIC, ENERGY SAVING, HIGH POWER FACTOR AND SHALL BE CLASS "P," <br />CBM, TITLE 24 CERTIFIED WITH INTERNAL THERMAL PROTECTOR WITH AUTOMATIC <br />RESET AND CLASS "A" SOUND RATING NOISE LEVELS LESS THAN 30 dB MAXIMUM. <br />BALLASTS SHALL BE MANUFACTURED BY GE., ADVANCE, UNIVERSAL OR EQUAL AND <br />SHALL BE GUARANTEED AGAINST ANY DEFECTS FOR TWO (2) YEARS. <br />T8 LAMP BALLASTS SHALL BE SOLID STATE ELECTRONIC. <br />2.10 LAMPS: LAMPS SHALL BE MANUFACTURED BY GE, SYLVANIA, PHILLIPS, OR <br />EQUIVALENT AND SHALL BE GUARANTEED FOR AT- LEAST NINETY (90) DAYS <br />AFTER THE ACCEPTANCE. HID LAMPS SHALL BE OPERATED THROUGH A <br />BALLAST RATED FOR THE LAMP VOLTAGE. <br />2.11 LIGHTING DEVICES: ALL UGHTING FIXTURES, EMERGENCY do EXIT LIGHTS <br />SHALL BE AS LISTED ON THE FIXTURE SCHEDULE. <br />2.12 TIME CLOCK OR TIME SWITCH: TIME CLOCK SHALL BE ELECTRO MECHANICAL <br />24 HOURS, 7 DAYS TYPE 'NTH RESERVE POWER AND CONTACTS RATED <br />40 A, 4 PST AND NEMA TYPE 1 OR 3R ENCLOSURE. IT SHALL BE SELF <br />POWERED BY A SELFSTARTING SYNCHRONOUS MOTOR WITH MINIMUM 16 HRS <br />SPRING DRIVEN RESERVE POWER AND A DAY OMITTING DEVICE. TIME CLOCK <br />SHALL BE PARAGON 7007 -0, TORN 7120 ZL OR APPROVED EQUAL. <br />2.13 PANEL BOARDS AND LOAD CENTERS SHALL BE GENERAL PURPOSE N.E.M.A. TYPE 1 <br />OR TYPE 3R ENCLOSURES SUITABLE FOR SPECIFIED LOCATION AND SURFACE <br />OR FLUSH MOUNTING APPLICATIONS AS INDICATED ON THE PANEL SCHEDULE. <br />PANEL BOARDS AND THE INTERNAL COMPONENTS SHALL BE RATED TO PERFORM <br />THEIR FUNCTIONS CONTINUOUSLY AT 40 DEGREE CENTIGRADE AMBIENT AND 503 <br />RELATIVE HUMIDITY. BUSSES, TERMINALS AND LUGS SHALL BE RATED AND <br />CAPABLE TO FUNCTION CONTINOUSLY AT 75 DEGREE CONTIGRADE. <br />PANEL BOARDS SHALL BE AS MANUFACTURED BY WESTINGHOUSE ELECTRIC <br />CORP., GENERAL ELECTRIC, SQUARE 'D', CHALLENGER, OR APPROVED EQUAL. <br />A NAMEPLATE LISTING PANEL TYPE, MANUFACTURER NAME, NUMBER OF <br />PROTECTIVE AND SWITCHING DEVICES AND RATINGS SHALL BE LOCATED <br />ON THE PANEL BOARD. <br />BRANCH CIRCUITS SHALL BE ARRANGED USING DOUBLE ROW CONSTRUCTION. <br />ALL INTERIORS OF PANEL BOARDS SHALL BE COMPLETELY FACTORY ASSEMBLED <br />'NTH SWITCHING AND PROTECTIVE DEVICES, WIRE CONNECTORS, ETC. ALL <br />WIRE CONNECTORS, EXCEPT SCREW TERMINALS, SHALL BE OF THE ANTI -TURN <br />SOLDERLESS TYPE AND ALL SHALL BE SUITABLE FOR COPPER WIRE OF THE <br />SIZES INDICATED ON DRAWINGS OR IN THE PANEL SCHEDULES. <br />INTERIORS SHALL BE SO DESIGNED THAT SWITCHING AND PROTECTIVE <br />DEVICES CAN BE REPLACED WITHOUT DISTURBING ADJACENT UNITS AND <br />WITHOUT REMOVING THE MAIN BUS CONNECTORS AND SHALL BE SO <br />DESIGNED THAT CIRCUITS MAY BE CHANGED WITHOUT MACHINING, <br />DRILLING, OR TAPPING. <br />BUS BARS FOR THE MAINS SHALL BE OF COPPER AND SIZED IN ACCORDANCE <br />WITH UNDERWRITERS' LABORATORIES STANDARDS. UNLESS NOTED <br />OTHERWISE, FULL SIZE NEUTRAL BARS SHALL BE INCLUDED, BUS BAR TAPS <br />FOR PANELS WITH SINGLE POLE BRANCHES SHALL BE ARRANGED FOR <br />SEQUENCE PHASING OF THE BRANCH CIRCUIT DEVICES. <br />THE SHORT CIRCUIT RATING OF THE ASSEMBLED PANEL BOARD SHALL BE IN <br />ACCORDANCE WITH UL. INC. STANDARDS AND THEIR TEST VERIFICATION. <br />PHASE BUSSING SHALL BE FULL HEIGHT WITHOUT REDUCTION. CROSS AND <br />CENTER CONNECTORS SHALL BE COPPER. <br />NEUTRAL AND GROUND BUSSING SHALL HAVE A SUITABLE LUG FOR EACH OUTGOING <br />FEEDER REQUIRING A NEUTRAL AND GROUND CONNECTION. <br />SPACES FOR FUTURE SWITCHING AND PROTECTIVE DEVICES ON LIGHTING AND <br />APPLIANCE PANEL BOARDS SHALL BE BUSSED FOR THE MAXIMUM DEVICE THAT <br />CAN BE FITTED INTO THEM. PROVIDE BLANK FILLER PLATES EMPTY SPACES. <br />2.14 CIRCUIT BREAKER: <br />THE CIRCUIT BREAKERS ARE TO BE INDUSTRIAL MOLDED CASE BOLT ON TYPE, <br />STANDARD THERMAL, MAGNETIC, WITH TRIP FREE MECHANISM, THREE <br />POSITION HANDLES INDICATING "ON" "OFF" AND "TRIPPED" CONDITION. <br />EACH POLE SHALL PROVIDE INVERSE TIME DELAY AND INSTANTANEOUS <br />CIRCUIT PROTECTION. THE BREAKER RATING AND CONFIGURATION SHALL BE <br />AS INDICATED ON THE PANEL BOARD SCHEDULE. ALL MULTIPOLE BREAKERS <br />SHALL HAVE AN INTERNAL COMMON TRIP. ALL BREAKER LUGS SHALL BE <br />RATED FOR 75 DEGREE CENTIGRADE CONTINUOUS OPERATION. <br />2.15 PANEL TRIM: <br />HINGED DOORS IN PANEL TRIMS SHALL COVER ALL SWITCHING DEVICE <br />HANDLES AND SHALL CONFORM TO ME FOLLOWING REQUIREMENTS: <br />1. DOORS SHALL NOT UNCOVER ANY LIVE PARTS WHILE MAKING SWITCHING <br />DEVICE HANDLES ACCESSIBLE. <br />2. 'DOORS SHALL HAVE FLUSH -TYPE CYLINDER LOCK AND CATCH, EXCEPT <br />THAT DOORS OVER 48" IN HEIGHT SHALL HAVE AUXILIARY FASTENERS AT <br />TOP AND BOTTOM OF DOOR IN ADDITION TO FLUSH -TYPE CYLINDER LOCK <br />AND CATCH. DOOR HINGES SHALL BE CONCEALED. ALL LOCKS SHALL BE <br />KEYED ALIKE. DIRECTORY FRAME AND CARD HAVING A TRANSPARENT <br />COVER SHALL FURNISHED LL 8E UR SHED ON EACH DOOR. <br />THE TRIMS SHALL BE FABRICATED FROM CODE GAUGE SHEET STEEL. ALL <br />EXTERIOR AND INTERIOR STEEL SURFACES OF THE PANEL BOARDS SHALL BE <br />PROPERLY CLEANED PRIMED AND PAINTED IN ACCORDANCE WITH THE <br />MANUFACTURERS STANDARD SPECIFICATIONS AND COLOR. <br />ALL AROUND. SURFACE MOUNT PANELS TRIMS SHALL HAVE THE SAME WIDTH <br />AND HEIGHT AS OF THE BOX. TRIMS SHALL BE MOUNTABLE BY A SCREW <br />DRIVER WITHOUT THE NEED FOR SPECIAL TOOLS. <br />2.16 PANEL BOXES: <br />BOXES SHALL BE MADE FROM UNPAINTED GALVANIZED CODE GAUGE STEEL <br />HAVING MULTIPLE KNOCKOUTS ON THE TOP AND THE BOTTOM EXCEPT <br />WHERE NOTED OTHERWISE. BOXES SHALL BE OF SUFFICIENT SIZE TO PROVIDE <br />A MINIMUM GUTTER SPACE OF 4" ON ALL SIDES. <br />WIHERE FEEDER CABLES SUPPLYING THE MAINS OF A PANEL ARE CARRIED <br />THROUGH ITS BOX TO SUPPLY OTHER ELECTRICAL EQUIPMENT, THE BOX <br />SHALL BE SO SIZED AS TO INCLUDE THIS WIRING SPACE. THIS WIRING SPACE <br />SHALL BE IN ADDITION TO THE MINIMUM GUTTER SPACE SPECIFIED ABOVE <br />AND THE UNITING WIDTH MAY BE INCREASED ACCORDINGLY. AT LEAST FOUR <br />(4) INTERIOR MOUNTING STUDS SHALL BE PROVIDED. <br />ALL UNUSED HOLES IN THE BOXES SHALL BE PLUGGED WITH APPROVED <br />INSERT CAPS. BOXES SHALL BE "STEEL CITY" OR EQUAL. <br />2.17 DISCONNECT SWITCHES: THE CONTRACTOR SHALL INSTALL N.E.M.A. TYPE 1 <br />ENCLOSURES FOR INDOOR APPLICATIONS AND TYPE 313 ENCLOSURES FOR OUT <br />DOOR APPLICATIONS. DISCONNECT SWITCHES FOR MOTOR CIRCUIT AND FIXED <br />LOAD (SUCH AS HVAC EQUIPMENT, AND WATER HEATER ETC.) CIRCUITS SHALL <br />BE FUSIBLE OR NON FUSIBLE AS SHOWN ON THE DRAWINGS OR REQUIRED BY <br />THE MANUFACTURER. <br />2.18 FUSE: THE CONTRACTOR SHALL USE DUAL ELEMENT, TIME DELAY CURRENT <br />LIMITING, CLASS RK -1 FUSES WHEN PROTECTING PANEL BOARDS AND XFRMRS. <br />AND CLASS RK -3 FUSES WHEN PROTECTING MOTORS UNLESS NOTED OTHERWISE <br />OR REQUIRED DIFFERENTLY BY THE MANUFACTURER. FUSES SHALL BE MANUFA- <br />CTURED BY BUSSMANN, COULD SHAWMUT OR EQUIVALENT. <br />3.0 INSTALLATION INSTRUCTIONS: <br />3.1 GENERAL: THE PLAN LOCATION OF LIGHTING FIXTURES, JUNCTION BOXES, <br />CONVENIENCE OUTLETS, AND PANEL 80ARDS ARE APPROXIMATE UNLESS <br />DIMENSIONED AND ARE TO BE ADJUSTED BY THE CONTRACTOR AS REQUIRED <br />IN THE AREAS WHERE CEILING GRID AND OTHER OBSTRUCTIONS DETERMINE <br />FIXTURE LOCATIONS. THE CONTRACTOR SHALL COORDINATE WITH OTHER <br />ARCHITECTURAL, MECHANICAL AND OTHER SYSTEMS TO AVOID <br />INTERFERENCE. ALL CUTTING AND CONSEQUENT REPAIRS IN CONJUNCTION <br />WITH THE WORK SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. <br />3.2 THE CONTRACTOR SHALL PROVIDE ALL NECESSARY MATERIALS, LABOR, <br />TRANSPORTATION, RIGGING & HOISTING, TOOLS, AND STORAGE, ETC. FOR ALL <br />WORK INDICATED AND REQUIRED FOR COMPLETE INSTALLATION. <br />3.3 ELECTRICAL WORK SHALL BE EXECUTED IN ACCORDANCE WITH ALL APPLICABLE <br />CODES AND SHALL INCLUDE COMPLETE TESTING OF ALL EQUIPMENT AND WIRING. <br />WORKMANSHIP SHALL BE THE HIGHEST QUALITY AS ESTABLISHED BY TRADE STD. <br />3.4 THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING NECESSARY <br />PERMITS, AND COMMUNICATIONS WITH THE LOCAL BUILDING DEPARTMENT <br />AND INSPECTION PERSONNEL TO REVIEW CONTRACT DOCUMENTS PRIOR TO <br />INSTALLATION. <br />3.5 OWNER WILL NOT BE HELD RESPONSIBLE FOR FIELD CHANGES THAT ARISE <br />FROM CONTRACTOR'S ERROR OR OMISSION OF MATERIALS OR WORKMANSHIP <br />IN WORK PERFORMANCE. <br />3.6 THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF ALL <br />UTILITIES PLACEMENT AND LOCATION OF THE ELECTRICAL SERVICE <br />EQUIPMENT. THE CONTRACTOR SHALL PAY ALL NECESSARY CHARGES <br />ASSOCIATED WITH INSTALLATION OF ALL UTILITIES TO THE POWER <br />COMPANY PRIOR TO THE CONSTRUCTION AND PROVIDE A LETTER FROM THE <br />POWER COMPANY THAT ALL THE CHARGES HAVE BEEN PAID IN FULL. <br />3.7 NECESSARY AND OBVIOUSLY REQUIRED, ELECTRICAL ITEMS THAT ARE NOT <br />SHOWN ON THE DRAWINGS, SHALL NOT RELIEVE THE CONTRACTOR OF HIS <br />RESPONSIBIUPES TO INSTALL A COMPLETE AND SAFE ELECTRICAL SYSTEM. <br />3.8 THE ELECTRICAL CONTRACTOR SHALL FOLLOW THE SAME COLOR CODE <br />IDENTIFICATION FOR EACH PHASE THROUGHOUT THE SYSTEM FROM SERVICE <br />SWITCH OR TRANSFORMER THROUGH ALL BRANCH CIRCUITS. <br />3.9 ALL SLAB OR ROOF PENETRATIONS SHALL BE MADE WITH APPROVED FIRE <br />RATED SMOKE BARRIER FITTINGS. PROVIDE ACCESSORIES (PITCH POCKETS, <br />SLEEVES, ETC.) AS REQUIRED. <br />3.10 JUNCTION BOXES FOR SIGN LIGHTS, SWITCHES, LIGHT FIXTURES, RECEPTACLES, <br />AND PULLING WIRES SHALL BE AS APPROXIMATELY AS SHOWN ON THE PLANS <br />BUT EXACT LOCATIONS SHALL BE GOVERNED BY THE ARCHITECTURAL PLANS. <br />3.11 ALL OUTLET BOXES SHALL HAVE SQUARE CUT CORNERS. AIR SPACE GREATER <br />THAN 1/8" AROUND OUTLET BOXES, AND ADJACENT DRYWALL WILL NOT BE <br />PERMITTED. THE CONTRACTOR SHALL COORDINATE WITH DRYWALL INSTALLER <br />IPRIOR TO INSTALLATION. THE CONTRACTOR SHALL CAULK AROUND BOXES. <br />3.12 LIGHTING SWITCHES AND CONVENIENCE RECEPTACLES SHALL BE FLUSH <br />MOUNTED IN SECTIONAL SWITCH BOXES WITH MATCHING COVER PLATES <br />UNLESS NOTED OTHERWISE. <br />3.13 THE MOUNTING ARRANGEMENT OF EACH FIXTURE WILL BE IN ACCORDANCE <br />WITH MANUFACTURER MOUNTING INSTRUCTIONS. <br />14 THE E C NTRA T R HA 0 C 0 S HALL FURNISH AND INSTALL ALL LUMINARIES, DEVICES, <br />AN EQUIPMENT D EQ MEN AS SPECIFIED AND SHOWN ON THE PLAN DIAGRAMS. PROVIDE <br />ALL CABLES, CONDUCTORS, CONDUITS, AND CONNECTIONS AS REQUIRED TO <br />PROVIDE COMPLETE AND OPERATIONAL ELECTRICAL AND MECHANICAL <br />SYSTEMS. ALL CONDUITS SHALL BE RUN CONCEALED IN FINISHED AREAS. <br />3.15 INDIVIDUAL BREAKERS WILL SUPPLY ELECTRICAL POWER TO INDIVIDUAL <br />SIGN OR NEON LIGHT CIRCUITS. NEON TRANSFORMER EQUIPMENT IS TO BE <br />CONCEALED ABOVE ADJACENT COLUMN ENCLOSURE. OR TO BE INSTALLED <br />AS SHOWN ON ARCHITECTURAL DRAWINGS. <br />3.16 ALL JOINTS IN CONDUIT AND RACEWAY SHALL BE MADE TIGHT AND BENDS <br />SHALL BE MADE OVER LONG RADIUS 'WHERE ENTERING A CABINET AND <br />JUNCTION BOX. THE CONTRACTOR SHALL SUPPORT ALL CONDUIT AND <br />RACEWAYS SECURELY FROM JOISTS AND /OR BEAMS (TIE WIRES ARE NOT <br />ACCEPTABLE). THE CONTRACTOR SHALL VERIFY ALL RACEWAY SIZES IN <br />ACCORDANCE WITH THE N.E.C. CODE. NO CONDUIT SHALL CARRY MORE THAN <br />THREE(3) CURRENT CARRYING CONDUCTORS. <br />3.17 LIGHTING CONDUITS SHALL BE SUPPORTED AT EVERY 8 FEET. <br />3.18 MOUNTING HEIGHT OF LIGHTING EQUIPMENT, UNLESS NOTED OTHERWISE <br />SHALL BE APPROXIMATELY AS FOLLOWS: <br />LIGHTING SWITCHES CENTERLINE 4 FEET ABOVE A.F.F <br />CONVENIENCE OUTLETS CENTERLINE 1 FEET, 6 INCHES A.F.F <br />LIGHTING & POWER PANELS TOP 6 FEET, 6 INCHES ABOVE A.F.F <br />EXIT LT /EMG LTS 9 FEET A.F.F. TO BOT. OF UNIT <br />3.19 ALL EQUIPMENT GROUNDING CONDUCTOR SHALL BE INSTALLED IN ALL <br />ELECTRICAL RACEWAYS AND SHALL BE SIZED IN ACCORDANCE WITH <br />NATIONAL ELECTRIC CODE (N.E.C), ARTICLE 250. ALL BRANCH CIRCUITS SHALL <br />HAVE A SEPARATE GREEN INSULATED GROUND WIRE IN EACH CONDUIT RUN. <br />ISOLATED GROUND CONDUCTORS SHALL BE ROUTED TO THOSE CIRCUITS WHICH <br />NEED ISOLATED GROUND, SPECIALLY FOR COMPUTERS AND CASH REGISTER ETC. <br />SUCH CIRCUITS SHALL BE INDENTIFIED ON PLAN DRAWINGS BY LETTER "IG" <br />3.20 THE CONTRACTOR SHALL PROVIDE LIGHTNING PROTECTION VOLTAGE SURGE <br />PROTECTOR FOR ALL SERVICE PHASE CONDUCTORS TO GROUND IF IT IS NOT <br />ALREADY THERE. DEVICE APT TE 400 OR APPROVED EQUIVALENT SHALL BE <br />USED. <br />3.21 LUMINARIES SHALL BE AS SPECIFIED IN THE "LIGHTING FIXTURE SCHEDULE ". <br />ALL RECESSED AND LAY -IN FIXTURES SHALL BE SUPPORTED FROM THE FOUR <br />CORNERS WITH SUPPORTS CAPABLE OF CARRYING TWICE THE WEIGHT OF THE <br />FIXTURE. ALL SUPPORTS SHALL BE ATTACHED TO THE JOISTS AND /OR BEAMS. <br />3.22 THE CONTRACTOR SHALL INSTALL ALL TELEPHONE JACKS AND WIRING FROM <br />THE MAIN TELEPHONE TERMINAL BOARD TO THE FINAL TELEPHONE OUTLETS. <br />WIRING SHALL BE INSTALLED IN A MINIMUM 1/2 INCH CONDUIT. <br />3.23 THE CONTRACTOR SHALL COORDINATE WITH THE FIRE PROTECTION <br />CONTRACTOR AND SHALL MAKE ALL NECESSARY CONNECTIONS BETWEEN <br />DUCT SMOKE DETECTORS AND HVAC UNITS. <br />3.24 ALL JUNCTION BOXES SHALL BE ACCESSIBLE FROM BELOW. OTHERWISE, <br />CONTRACTOR SHALL PROVIDE ACCESS PANEL AT ALL JUNCTION BOX <br />LOCATIONS AND SMOKE DETECTORS. <br />3.25 IF NOT ALREADY PROVIDED, THE CONTRACTOR SHALL FURNISH ALL THE <br />NECESSARY DISCONNECT SWITCHES, RELAY BOXES, AND CONTROL BOXES AS <br />REQUIRED AND RECOMMENDED BY THE HVAC MANUFACTURER FOR THE <br />HVAC UNIT AND WATER HEATER. THE ELECTRICAL CONTRACTOR SHALL <br />COORDINATE WITH THE MECHANICAL CONTRACTOR AND MAKE ALL <br />NECESSARY CONNECTIONS TO MAKE THE HVAC SYSTEM FUNCTIONAL. <br />3.26 COMPLETE TYPE WRITTEN IDENTIFICATION CARD FOR ALL MAIN AND BRANCH <br />CIRCUITS SHALL BE POSTED AT THE INSIDE OF THE PANEL DOOR. <br />