Laserfiche WebLink
1 <br />GENERAL <br />1. THE ELECTRICAL CONTRACTOR REFERRED TO HEREAFTER, AS THE <br />"CONTRACTOR" SHALL PROVIDE COMPLETE ELECTRICAL SYSTEMS AS <br />INDICATED ON THE DRAWINGS AND SPECIFIED HEREIN. <br />3 <br />2, CONTRACTOR SHALL PROVIDE PROTECTIVE DEVICES, CONDUCTORS, <br />SUPPORTS, RACEWAYS, AND MISCELLANEOUS MATERIALS TO SERVE ALL <br />DEVICES REQUIRING ELECTRICAL POWER. <br />3. CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS, FEES, AND <br />INSPECTIONS REQUIRED TO COMMENCE AND COMPLETE ELECTRICAL WORK, <br />4, CONTRACTOR SHALL CONDUCT A THROUGH SITE INSPECTION TO <br />FAMILIARIZE HIMSELF WITH EXISTING CONDITIONS AND ALL ASPECTS OF HIS <br />SCOPE OF WORK, SUCH AN INSPECTION SHALL BE CONDUCTED PRIOR TO <br />SUBMITTING A BID. <br />5. CONTRACTOR SHALL REFER TO INTERIOR ARCHITECTURAL CASE WORK <br />ELEVATIONS FOR EXACT MOUNTING HEIGHTS AND /OR LOCATIONS OF <br />SWITCHES, OUTLETS, AND WIRING DEVICES. <br />6, CONTRACTOR SHALL MAINTAIN A COMPLETE TEMPORARY POWER AND <br />LIGHTING SYSTEM DURING CONSTRUCTION. <br />7. THE CONTRACTOR SHALL PROVIDE, DROP CLOTH, RUBBER MATS AND <br />PLYWOOD COVERS FOR OWNERS EQUIPMENT SUSCEPTIBLE TO DAMAGE <br />DURING CONSTRUCTION. VERIFY SPECIFIC LOCATIONS WITH OWNER'S <br />REPRESENTATIVE. <br />8. ALL WORK SHALL BE PERFORMED DURING PERIODS ACCEPTABLE TO THE <br />OWNER. SCHEDULE ALL WORK WITH THE OWNER'S REPRESENTATIVE BEFORE <br />PROCEEDING. <br />9, THE CONTRACTOR SHALL PERFORM TEMPORARY WORK NECESSARY TO <br />MAINTAIN CONTINUITY OF ELECTRICAL SERVICE WHEN CONNECTION IS MADE <br />TO EXISTING SYSTEMS AND FACILITIES. EXISTING SERVICE SHALL NOT BE <br />INTERRUPTED WITHOUT PRIOR CONSENT OF THE OWNER'S REPRESENTATIVE. <br />10. AT PROJECT COMPLETION, THE CONTRACTOR SHALL INSURE THAT ALL <br />ELECTRICAL SYSTEMS OPERATE PROPERLY, CONTRACTOR SHALL <br />DEMONSTRATE OPERATION OF EACH SYSTEM WITH THE OWNER'S <br />REPRESENTATIVE. <br />11. CONTRACTOR SHALL COORDINATE AND VERIFY WITH LOCAL POWER <br />COMPANY THE FOLLOWING: <br />EXACT LOCATION OF SERVICE CONNECTION, <br />- ELECTRICAL CHARACTERISTICS (VOLTAGE AND PHASING) <br />- AVAILABLE FAULT CURRENT <br />METERING REQUIREMENTS <br />CODES AND STANDARDS <br />1. ELECTRICAL WORK SHALL COMPLY WITH THE LATEST EDITION OF <br />- NFPA 70 (NATIONAL ELECTRICAL CODE) <br />- NFPA 101 (LIFE SAFETY CODE) <br />- CODES SPECIFIC TO OTHER SECTIONS HEREIN <br />2. ELECTRICAL WORK SHALL COMPLY WITH ALL LOCAL AND STATE <br />ELECTRICAL CODES AND IN ACCORDANCE WITH REQUIREMENTS OF THE <br />AUTHORITY HAVING JURISDICTION (AHJ). <br />QUALITY <br />1. WORKMANSHIP SHALL BE HIGH QUALITY AND FOLLOW INDUSTRY <br />STANDARDS. SUBSTANDARD WORK WILL BE REJECTED. THE CONTRACTOR IS <br />RESPONSIBLE FOR REPAIR AND REWORK TO RECTIFY SUBSTANDARD WORK. <br />QUALITY OF WORK SHALL BE DETERMINED BY THE OWNER'S <br />REPRESENTATIVE AND /OR ENGINEER OF RECORD, <br />I NTERFERENCES <br />1, PLANS ARE GENERALLY DIAGRAMMATIC, THE CONTRACTOR SHALL <br />COORDINATE WITH THE OTHER TRADES SO THAT INTERFERENCES BETWEEN <br />CONDUITS, PIPING, EQUIPMENT, DUCTS, AND STRUCTURAL WORK WILL BE <br />AVOIDED. IN SUCH CASE, THE CONTRACTOR FAILS TO COORDINATE WITH <br />OTHER TRADES AND INTERFERENCES ARE ALLOWED DEVELOP, THE OWNER'S <br />AUTHORIZED REPRESENTATIVE WILL DECIDE WHICH EQUIPMENT, DUCT, <br />CONDUIT, ETC., MUST BE RELOCATED, REGARDLESS OF WHICH WAS <br />INSTALLED FIRST, ELECTRICAL REWORK REQUIRED TO CORRECT <br />INTERFERENCES WILL BE AT THE CONTRACTORS EXPENSE. <br />MATERIALS <br />1. ALL ELECTRICAL EQUIPMENT AND MATERIALS SHALL BE APPROVED BY <br />UNDERWRITERS LABORATORY FOR THE APPLICATION AND SHALL BEAR A <br />UL LABEL, <br />2. ELECTRICAL ENCLOSURES SHALL BE NEMA RATED. UNLESS OTHERWISE <br />NOTED, ENCLOSURE RATINGS SHALL ADHERE TO THE FOLLOWING: <br />- NEMA 1 INDOOR <br />- NEMA 3R OUTDOOR <br />- NEMA 4 CORROSIVE ENVIRONMENT <br />GUARANTEE <br />1. CONTRACTOR SHALL GUARANTEE ALL WORK FOR A PERIOD OF ONE <br />YEAR FROM DATE OF OWNER'S ACCEPTANCE, THE CONTRACTOR SHALL <br />RECTIFY ANY DEFECTS DUE TO FAULTY MATERIALS OR WORKMANSHIP AND <br />PAY FOR DAMAGE CAUSED BY FAILURE AND REWORK. THE OWNER WILL <br />GIVE NOTICE OF DEFECTS WITH REASONABLE PROMPTNESS AFTER <br />DISCOVERY. THE CONTRACTOR SHALL START REWORK WITHIN TEN (10) <br />WORKING DAYS OF NOTIFICATION AND COMPLETE REPAIRS IN A TIMELY <br />MANNER. <br />SUBMITTAL DATA AND RECORD DRAWINGS <br />1. THE ELECTRICAL DESIGN IS BASED ON A SINGLE MANUFACTURE OF <br />SWITCH GEAR, LIGHTS, TRANSFORMER, GENERATORS, ETC, WHEREAS <br />SUBSTITUTIONS ARE PROVIDED IN LIEU OF THAT WHICH IS SPECIFIED, THE <br />CONTRACTOR ASSUMES FULL RESPONSIBILITY FOR ANY IMPACT TO THE <br />INSTALLATION, CONTRACTOR SHALL VERIFY THAT SUBSTITUTIONS CAN <br />FUNCTION SATISFACTORILY IN THEIR DESIGNATED SPACE AND CHANGES IN <br />OPERATING CHARACTERISTICS DO NOT DEGRADE THE INSTALLATION. <br />2. SUBMIT MANUFACTURER'S DATA (MINIMUM 5 COPIES) FOR ELECTRICAL <br />GEAR, LIGHT FIXTURES, WIRING DEVICES AND OTHER EQUIPMENT SPECIFIED <br />HEREIN, SUBMIT SHOP DRAWINGS IN BOOKLET FORM WITH SEPARATE SHEE <br />FOR EACH DEVICE. PROVIDE EQUIPMENT IDENTIFICATION AS DESIGNATED/ <br />ON PLANS FOR EACH SHOP DRAWING CUT SHEET SUBMITTED. <br />3. AT PROJECT COMPLETION THE CONTRACTOR SHALL COMPILE TWO (2)\ <br />COMPLETE SETS OF RECORD DRAWINGS INDICATING ALL DEVIATIONS FROM <br />CONSTRUCTION DOCUMENTS, ONE SET SHALL BE ISSUED TO THE <br />ARCHITECT AND ONE SET SHALL BE ISSUED TO OWNER'S REPRESENTATIVE. <br />1 <br />IDENTIFICATION OF EQUIPMENT <br />1. LABEL ALL ELECTRICAL EQUIPMENT WITH ENGRAVED LAMINATED PLASTIC <br />NAMEPLATE THAT CLEARLY DESCRIBES THE EQUIPMENT NAME, VOLTAGE, <br />AMPERAGE RATING, AND FUNCTION. NAMEPLATES SHALL BE RED <br />BACKGROUND WITH WHITE STENCILED UPPER CASE LETTERING A MINIMUM <br />OF 3/16" IN HEIGHT, <br />2. INSTALL VINYL CLOTH SELF- ADHESIVE CIRCUIT LABELS ON ALL WIRE <br />AND CABLE IN JUNCTION BOXES, WIRE TROUGHS, AND PANELBOARD WIRING <br />GUTTERS. <br />3. IDENTIFY JUNCTION BOXES WITH PERMANENT MARKER INDICATING <br />PANELBOARD AND CIRCUIT NUMBERS OF WIRING CONTAINED WITHIN, <br />4. PROVIDE TYPEWRITTEN PANELBOARD DIRECTORIES WITH ACCURATE AS <br />BUILT INFORMATION. DIRECTORIES SHALL REFLECT TYPE OF LOAD AND <br />AREA SERVED FOR EACH BREAKER. <br />RACEWAYS AND FITTINGS <br />1. CONDUIT SHALL BE PROPERLY ALIGNED, GROUPED AND SUPPORTED. <br />EXPOSED CONDUIT SHALL BE INSTALLED AT RIGHT ANGLES TO OR <br />PARALLEL TO THE PRINCIPAL STRUCTURAL MEMBERS, CONDUIT SHALL BE <br />SUPPORTED AT INTERVALS NOT EXCEEDING 8 FEET. CONDUIT SHALL BE <br />SUPPORTED FROM STRUCTURE AND NOT FROM CEILING SUPPORT SYSTEM, <br />2. EXCEPT IN MECHANICAL ROOMS, ELECTRICAL ROOMS, OPEN STRUCTURE <br />CANOPIES, AND EXTERIOR SERVICE ENTRANCES, CONDUIT SHALL BE <br />CONCEALED THROUGHOUT THE FACILITY, <br />3. PROVIDE NYLON PULL CORD IN ALL EMPTY CONDUITS, <br />4. ELECTRICAL METAL TUBING (EMT) SHALL BE GALVANIZED STEEL FOR <br />DRY INTERIOR INSTALLATIONS AND ALUMINUM FOR, DAMP, WET OR <br />EXTERIOR INSTALLATIONS. COUPLINGS AND CONNECTORS SHALL BE SET <br />SCREW TYPE FOR STEEL, EMT SHALL BE USED CONCEALED ABOVE <br />CEILINGS, CONCEALED IN WALLS, AND EXPOSED IN MECHANICAL AND <br />ELECTRICAL ROOMS. <br />5. FLEXIBLE METALLIC CONDUIT IN DRY LOCATIONS SHALL BE <br />UNDERWRITERS' APPROVED, STEEL, ZINC COATED, SINGLE STRIP TYPE, <br />FITTINGS SHALL BE AS MANUFACTURED BY THOMAS AND BETTS <br />"TITE- BITE ", OR APPROVED EQUAL, <br />6. FLEXIBLE METALLIC CONDUIT IN DAMP OR WET LOCATIONS SHALL BE <br />UNDERWRITERS' APPROVED, GALVANIZED STEEL WITH MOISTURE PROOF PVC <br />JACKET . FITTINGS SHALL INSULATED THROAT AND LIQUID TIGHT AS <br />MANUFACTURE BY THOMAS AND BETTS, OR APPROVED EQUAL. <br />7. GALVANIZED RIGID STEEL (GRS) CONDUIT SHALL BE ILL APPROVED HOT <br />DIPPED GALVANIZED. GRS CONDUIT COUPLINGS SHALL BE THREADED <br />HEAVY WALL GALVANIZED STEEL. USE 90 DEGREE GRS SWEEPS AND GRS <br />RISERS IN UNDERGROUND PVC CONDUIT RUNS. PAINT ALL GALVANIZED <br />RIGID CONDUITS INSTALLED BELOW GRADE WITH RUST INHIBITING PAINT. <br />8. PVC CONDUIT SHALL BE UL LISTED SCHEDULE 40 PVC UV RESISTANT, <br />PVC CONDUIT MAY BE USED BELOW GRADE, UNDER FLOORS, IN CONCRETE, <br />AND FOR GROUNDING SYSTEM CONDUCTORS <br />9. CONDUIT AND WIRING PENETRATING RATED FLOORS AND WALLS SHALL <br />BE SEALED WITH A UL RATED ASSEMBLY TO MAINTAIN FIRE RATING AND <br />INTEGRITY OF SEPARATION. <br />10. METAL CLAD CABLE (TYPE MC) IS PERMISSABLE IF INSTALLED PER <br />NEC ARTICLE 334. FITTINGS SHALL BE INSULATED THROAT AS <br />MANUFACTURED BY THOMAS AND BETTS "TITE- BITE ", OR APPROVED <br />EQUAL, <br />BOXES <br />1. BOXES SHALL BE RIGIDLY MOUNTED AND COVERED WITH MATCHING <br />PLATE, OPEN KNOCK -OUTS OR HOLES IN BOXES SHALL BE PLUGGED <br />WITH A SUITABLE BLANKING DEVICE, <br />2. SURFACE MOUNT EXTERIOR OUTLET BOXES SHALL BE CAST ALUMINUM <br />WITH WEATHERPROOF ALUMINUM GASKETED COVER. <br />3. FLUSH MOUNT EXTERIOR OUTLET BOXES SHALL 4" SQUARE STEEL WITH <br />MASONRY RING AND WEATHERPROOF GASKETED CAST ALUMINUM COVER. <br />CONDUCTORS <br />1, UNLESS OTHERWISE INDICATED, BRANCH CIRCUIT CONDUCTORS SHALL BE <br />SOLID NO. 12 AWG COPPER. BRANCH CIRCUITS RUN OVER 75 FEET IN <br />LENGTH, MEASURING ONE WAY FROM THE FIRST OUTLET OF THE CIRCUIT <br />TO THE PANEL, SHALL BE SOLID N0, 10 AWG COPPER FOR THE ENTIRE <br />CIRCUIT. <br />2, SPLICES AND TAPS SHALL UTILIZE SOLDERLESS LUGS FOR #8 AWG AND <br />LARGER, SPLICES AND TAPS SHALL FORM A ELECTRICAL AND <br />MECHANICALLY SECURE CONNECTION. LUGS SHALL BE CORRECTLY SIZED <br />FOR THE CONDUCTORS, TAPE JOINTS WITH VINYL PLASTIC ELECTRICAL <br />TAPE. <br />3. ALLOW SUFFICIENT CABLE SLACK IN BOXES, OUTLETS AND CABINETS TO <br />MAKE CONNECTION AND INSURE THERE IS NO BINDING AT THE <br />SPLICE /TAP. <br />4. CONDUCTORS SHALL BE COPPER. UNLESS OTHERWISE NOTED, <br />INSULATION SHALL BE DUAL TYPE THHN /THWN 75 °C. CONDUCTORS SHALL <br />BE COLOR CODED IN ACCORDANCE WITH NFC 70. COLOR CODING SHALL BE <br />BY MEANS OF COLORED INSULATING MATERIAL, COLORED BRAID OR <br />JACKET OVER THE INSULATION OR BY MEANS OF SUITABLE COLORED, <br />PERMANENT, NON- AGING, INSULATING TAPE APPLIED TO CONDUCTORS AT <br />EACH CABINET OR JUNCTION POINT, THE FOLLOWING SYSTEM OF COLOR <br />CODING SHALL BE ADHERED TO: <br />- GROUND LEADS: GREEN <br />- 120/208 NEUTRAL CONDUCTOR: WHITE <br />- 120/208 VOLT, PHASE CONDUCTORS: BLACK, RED, BLUE <br />5. EXISTING FACILITIES: WHERE EXISTING COLOR CODING SCHEME DIFFERS <br />FROM THAT SPECIFIED HEREIN, CONTRACTOR SHALL ADHERE TO <br />ESTABLISHED BUILDING STANDARD. ADVISE PROJECT ADMINISTRATOR IN <br />WRITING OF COLOR CODING SCHEME BEING USED, <br />6. THE COLOR CODE ASSIGNED TO EACH PHASE WIRE SHALL BE <br />CONSISTENTLY FOLLOWED THROUGHOUT. <br />GROUNDING <br />1. ALL INTERIOR ELECTRICAL SYSTM S SHALL BE COMPLETELY AND <br />EFFECTIVELY GROUNDED AS RE BY NFPA 70 AND AS SPECIFIED <br />HEREIN. `, & <br />n <br />2. METALLIC RACEWAYS SHALL BE MECHANICALLY AND ELECTRICALLY <br />SECURE AT ALL JOINTS AND AT ALL BOXES, CABINETS, FITTINGS, AND <br />EQUIPMENT. METALLIC RACEWAYS SHALL BE CONNECTED TO A DIRECT <br />GROUND AT POINT OF ELECTRICAL SERVICE ENTRANCE AND SHALL BE <br />ELECTRICALLY CONTINUOUS THROUGHOUT THE ENTIRE SYSTEM. <br />3. ALL GROUND CONDUCTORS SHALL BE INSULATED COPPER UNLESS <br />OTHERWISE NOTED. <br />4. RACEWAYS WITH NO. 10 OR 12 AWG PHASE CONDUCTORS FOR <br />RECEPTACLES, LIGHT FIXTURES AND SIMILAR CIRCUITS (NEW BRANCH <br />CIRCUITS) SHALL BE PROVIDED WITH A PARITY SIZED GREEN EQUIPMENT <br />GROUND CONDUCTOR. GROUND CONDUCTOR SHALL BE INSTALLED IN <br />ENTIRE RACEWAY SYSTEM INCLUDING WALL SWITCHES AND FLEXIBLE <br />CONDUIT TO LIGHT FIXTURES. EQUIPMENT GROUND CONDUCTOR SIZES FOR <br />CIRCUITS WITH PHASE CONDUCTORS LARGER THAN NO. 12 AWG ARE <br />INDICATED ON DRAWINGS, <br />PANEL BOARDS AND SAFETY SWITCHES <br />1. ELECTRICAL PANELS AND DISCONNECTS SHALL BE PLUMB AND <br />SECURELY SUPPORTED. IF SUITABLE SUPPORT DOES NOT EXIST, PROVIDE <br />SUPPORTING STRUCTURE WITH PROPERLY SIZED "U" CHANNEL. <br />2. CIRCUIT BREAKERS SHALL BE MOLDED PLASTIC CASE WITH <br />QUICK -MAKE, QUICK -BREAK CONTACTS, BREAKERS SHALL HAVE THERMAL <br />MAGNETIC TRIP UNITS. MULTI -POLE BREAKERS SHALL HAVE A FACTORY <br />INSTALLED COMMON TRIP, TIE BARS INSTALLED IN THE FIELD ARE NOT <br />ACCEPTABLE. <br />3. SAFETY SWITCH MECHANISMS SHALL BE QUICK -MAKE, QUICK- BREAK. <br />COVER SHALL BE INTERLOCKED WITH MECHANISM TO PREVENT OPENING <br />WITH HANDLE IN THE "ON" POSITION. ALL ENCLOSURES SHALL BE PRIMED <br />AND FINISHED TO RESIST RUSTING AND CORROSION. SWITCHES SHALL BE <br />GENERAL ELECTRIC, OR SQUARE -D (MATCH BUILDING STANDARD WHERE <br />APPLICABLE), <br />4. FUSES SHALL BE DUAL ELEMENT, CARTRIDGE TYPE. FUSES SHALL BE <br />BUSMAN "FUSETRON" OR CHASE SHAWMUT "TRIONIC ", THE CONTRACTOR <br />SHALL PROVIDE SIZES BASED ON EQUIPMENT NAMEPLATE DATA. <br />CONTRACTOR SHALL FURNISH AS SPARE, A DUPLICATE CARTRIDGE FOR <br />EACH FUSE INSTALLED. <br />5, PANELBOARDS SHALL BE DEADFRONT TYPE, COPPER BUS BARS, AND <br />BOLT -ON TYPE BRANCH CIRCUIT BREAKERS. <br />LIGHTING <br />1. CONTRACTOR SHALL PROVIDE ALL MOUNTING HARDWARE AND LIGHTING <br />OPTIONS TO PROVIDE A PROPER LIGHTING INSTALLATION. <br />2, BALLASTS FOR FLUORESCENT LAMPS SHALL BE HIGH POWER FACTOR <br />TYPE AND SHALL BEAR THE CBM, AND UL LABELS, ALL BALLASTS SHALL <br />BE UNDERWRITERS CLASS P. BALLASTS SHALL BE MAGNETEK TRIAD 'HP' <br />OCTIC OR EQUAL BY MOTOROLA. BALLASTS FOR FLUORESCENT FIXTURES <br />SHALL BE INDIVIDUALLY FUSED, FUSES SHALL BE INSTALLED ON THE LINE <br />SIDE OF THE BALLAST. <br />3. FIXTURES SHALL BE PROPERLY SUPPORTED AND ALIGNED. LIGHTING <br />FIXTURES SHALL BE CLEANED AND LAMPED IMMEDIATELY PRIOR TO FINAL <br />INSPECTION. <br />4. USE STEEL 4" SQUARE BACK BOXES FOR SURFACE MOUNT FIXTURES. <br />RECEPTACLES AND SWITCHES <br />1. UNLESS OTHERWISE NOTED, WALL PLATES SHALL BE MOLDED NYLON, <br />WH I TE. <br />2. PROVIDE WALLPLATES FOR SINGLE AND COMBINATION WIRING DEVICES, <br />OF TYPES, SIZES, AND GANGING TO MATCH INSTALLATION, SELECT PLATES <br />WHICH MATE AND MATCH WIRING DEVICES. SECURE WALL PLATES WITH <br />METAL SCREWS. SCREW HEADS SHALL BE COLORED TO MATCH FINISH OF <br />PLATE. <br />3, GENERAL PURPOSE RECEPTACLES SHALL BE 125V, 20A, NEMA 5 -20R, <br />WHITE. PROVIDE LEVITON - DUPLEX: CR20, SIMPLEX: 5801, OR <br />APPROVED EQUAL. <br />4. ISOLATED GROUND (IG) RECEPTACLES SHALL BE 125V, 20A, NEMA <br />5 -20R, ORANGE WITH GREEN TRIANGLE. PROVIDE LEVITON - DUPLEX: <br />5362 -IG, SIMPLEX: 5361 -IG, OR APPROVED EQUAL. <br />5. GROUND FAULT CIRCUIT INTERRUPTER (GFI) RECEPTACLES SHALL BE <br />125V, 20A, NEMA 5 -20R, WHITE TEST AND RESET BUTTONS ON FRONT <br />FACE. PROVIDE LEVITON: 6899, OR APPROVED EQUAL, <br />6. RECEPTACLES DEDICATED TO A SINGLE PIECE OF EQUIPMENT SHALL <br />MATCH SAID EQUIPMENT REQUIREMENTS. CONTRACTOR SHALL MAKE <br />RECEPTACLE SELECTION BASED EQUIPMENT VOLTAGE, AMPERAGE, AND <br />PLUG CONFIGURATION. INCLUDE THIS INFORMATION IN SHOP DRAWING <br />SUBMITTALS. ADVISE ENGINEER OF DISCREPANCIES. <br />7, SWITCHES SHALL BE WHITE, AC QUIET, SNAP TYPE, RATED 120/277V, <br />20A. SWITCH TYPE SHALL BE AS INDICATED ON DRAWINGS. PROVIDE <br />LEVITON - SINGLE POLE: CS120, TWO POLE: CS220, THREE -WAY: CS320, <br />FOUR -POLE: CS420, OR APPROVED EQUAL. <br />8. APPROVED MANUFACTURERS: HUBBLE, LEVITON, OR GENERAL <br />ELECTRIC, <br />COMMUNICATIONS: <br />1. FURNISH SINGLE GANG BOX AND 3/4" CONDUIT WITH PULL WIRE FOR <br />EACH TELEPHONE /DATA SYSTEM DEVICE LOCATION. EXTEND CONDUIT TO <br />ACCESSIBLE SPACE ABOVE CEILING AND TERMINATE WITH INSULATING <br />BUSHING, COVER UNUSED BOXES WITH BLANK COVER PLATE. OWNER'S <br />CONTRACTOR SHALL PROVIDE TELEPHONE /DATA CABLING AND DEVICES. <br />2. FURNISH SINGLE GANG BOX AND 3/4" CONDUIT WITH PULL WIRE FOR <br />EACH CABLE TV SYSTEM DEVICE LOCATION EXTEND CONDUIT TO <br />ACCESSIBLE SPACE ABOVE CEILING AND TERMINATE WITH INSULATING <br />BUSHING. COVER UNUSED BOXES WITH BLANK COVER PLATE. OWNER'S <br />CONTRACTOR SHALL PROVIDE CABLE TV CABLING AND DEVICES. <br />3. PROVIDE 3/4" THICK BACKBOARD WITH COPPER GROUND BAR FOR <br />DATA, TELEPHONE, AND CABLE TV EQUIPMENT. PROVIDE #6 AWG (MIN) <br />GROUND CONDUCTOR TO GROUNDING ELECTRODE SYSTEM. GROUND BUSS <br />OF SERVICE ENTRANCE PANEL IS PREFERRED. REFER TO PLANS FOR <br />BACKBOARD LOCATION(S) AND COORDINATE WITH OWNER'S <br />REPRESENTATIVE FOR SPECIFIC REQUIREMENTS, <br />Di_Do TP CAD SYM DOD LEGEND <br />LOAD SUMMARY <br />ESTIMATED <br />CONNECTED LOAD FUTURE LOAD <br />kVA kVA <br />SYMBOL <br />DESCRIPTION <br />MOUNTING <br />F: E l <br />2' X 4' FLUORESCENT TROFFER, LETTER INDICATES TYPE <br />SEE FIXTURE SCHEDULE <br />A O_ <br />CEILING MOUNTED LIGHT FIXTURE, LETTER INDICATES TYPE. <br />SEE FIXTURE SCHEDULE <br />10.02 <br />SWITCH, SINGLE POLE, 20 A, 120/277 VAC, REFER TO SPECIFICATIONS FOR DEVICE 48" AFF TO TOP <br />0.00 0.00 <br />COLOR, WALL PLATE COLOR AND MATERIAL, AND DEVICE MODEL NUMBER. UNLESS NOTED OTHERWISE <br />SWITCH, THREE -WAY, 20 A, 1201277 VAC. REFER TO SPECIFICATIONS FOR DEVICE <br />48" AFF TO TOP <br />amperes at 208 V 3 PHASE <br />COLOR, WALL PLATE COLOR AND MATERIAL, AND DEVICE MODEL NUMBER, <br />UNLESS NOTED OTHERWISE <br />* EST IMATED LOAD B ASED ON NEC <br />DUPLEX RECEPTACLE, 20 A, 120 VAC. REFER TO SPECIFICATIONS FOR DEVICE <br />UNLESS NOTED OTHERWISE, <br />COLOR, WALL PLATE REQUIREMENTS, AND DEVICE MODEL NUMBER, <br />THE SYMBOLS SHOWN BELOW <br />DEFINE MOUNTING HEIGHTS: <br />TWO (2) DUPLEX RECEPTACLES IN COMMON BOX, 20 A, 120 VAC. REFER TO <br />00 0 <br />SPECIFICATIONS FOR DEVICE COLOR, WALL PLATE REQUIREMENTS, AND DEVICE <br />18" AFF TO CENTERLINE <br />MODEL NUMBER, <br />ABOVE COUNTER <br />SIMPLEX REFER SPECIF FOR DEVICE <br />COLOR ,WALLEPLATEEREQUIREMENNTS, MODEL NUMBER, <br />BELOW COUNTER <br />COMMUNICATIONS OUTLET: SINGLE GANG, DEEP, FLUSH MOUNT BOX AND 3/4" C <br />18" AFF TO CENTERLINE <br />WITH PULLSTRING, STUB CONDUIT UP INTO ACCESSIBLE CEILING SPACE AND <br />UNLESS NOTED OTHERWISE <br />TERMINATE WITH INSULATING BUSHING. COVER UNUSED BOXES WITH BLANK PLATE <br />TO MATCH DEVICE WALLPLATES AND IDENTIFY FOR FUTURE. <br />L <br />FUSED DISCONNECT SWITCH, <br />60" AFF TO TOP <br />60/60/3/N3R <br />CURRENT RATING /FUSING /NUMBER OF POLES /ENCLOSURE <br />UNLESS NOTED OTHERWISE <br />NON -FUSED DISCONNECT SWITCH, <br />60" AFF TO TOP <br />60 /N11i <br />CURRENT RATING /FUSING /NUMBER OF POLES /ENCLOSURE <br />UNLESS NOTED OTHERWISE <br />BRANCH CIRCUIT PANELBOARD, 120/208 V OR 120/240 V, SURFACE MOUNT <br />78" AFF TO TOP <br />UNLESS NOTED OTHERWISE <br />�j <br />ELECTRIC METER <br />60" AFF TO TOP <br />UNLESS NOTED OTHERWISE <br />"GFI" NOTATION MEANS ASSOCIATED DEVICE SHALL BE GROUND FAULT CIRCUIT <br />AS DEFINED BY SYMBOL <br />GFI <br />INTERRUPTER TYPE, REFER TO SPECIFICATIONS FOR DEVICE COLOR, WALL PLATE <br />REQUIREMENTS, AND MODEL NUMBER. <br />WP <br />"WP" NOTATION MEANS ASSOCIATED DEVICE SHALL BE MOUNTED IN WEATHERPROOF <br />AS DEFINED BY SYMBOL <br />ENCLOSURE. <br />HOME RUN TO PANEL. LABEL INDICATES PANEL NAME AND CIRCUIT NUMBER(S). <br />SEE SPECIFICATIONS <br />CIRCUITS WITHOUT FURTHER DESIGNATION INDICATES A 2 WIRE CIRCUIT WITH A <br />L1A -1 <br />PARITY SIZED EQUIPMENT GROUND. CIRCUIT WITH MORE THAN 2 WIRES IS SHOWN <br />AS FOLLOWS: <br />48" AFF TO TOP <br />= 3 PHASE WIRES AND AN EQUIPMENT GROUND <br />UNLESS NOTED OTHERWISE <br />XX = 3 PHASE WIRES, 1 NEUTRAL AND AN EQUIPMENT GROUND <br />= 3 PHASE WIRES, 1 NEUTRAL, AN ISOLATED GROUND AND AN EQUIPMENT GROUND <br />ALL CONDUCTORS ARE #12 AWG Cu UNLESS NOTED OTHERWISE. <br />�\ <br />RACEWAY CONCEALED IN WALL OR ABOVE CEILINGS <br />SEE SPECIFICATIONS <br />/ \ <br />RACEWAY CONCEALED UNDER FLOOR OR BELOW GRADE <br />SEE SPECIFICATIONS <br />- - - - <br />RACEWAY EXPOSED ON WALL OR CEILING <br />SEE SPECIFICATIONS <br />120/208V., 3 PHASE <br />SECONDARY SERVICE <br />1 14 , 648 AFC <br />22,000 AIC <br />LOAD SUMMARY <br />ESTIMATED <br />CONNECTED LOAD FUTURE LOAD <br />kVA kVA <br />10* X 10" X LENGTH AS REQUIRED NEMA 3R WIREW AY <br />F <br />0 1101 101 <br />METER METER METER J <br />4 <br />FUTURE FUTURE <br />PANEL PANEL PANEL <br />A' <br />1 <br />LOAD DESCRIPTION <br />LOAD SUMMARY <br />ESTIMATED <br />CONNECTED LOAD FUTURE LOAD <br />kVA kVA <br />TOTAL OAD <br />L <br />k L <br />LIGHTING 1.25 demand factor applied) <br />7.90 4.50 <br />12.40 <br />HVAC heat load used for calculation <br />47.61 16.00 <br />63.61 <br />RECEPTACLE (demand factor applied) <br />8.82 1.20 <br />10.02 <br />misc. <br />0.00 0.00 <br />0.00 <br />TOTAL= <br />86.03 <br />amperes at 208 V 3 PHASE <br />238.80 amps <br />amps <br />* EST IMATED LOAD B ASED ON NEC <br />3 500 <br />MCM N, #� <br />4 <br />1/2° C. <br />cc <br />vv 6 ' -0 " v <br />MI IN, I <br />ONE-LINE <br />NO SCALE <br />v <br />0 ONE -LINE DIAGRAM NOTES <br />1) METER PER UTILITY COMPANY REQUIREMENTS. <br />2) 120/208V., 3 PHASE LIGHTNING ARRESTOR. <br />\AN 3) FURNISH AND INSTALL WIRE WAY CAPABLE OF ACCEPTING <br />ADDITIONAL TWO METERS AND PANELS FOR POSSIBLE <br />FUTURE TENANTS. <br />') (3) #4/0, #4/0 N., #2 G.C., 2 -112" C. <br />5) GROUNDING ELECTRODE SYSTEM: (2) 5/8 "x10' COPPER <br />CLAD GROUND RODS, BUILDING STEEL, AND METAL COLD <br />WATER PIPE. <br />6) TIME CLOCK IN NEMA 3R ENCLOSURE. SEE DETAIL ON <br />SHEET E -2 FOR MORE INFORMATION, <br />7) 120V, PHOTOCELL. MOUNT FACING NORTH AND AS HIGH AS <br />POSSIBLE ON BUILDING. <br />A <br />13 <br />Architec n <br />ctu e 0 e. Inc. <br />1526 Junior Court <br />Lehigh, Florida 33971 <br />Phone: 239.693.8687 <br />Fax: 239.690.0795 <br />E -mail: architectureone @iline.com <br />License no: AA 0003632 <br />Consultant: <br />F <br />Project: <br />Proposed Building for <br />K &KGlass <br />Zepherhills, Florida <br />Client <br />Apco Building Systems, Inc. <br />106 Whitaker Road <br />Lutz, Florida <br />C <br />JUL 2 9 1003 <br />rain 6. Curb^ m n N0. moo <br />Project Number: 0220 <br />Copyright 2002 © Architecture One, Inc. reserves copyright and other rights restricting <br />these documents to the original site or purpose for which they were prepared. <br />Reproductions, changes or assignments are prohibitted. <br />Sheet Title: <br />Specifications <br />One Line and <br />Legend <br />Sheet <br />Eml <br />