1
<br />GENERAL
<br />1. THE ELECTRICAL CONTRACTOR REFERRED TO HEREAFTER, AS THE
<br />"CONTRACTOR" SHALL PROVIDE COMPLETE ELECTRICAL SYSTEMS AS
<br />INDICATED ON THE DRAWINGS AND SPECIFIED HEREIN.
<br />3
<br />2, CONTRACTOR SHALL PROVIDE PROTECTIVE DEVICES, CONDUCTORS,
<br />SUPPORTS, RACEWAYS, AND MISCELLANEOUS MATERIALS TO SERVE ALL
<br />DEVICES REQUIRING ELECTRICAL POWER.
<br />3. CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS, FEES, AND
<br />INSPECTIONS REQUIRED TO COMMENCE AND COMPLETE ELECTRICAL WORK,
<br />4, CONTRACTOR SHALL CONDUCT A THROUGH SITE INSPECTION TO
<br />FAMILIARIZE HIMSELF WITH EXISTING CONDITIONS AND ALL ASPECTS OF HIS
<br />SCOPE OF WORK, SUCH AN INSPECTION SHALL BE CONDUCTED PRIOR TO
<br />SUBMITTING A BID.
<br />5. CONTRACTOR SHALL REFER TO INTERIOR ARCHITECTURAL CASE WORK
<br />ELEVATIONS FOR EXACT MOUNTING HEIGHTS AND /OR LOCATIONS OF
<br />SWITCHES, OUTLETS, AND WIRING DEVICES.
<br />6, CONTRACTOR SHALL MAINTAIN A COMPLETE TEMPORARY POWER AND
<br />LIGHTING SYSTEM DURING CONSTRUCTION.
<br />7. THE CONTRACTOR SHALL PROVIDE, DROP CLOTH, RUBBER MATS AND
<br />PLYWOOD COVERS FOR OWNERS EQUIPMENT SUSCEPTIBLE TO DAMAGE
<br />DURING CONSTRUCTION. VERIFY SPECIFIC LOCATIONS WITH OWNER'S
<br />REPRESENTATIVE.
<br />8. ALL WORK SHALL BE PERFORMED DURING PERIODS ACCEPTABLE TO THE
<br />OWNER. SCHEDULE ALL WORK WITH THE OWNER'S REPRESENTATIVE BEFORE
<br />PROCEEDING.
<br />9, THE CONTRACTOR SHALL PERFORM TEMPORARY WORK NECESSARY TO
<br />MAINTAIN CONTINUITY OF ELECTRICAL SERVICE WHEN CONNECTION IS MADE
<br />TO EXISTING SYSTEMS AND FACILITIES. EXISTING SERVICE SHALL NOT BE
<br />INTERRUPTED WITHOUT PRIOR CONSENT OF THE OWNER'S REPRESENTATIVE.
<br />10. AT PROJECT COMPLETION, THE CONTRACTOR SHALL INSURE THAT ALL
<br />ELECTRICAL SYSTEMS OPERATE PROPERLY, CONTRACTOR SHALL
<br />DEMONSTRATE OPERATION OF EACH SYSTEM WITH THE OWNER'S
<br />REPRESENTATIVE.
<br />11. CONTRACTOR SHALL COORDINATE AND VERIFY WITH LOCAL POWER
<br />COMPANY THE FOLLOWING:
<br />EXACT LOCATION OF SERVICE CONNECTION,
<br />- ELECTRICAL CHARACTERISTICS (VOLTAGE AND PHASING)
<br />- AVAILABLE FAULT CURRENT
<br />METERING REQUIREMENTS
<br />CODES AND STANDARDS
<br />1. ELECTRICAL WORK SHALL COMPLY WITH THE LATEST EDITION OF
<br />- NFPA 70 (NATIONAL ELECTRICAL CODE)
<br />- NFPA 101 (LIFE SAFETY CODE)
<br />- CODES SPECIFIC TO OTHER SECTIONS HEREIN
<br />2. ELECTRICAL WORK SHALL COMPLY WITH ALL LOCAL AND STATE
<br />ELECTRICAL CODES AND IN ACCORDANCE WITH REQUIREMENTS OF THE
<br />AUTHORITY HAVING JURISDICTION (AHJ).
<br />QUALITY
<br />1. WORKMANSHIP SHALL BE HIGH QUALITY AND FOLLOW INDUSTRY
<br />STANDARDS. SUBSTANDARD WORK WILL BE REJECTED. THE CONTRACTOR IS
<br />RESPONSIBLE FOR REPAIR AND REWORK TO RECTIFY SUBSTANDARD WORK.
<br />QUALITY OF WORK SHALL BE DETERMINED BY THE OWNER'S
<br />REPRESENTATIVE AND /OR ENGINEER OF RECORD,
<br />I NTERFERENCES
<br />1, PLANS ARE GENERALLY DIAGRAMMATIC, THE CONTRACTOR SHALL
<br />COORDINATE WITH THE OTHER TRADES SO THAT INTERFERENCES BETWEEN
<br />CONDUITS, PIPING, EQUIPMENT, DUCTS, AND STRUCTURAL WORK WILL BE
<br />AVOIDED. IN SUCH CASE, THE CONTRACTOR FAILS TO COORDINATE WITH
<br />OTHER TRADES AND INTERFERENCES ARE ALLOWED DEVELOP, THE OWNER'S
<br />AUTHORIZED REPRESENTATIVE WILL DECIDE WHICH EQUIPMENT, DUCT,
<br />CONDUIT, ETC., MUST BE RELOCATED, REGARDLESS OF WHICH WAS
<br />INSTALLED FIRST, ELECTRICAL REWORK REQUIRED TO CORRECT
<br />INTERFERENCES WILL BE AT THE CONTRACTORS EXPENSE.
<br />MATERIALS
<br />1. ALL ELECTRICAL EQUIPMENT AND MATERIALS SHALL BE APPROVED BY
<br />UNDERWRITERS LABORATORY FOR THE APPLICATION AND SHALL BEAR A
<br />UL LABEL,
<br />2. ELECTRICAL ENCLOSURES SHALL BE NEMA RATED. UNLESS OTHERWISE
<br />NOTED, ENCLOSURE RATINGS SHALL ADHERE TO THE FOLLOWING:
<br />- NEMA 1 INDOOR
<br />- NEMA 3R OUTDOOR
<br />- NEMA 4 CORROSIVE ENVIRONMENT
<br />GUARANTEE
<br />1. CONTRACTOR SHALL GUARANTEE ALL WORK FOR A PERIOD OF ONE
<br />YEAR FROM DATE OF OWNER'S ACCEPTANCE, THE CONTRACTOR SHALL
<br />RECTIFY ANY DEFECTS DUE TO FAULTY MATERIALS OR WORKMANSHIP AND
<br />PAY FOR DAMAGE CAUSED BY FAILURE AND REWORK. THE OWNER WILL
<br />GIVE NOTICE OF DEFECTS WITH REASONABLE PROMPTNESS AFTER
<br />DISCOVERY. THE CONTRACTOR SHALL START REWORK WITHIN TEN (10)
<br />WORKING DAYS OF NOTIFICATION AND COMPLETE REPAIRS IN A TIMELY
<br />MANNER.
<br />SUBMITTAL DATA AND RECORD DRAWINGS
<br />1. THE ELECTRICAL DESIGN IS BASED ON A SINGLE MANUFACTURE OF
<br />SWITCH GEAR, LIGHTS, TRANSFORMER, GENERATORS, ETC, WHEREAS
<br />SUBSTITUTIONS ARE PROVIDED IN LIEU OF THAT WHICH IS SPECIFIED, THE
<br />CONTRACTOR ASSUMES FULL RESPONSIBILITY FOR ANY IMPACT TO THE
<br />INSTALLATION, CONTRACTOR SHALL VERIFY THAT SUBSTITUTIONS CAN
<br />FUNCTION SATISFACTORILY IN THEIR DESIGNATED SPACE AND CHANGES IN
<br />OPERATING CHARACTERISTICS DO NOT DEGRADE THE INSTALLATION.
<br />2. SUBMIT MANUFACTURER'S DATA (MINIMUM 5 COPIES) FOR ELECTRICAL
<br />GEAR, LIGHT FIXTURES, WIRING DEVICES AND OTHER EQUIPMENT SPECIFIED
<br />HEREIN, SUBMIT SHOP DRAWINGS IN BOOKLET FORM WITH SEPARATE SHEE
<br />FOR EACH DEVICE. PROVIDE EQUIPMENT IDENTIFICATION AS DESIGNATED/
<br />ON PLANS FOR EACH SHOP DRAWING CUT SHEET SUBMITTED.
<br />3. AT PROJECT COMPLETION THE CONTRACTOR SHALL COMPILE TWO (2)\
<br />COMPLETE SETS OF RECORD DRAWINGS INDICATING ALL DEVIATIONS FROM
<br />CONSTRUCTION DOCUMENTS, ONE SET SHALL BE ISSUED TO THE
<br />ARCHITECT AND ONE SET SHALL BE ISSUED TO OWNER'S REPRESENTATIVE.
<br />1
<br />IDENTIFICATION OF EQUIPMENT
<br />1. LABEL ALL ELECTRICAL EQUIPMENT WITH ENGRAVED LAMINATED PLASTIC
<br />NAMEPLATE THAT CLEARLY DESCRIBES THE EQUIPMENT NAME, VOLTAGE,
<br />AMPERAGE RATING, AND FUNCTION. NAMEPLATES SHALL BE RED
<br />BACKGROUND WITH WHITE STENCILED UPPER CASE LETTERING A MINIMUM
<br />OF 3/16" IN HEIGHT,
<br />2. INSTALL VINYL CLOTH SELF- ADHESIVE CIRCUIT LABELS ON ALL WIRE
<br />AND CABLE IN JUNCTION BOXES, WIRE TROUGHS, AND PANELBOARD WIRING
<br />GUTTERS.
<br />3. IDENTIFY JUNCTION BOXES WITH PERMANENT MARKER INDICATING
<br />PANELBOARD AND CIRCUIT NUMBERS OF WIRING CONTAINED WITHIN,
<br />4. PROVIDE TYPEWRITTEN PANELBOARD DIRECTORIES WITH ACCURATE AS
<br />BUILT INFORMATION. DIRECTORIES SHALL REFLECT TYPE OF LOAD AND
<br />AREA SERVED FOR EACH BREAKER.
<br />RACEWAYS AND FITTINGS
<br />1. CONDUIT SHALL BE PROPERLY ALIGNED, GROUPED AND SUPPORTED.
<br />EXPOSED CONDUIT SHALL BE INSTALLED AT RIGHT ANGLES TO OR
<br />PARALLEL TO THE PRINCIPAL STRUCTURAL MEMBERS, CONDUIT SHALL BE
<br />SUPPORTED AT INTERVALS NOT EXCEEDING 8 FEET. CONDUIT SHALL BE
<br />SUPPORTED FROM STRUCTURE AND NOT FROM CEILING SUPPORT SYSTEM,
<br />2. EXCEPT IN MECHANICAL ROOMS, ELECTRICAL ROOMS, OPEN STRUCTURE
<br />CANOPIES, AND EXTERIOR SERVICE ENTRANCES, CONDUIT SHALL BE
<br />CONCEALED THROUGHOUT THE FACILITY,
<br />3. PROVIDE NYLON PULL CORD IN ALL EMPTY CONDUITS,
<br />4. ELECTRICAL METAL TUBING (EMT) SHALL BE GALVANIZED STEEL FOR
<br />DRY INTERIOR INSTALLATIONS AND ALUMINUM FOR, DAMP, WET OR
<br />EXTERIOR INSTALLATIONS. COUPLINGS AND CONNECTORS SHALL BE SET
<br />SCREW TYPE FOR STEEL, EMT SHALL BE USED CONCEALED ABOVE
<br />CEILINGS, CONCEALED IN WALLS, AND EXPOSED IN MECHANICAL AND
<br />ELECTRICAL ROOMS.
<br />5. FLEXIBLE METALLIC CONDUIT IN DRY LOCATIONS SHALL BE
<br />UNDERWRITERS' APPROVED, STEEL, ZINC COATED, SINGLE STRIP TYPE,
<br />FITTINGS SHALL BE AS MANUFACTURED BY THOMAS AND BETTS
<br />"TITE- BITE ", OR APPROVED EQUAL,
<br />6. FLEXIBLE METALLIC CONDUIT IN DAMP OR WET LOCATIONS SHALL BE
<br />UNDERWRITERS' APPROVED, GALVANIZED STEEL WITH MOISTURE PROOF PVC
<br />JACKET . FITTINGS SHALL INSULATED THROAT AND LIQUID TIGHT AS
<br />MANUFACTURE BY THOMAS AND BETTS, OR APPROVED EQUAL.
<br />7. GALVANIZED RIGID STEEL (GRS) CONDUIT SHALL BE ILL APPROVED HOT
<br />DIPPED GALVANIZED. GRS CONDUIT COUPLINGS SHALL BE THREADED
<br />HEAVY WALL GALVANIZED STEEL. USE 90 DEGREE GRS SWEEPS AND GRS
<br />RISERS IN UNDERGROUND PVC CONDUIT RUNS. PAINT ALL GALVANIZED
<br />RIGID CONDUITS INSTALLED BELOW GRADE WITH RUST INHIBITING PAINT.
<br />8. PVC CONDUIT SHALL BE UL LISTED SCHEDULE 40 PVC UV RESISTANT,
<br />PVC CONDUIT MAY BE USED BELOW GRADE, UNDER FLOORS, IN CONCRETE,
<br />AND FOR GROUNDING SYSTEM CONDUCTORS
<br />9. CONDUIT AND WIRING PENETRATING RATED FLOORS AND WALLS SHALL
<br />BE SEALED WITH A UL RATED ASSEMBLY TO MAINTAIN FIRE RATING AND
<br />INTEGRITY OF SEPARATION.
<br />10. METAL CLAD CABLE (TYPE MC) IS PERMISSABLE IF INSTALLED PER
<br />NEC ARTICLE 334. FITTINGS SHALL BE INSULATED THROAT AS
<br />MANUFACTURED BY THOMAS AND BETTS "TITE- BITE ", OR APPROVED
<br />EQUAL,
<br />BOXES
<br />1. BOXES SHALL BE RIGIDLY MOUNTED AND COVERED WITH MATCHING
<br />PLATE, OPEN KNOCK -OUTS OR HOLES IN BOXES SHALL BE PLUGGED
<br />WITH A SUITABLE BLANKING DEVICE,
<br />2. SURFACE MOUNT EXTERIOR OUTLET BOXES SHALL BE CAST ALUMINUM
<br />WITH WEATHERPROOF ALUMINUM GASKETED COVER.
<br />3. FLUSH MOUNT EXTERIOR OUTLET BOXES SHALL 4" SQUARE STEEL WITH
<br />MASONRY RING AND WEATHERPROOF GASKETED CAST ALUMINUM COVER.
<br />CONDUCTORS
<br />1, UNLESS OTHERWISE INDICATED, BRANCH CIRCUIT CONDUCTORS SHALL BE
<br />SOLID NO. 12 AWG COPPER. BRANCH CIRCUITS RUN OVER 75 FEET IN
<br />LENGTH, MEASURING ONE WAY FROM THE FIRST OUTLET OF THE CIRCUIT
<br />TO THE PANEL, SHALL BE SOLID N0, 10 AWG COPPER FOR THE ENTIRE
<br />CIRCUIT.
<br />2, SPLICES AND TAPS SHALL UTILIZE SOLDERLESS LUGS FOR #8 AWG AND
<br />LARGER, SPLICES AND TAPS SHALL FORM A ELECTRICAL AND
<br />MECHANICALLY SECURE CONNECTION. LUGS SHALL BE CORRECTLY SIZED
<br />FOR THE CONDUCTORS, TAPE JOINTS WITH VINYL PLASTIC ELECTRICAL
<br />TAPE.
<br />3. ALLOW SUFFICIENT CABLE SLACK IN BOXES, OUTLETS AND CABINETS TO
<br />MAKE CONNECTION AND INSURE THERE IS NO BINDING AT THE
<br />SPLICE /TAP.
<br />4. CONDUCTORS SHALL BE COPPER. UNLESS OTHERWISE NOTED,
<br />INSULATION SHALL BE DUAL TYPE THHN /THWN 75 °C. CONDUCTORS SHALL
<br />BE COLOR CODED IN ACCORDANCE WITH NFC 70. COLOR CODING SHALL BE
<br />BY MEANS OF COLORED INSULATING MATERIAL, COLORED BRAID OR
<br />JACKET OVER THE INSULATION OR BY MEANS OF SUITABLE COLORED,
<br />PERMANENT, NON- AGING, INSULATING TAPE APPLIED TO CONDUCTORS AT
<br />EACH CABINET OR JUNCTION POINT, THE FOLLOWING SYSTEM OF COLOR
<br />CODING SHALL BE ADHERED TO:
<br />- GROUND LEADS: GREEN
<br />- 120/208 NEUTRAL CONDUCTOR: WHITE
<br />- 120/208 VOLT, PHASE CONDUCTORS: BLACK, RED, BLUE
<br />5. EXISTING FACILITIES: WHERE EXISTING COLOR CODING SCHEME DIFFERS
<br />FROM THAT SPECIFIED HEREIN, CONTRACTOR SHALL ADHERE TO
<br />ESTABLISHED BUILDING STANDARD. ADVISE PROJECT ADMINISTRATOR IN
<br />WRITING OF COLOR CODING SCHEME BEING USED,
<br />6. THE COLOR CODE ASSIGNED TO EACH PHASE WIRE SHALL BE
<br />CONSISTENTLY FOLLOWED THROUGHOUT.
<br />GROUNDING
<br />1. ALL INTERIOR ELECTRICAL SYSTM S SHALL BE COMPLETELY AND
<br />EFFECTIVELY GROUNDED AS RE BY NFPA 70 AND AS SPECIFIED
<br />HEREIN. `, &
<br />n
<br />2. METALLIC RACEWAYS SHALL BE MECHANICALLY AND ELECTRICALLY
<br />SECURE AT ALL JOINTS AND AT ALL BOXES, CABINETS, FITTINGS, AND
<br />EQUIPMENT. METALLIC RACEWAYS SHALL BE CONNECTED TO A DIRECT
<br />GROUND AT POINT OF ELECTRICAL SERVICE ENTRANCE AND SHALL BE
<br />ELECTRICALLY CONTINUOUS THROUGHOUT THE ENTIRE SYSTEM.
<br />3. ALL GROUND CONDUCTORS SHALL BE INSULATED COPPER UNLESS
<br />OTHERWISE NOTED.
<br />4. RACEWAYS WITH NO. 10 OR 12 AWG PHASE CONDUCTORS FOR
<br />RECEPTACLES, LIGHT FIXTURES AND SIMILAR CIRCUITS (NEW BRANCH
<br />CIRCUITS) SHALL BE PROVIDED WITH A PARITY SIZED GREEN EQUIPMENT
<br />GROUND CONDUCTOR. GROUND CONDUCTOR SHALL BE INSTALLED IN
<br />ENTIRE RACEWAY SYSTEM INCLUDING WALL SWITCHES AND FLEXIBLE
<br />CONDUIT TO LIGHT FIXTURES. EQUIPMENT GROUND CONDUCTOR SIZES FOR
<br />CIRCUITS WITH PHASE CONDUCTORS LARGER THAN NO. 12 AWG ARE
<br />INDICATED ON DRAWINGS,
<br />PANEL BOARDS AND SAFETY SWITCHES
<br />1. ELECTRICAL PANELS AND DISCONNECTS SHALL BE PLUMB AND
<br />SECURELY SUPPORTED. IF SUITABLE SUPPORT DOES NOT EXIST, PROVIDE
<br />SUPPORTING STRUCTURE WITH PROPERLY SIZED "U" CHANNEL.
<br />2. CIRCUIT BREAKERS SHALL BE MOLDED PLASTIC CASE WITH
<br />QUICK -MAKE, QUICK -BREAK CONTACTS, BREAKERS SHALL HAVE THERMAL
<br />MAGNETIC TRIP UNITS. MULTI -POLE BREAKERS SHALL HAVE A FACTORY
<br />INSTALLED COMMON TRIP, TIE BARS INSTALLED IN THE FIELD ARE NOT
<br />ACCEPTABLE.
<br />3. SAFETY SWITCH MECHANISMS SHALL BE QUICK -MAKE, QUICK- BREAK.
<br />COVER SHALL BE INTERLOCKED WITH MECHANISM TO PREVENT OPENING
<br />WITH HANDLE IN THE "ON" POSITION. ALL ENCLOSURES SHALL BE PRIMED
<br />AND FINISHED TO RESIST RUSTING AND CORROSION. SWITCHES SHALL BE
<br />GENERAL ELECTRIC, OR SQUARE -D (MATCH BUILDING STANDARD WHERE
<br />APPLICABLE),
<br />4. FUSES SHALL BE DUAL ELEMENT, CARTRIDGE TYPE. FUSES SHALL BE
<br />BUSMAN "FUSETRON" OR CHASE SHAWMUT "TRIONIC ", THE CONTRACTOR
<br />SHALL PROVIDE SIZES BASED ON EQUIPMENT NAMEPLATE DATA.
<br />CONTRACTOR SHALL FURNISH AS SPARE, A DUPLICATE CARTRIDGE FOR
<br />EACH FUSE INSTALLED.
<br />5, PANELBOARDS SHALL BE DEADFRONT TYPE, COPPER BUS BARS, AND
<br />BOLT -ON TYPE BRANCH CIRCUIT BREAKERS.
<br />LIGHTING
<br />1. CONTRACTOR SHALL PROVIDE ALL MOUNTING HARDWARE AND LIGHTING
<br />OPTIONS TO PROVIDE A PROPER LIGHTING INSTALLATION.
<br />2, BALLASTS FOR FLUORESCENT LAMPS SHALL BE HIGH POWER FACTOR
<br />TYPE AND SHALL BEAR THE CBM, AND UL LABELS, ALL BALLASTS SHALL
<br />BE UNDERWRITERS CLASS P. BALLASTS SHALL BE MAGNETEK TRIAD 'HP'
<br />OCTIC OR EQUAL BY MOTOROLA. BALLASTS FOR FLUORESCENT FIXTURES
<br />SHALL BE INDIVIDUALLY FUSED, FUSES SHALL BE INSTALLED ON THE LINE
<br />SIDE OF THE BALLAST.
<br />3. FIXTURES SHALL BE PROPERLY SUPPORTED AND ALIGNED. LIGHTING
<br />FIXTURES SHALL BE CLEANED AND LAMPED IMMEDIATELY PRIOR TO FINAL
<br />INSPECTION.
<br />4. USE STEEL 4" SQUARE BACK BOXES FOR SURFACE MOUNT FIXTURES.
<br />RECEPTACLES AND SWITCHES
<br />1. UNLESS OTHERWISE NOTED, WALL PLATES SHALL BE MOLDED NYLON,
<br />WH I TE.
<br />2. PROVIDE WALLPLATES FOR SINGLE AND COMBINATION WIRING DEVICES,
<br />OF TYPES, SIZES, AND GANGING TO MATCH INSTALLATION, SELECT PLATES
<br />WHICH MATE AND MATCH WIRING DEVICES. SECURE WALL PLATES WITH
<br />METAL SCREWS. SCREW HEADS SHALL BE COLORED TO MATCH FINISH OF
<br />PLATE.
<br />3, GENERAL PURPOSE RECEPTACLES SHALL BE 125V, 20A, NEMA 5 -20R,
<br />WHITE. PROVIDE LEVITON - DUPLEX: CR20, SIMPLEX: 5801, OR
<br />APPROVED EQUAL.
<br />4. ISOLATED GROUND (IG) RECEPTACLES SHALL BE 125V, 20A, NEMA
<br />5 -20R, ORANGE WITH GREEN TRIANGLE. PROVIDE LEVITON - DUPLEX:
<br />5362 -IG, SIMPLEX: 5361 -IG, OR APPROVED EQUAL.
<br />5. GROUND FAULT CIRCUIT INTERRUPTER (GFI) RECEPTACLES SHALL BE
<br />125V, 20A, NEMA 5 -20R, WHITE TEST AND RESET BUTTONS ON FRONT
<br />FACE. PROVIDE LEVITON: 6899, OR APPROVED EQUAL,
<br />6. RECEPTACLES DEDICATED TO A SINGLE PIECE OF EQUIPMENT SHALL
<br />MATCH SAID EQUIPMENT REQUIREMENTS. CONTRACTOR SHALL MAKE
<br />RECEPTACLE SELECTION BASED EQUIPMENT VOLTAGE, AMPERAGE, AND
<br />PLUG CONFIGURATION. INCLUDE THIS INFORMATION IN SHOP DRAWING
<br />SUBMITTALS. ADVISE ENGINEER OF DISCREPANCIES.
<br />7, SWITCHES SHALL BE WHITE, AC QUIET, SNAP TYPE, RATED 120/277V,
<br />20A. SWITCH TYPE SHALL BE AS INDICATED ON DRAWINGS. PROVIDE
<br />LEVITON - SINGLE POLE: CS120, TWO POLE: CS220, THREE -WAY: CS320,
<br />FOUR -POLE: CS420, OR APPROVED EQUAL.
<br />8. APPROVED MANUFACTURERS: HUBBLE, LEVITON, OR GENERAL
<br />ELECTRIC,
<br />COMMUNICATIONS:
<br />1. FURNISH SINGLE GANG BOX AND 3/4" CONDUIT WITH PULL WIRE FOR
<br />EACH TELEPHONE /DATA SYSTEM DEVICE LOCATION. EXTEND CONDUIT TO
<br />ACCESSIBLE SPACE ABOVE CEILING AND TERMINATE WITH INSULATING
<br />BUSHING, COVER UNUSED BOXES WITH BLANK COVER PLATE. OWNER'S
<br />CONTRACTOR SHALL PROVIDE TELEPHONE /DATA CABLING AND DEVICES.
<br />2. FURNISH SINGLE GANG BOX AND 3/4" CONDUIT WITH PULL WIRE FOR
<br />EACH CABLE TV SYSTEM DEVICE LOCATION EXTEND CONDUIT TO
<br />ACCESSIBLE SPACE ABOVE CEILING AND TERMINATE WITH INSULATING
<br />BUSHING. COVER UNUSED BOXES WITH BLANK COVER PLATE. OWNER'S
<br />CONTRACTOR SHALL PROVIDE CABLE TV CABLING AND DEVICES.
<br />3. PROVIDE 3/4" THICK BACKBOARD WITH COPPER GROUND BAR FOR
<br />DATA, TELEPHONE, AND CABLE TV EQUIPMENT. PROVIDE #6 AWG (MIN)
<br />GROUND CONDUCTOR TO GROUNDING ELECTRODE SYSTEM. GROUND BUSS
<br />OF SERVICE ENTRANCE PANEL IS PREFERRED. REFER TO PLANS FOR
<br />BACKBOARD LOCATION(S) AND COORDINATE WITH OWNER'S
<br />REPRESENTATIVE FOR SPECIFIC REQUIREMENTS,
<br />Di_Do TP CAD SYM DOD LEGEND
<br />LOAD SUMMARY
<br />ESTIMATED
<br />CONNECTED LOAD FUTURE LOAD
<br />kVA kVA
<br />SYMBOL
<br />DESCRIPTION
<br />MOUNTING
<br />F: E l
<br />2' X 4' FLUORESCENT TROFFER, LETTER INDICATES TYPE
<br />SEE FIXTURE SCHEDULE
<br />A O_
<br />CEILING MOUNTED LIGHT FIXTURE, LETTER INDICATES TYPE.
<br />SEE FIXTURE SCHEDULE
<br />10.02
<br />SWITCH, SINGLE POLE, 20 A, 120/277 VAC, REFER TO SPECIFICATIONS FOR DEVICE 48" AFF TO TOP
<br />0.00 0.00
<br />COLOR, WALL PLATE COLOR AND MATERIAL, AND DEVICE MODEL NUMBER. UNLESS NOTED OTHERWISE
<br />SWITCH, THREE -WAY, 20 A, 1201277 VAC. REFER TO SPECIFICATIONS FOR DEVICE
<br />48" AFF TO TOP
<br />amperes at 208 V 3 PHASE
<br />COLOR, WALL PLATE COLOR AND MATERIAL, AND DEVICE MODEL NUMBER,
<br />UNLESS NOTED OTHERWISE
<br />* EST IMATED LOAD B ASED ON NEC
<br />DUPLEX RECEPTACLE, 20 A, 120 VAC. REFER TO SPECIFICATIONS FOR DEVICE
<br />UNLESS NOTED OTHERWISE,
<br />COLOR, WALL PLATE REQUIREMENTS, AND DEVICE MODEL NUMBER,
<br />THE SYMBOLS SHOWN BELOW
<br />DEFINE MOUNTING HEIGHTS:
<br />TWO (2) DUPLEX RECEPTACLES IN COMMON BOX, 20 A, 120 VAC. REFER TO
<br />00 0
<br />SPECIFICATIONS FOR DEVICE COLOR, WALL PLATE REQUIREMENTS, AND DEVICE
<br />18" AFF TO CENTERLINE
<br />MODEL NUMBER,
<br />ABOVE COUNTER
<br />SIMPLEX REFER SPECIF FOR DEVICE
<br />COLOR ,WALLEPLATEEREQUIREMENNTS, MODEL NUMBER,
<br />BELOW COUNTER
<br />COMMUNICATIONS OUTLET: SINGLE GANG, DEEP, FLUSH MOUNT BOX AND 3/4" C
<br />18" AFF TO CENTERLINE
<br />WITH PULLSTRING, STUB CONDUIT UP INTO ACCESSIBLE CEILING SPACE AND
<br />UNLESS NOTED OTHERWISE
<br />TERMINATE WITH INSULATING BUSHING. COVER UNUSED BOXES WITH BLANK PLATE
<br />TO MATCH DEVICE WALLPLATES AND IDENTIFY FOR FUTURE.
<br />L
<br />FUSED DISCONNECT SWITCH,
<br />60" AFF TO TOP
<br />60/60/3/N3R
<br />CURRENT RATING /FUSING /NUMBER OF POLES /ENCLOSURE
<br />UNLESS NOTED OTHERWISE
<br />NON -FUSED DISCONNECT SWITCH,
<br />60" AFF TO TOP
<br />60 /N11i
<br />CURRENT RATING /FUSING /NUMBER OF POLES /ENCLOSURE
<br />UNLESS NOTED OTHERWISE
<br />BRANCH CIRCUIT PANELBOARD, 120/208 V OR 120/240 V, SURFACE MOUNT
<br />78" AFF TO TOP
<br />UNLESS NOTED OTHERWISE
<br />�j
<br />ELECTRIC METER
<br />60" AFF TO TOP
<br />UNLESS NOTED OTHERWISE
<br />"GFI" NOTATION MEANS ASSOCIATED DEVICE SHALL BE GROUND FAULT CIRCUIT
<br />AS DEFINED BY SYMBOL
<br />GFI
<br />INTERRUPTER TYPE, REFER TO SPECIFICATIONS FOR DEVICE COLOR, WALL PLATE
<br />REQUIREMENTS, AND MODEL NUMBER.
<br />WP
<br />"WP" NOTATION MEANS ASSOCIATED DEVICE SHALL BE MOUNTED IN WEATHERPROOF
<br />AS DEFINED BY SYMBOL
<br />ENCLOSURE.
<br />HOME RUN TO PANEL. LABEL INDICATES PANEL NAME AND CIRCUIT NUMBER(S).
<br />SEE SPECIFICATIONS
<br />CIRCUITS WITHOUT FURTHER DESIGNATION INDICATES A 2 WIRE CIRCUIT WITH A
<br />L1A -1
<br />PARITY SIZED EQUIPMENT GROUND. CIRCUIT WITH MORE THAN 2 WIRES IS SHOWN
<br />AS FOLLOWS:
<br />48" AFF TO TOP
<br />= 3 PHASE WIRES AND AN EQUIPMENT GROUND
<br />UNLESS NOTED OTHERWISE
<br />XX = 3 PHASE WIRES, 1 NEUTRAL AND AN EQUIPMENT GROUND
<br />= 3 PHASE WIRES, 1 NEUTRAL, AN ISOLATED GROUND AND AN EQUIPMENT GROUND
<br />ALL CONDUCTORS ARE #12 AWG Cu UNLESS NOTED OTHERWISE.
<br />�\
<br />RACEWAY CONCEALED IN WALL OR ABOVE CEILINGS
<br />SEE SPECIFICATIONS
<br />/ \
<br />RACEWAY CONCEALED UNDER FLOOR OR BELOW GRADE
<br />SEE SPECIFICATIONS
<br />- - - -
<br />RACEWAY EXPOSED ON WALL OR CEILING
<br />SEE SPECIFICATIONS
<br />120/208V., 3 PHASE
<br />SECONDARY SERVICE
<br />1 14 , 648 AFC
<br />22,000 AIC
<br />LOAD SUMMARY
<br />ESTIMATED
<br />CONNECTED LOAD FUTURE LOAD
<br />kVA kVA
<br />10* X 10" X LENGTH AS REQUIRED NEMA 3R WIREW AY
<br />F
<br />0 1101 101
<br />METER METER METER J
<br />4
<br />FUTURE FUTURE
<br />PANEL PANEL PANEL
<br />A'
<br />1
<br />LOAD DESCRIPTION
<br />LOAD SUMMARY
<br />ESTIMATED
<br />CONNECTED LOAD FUTURE LOAD
<br />kVA kVA
<br />TOTAL OAD
<br />L
<br />k L
<br />LIGHTING 1.25 demand factor applied)
<br />7.90 4.50
<br />12.40
<br />HVAC heat load used for calculation
<br />47.61 16.00
<br />63.61
<br />RECEPTACLE (demand factor applied)
<br />8.82 1.20
<br />10.02
<br />misc.
<br />0.00 0.00
<br />0.00
<br />TOTAL=
<br />86.03
<br />amperes at 208 V 3 PHASE
<br />238.80 amps
<br />amps
<br />* EST IMATED LOAD B ASED ON NEC
<br />3 500
<br />MCM N, #�
<br />4
<br />1/2° C.
<br />cc
<br />vv 6 ' -0 " v
<br />MI IN, I
<br />ONE-LINE
<br />NO SCALE
<br />v
<br />0 ONE -LINE DIAGRAM NOTES
<br />1) METER PER UTILITY COMPANY REQUIREMENTS.
<br />2) 120/208V., 3 PHASE LIGHTNING ARRESTOR.
<br />\AN 3) FURNISH AND INSTALL WIRE WAY CAPABLE OF ACCEPTING
<br />ADDITIONAL TWO METERS AND PANELS FOR POSSIBLE
<br />FUTURE TENANTS.
<br />') (3) #4/0, #4/0 N., #2 G.C., 2 -112" C.
<br />5) GROUNDING ELECTRODE SYSTEM: (2) 5/8 "x10' COPPER
<br />CLAD GROUND RODS, BUILDING STEEL, AND METAL COLD
<br />WATER PIPE.
<br />6) TIME CLOCK IN NEMA 3R ENCLOSURE. SEE DETAIL ON
<br />SHEET E -2 FOR MORE INFORMATION,
<br />7) 120V, PHOTOCELL. MOUNT FACING NORTH AND AS HIGH AS
<br />POSSIBLE ON BUILDING.
<br />A
<br />13
<br />Architec n
<br />ctu e 0 e. Inc.
<br />1526 Junior Court
<br />Lehigh, Florida 33971
<br />Phone: 239.693.8687
<br />Fax: 239.690.0795
<br />E -mail: architectureone @iline.com
<br />License no: AA 0003632
<br />Consultant:
<br />F
<br />Project:
<br />Proposed Building for
<br />K &KGlass
<br />Zepherhills, Florida
<br />Client
<br />Apco Building Systems, Inc.
<br />106 Whitaker Road
<br />Lutz, Florida
<br />C
<br />JUL 2 9 1003
<br />rain 6. Curb^ m n N0. moo
<br />Project Number: 0220
<br />Copyright 2002 © Architecture One, Inc. reserves copyright and other rights restricting
<br />these documents to the original site or purpose for which they were prepared.
<br />Reproductions, changes or assignments are prohibitted.
<br />Sheet Title:
<br />Specifications
<br />One Line and
<br />Legend
<br />Sheet
<br />Eml