Laserfiche WebLink
' Comment #4: The egress through the break room is ok provided the tables and chairs <br /> remain to the side wall adjacent to the egress door not causing an <br /> obstruction. <br /> Response: Please see revised sheet LS-1. <br /> Comment #5: Exit and emergency lighting may have to be redesigned due to the exit sign being <br /> removed from the private office. <br /> Response: Please see revised sheet LS-1. <br /> Comment #6: The storage room for med gas requires a fire resistant rating of 1 hour along <br /> with the fire sprinkler system because it is a high hazard room. Ventilation <br /> would have to be through the outside wall. The door shall be a 1 hour rated door <br /> and it shall also be placarded. Due to the lugh hazard, ensure the ventilation and <br /> electric in that room is explosion proo£ NFPA 101, Sections 8.7.1.1 and 6.2.2. <br /> Response: Please see revised sheet A-2. <br /> Comment #7: The mechanical room is considered a special hazard — a hazard greater than the <br /> occupancy is. It also appears to be acting as a room plenum. This room shall be <br /> smoke tight. Ventilation shall be accomplished through some other avenue (i.e. <br /> smoke dampers). NFPA 101, Section 8.7.1.2. <br /> Response: Please see revised sheet A-2. <br /> Comment #8: Upon completion of the build-out, the occupant shall provide a key for the Knox <br /> Box on the front of the building. <br /> Response: Please see revised sheet A-2. <br /> Comment #9: Ensure the address of the occupancy is located on the rear door and electrical <br /> meter and panels m the rear. <br /> Response: Please see revised sheets A-2 and E-1. <br /> BUILDING <br /> Comment #1: Installation of electnc shall comply with all applicable sections of Article 17 of <br /> N.E.C. special attention to section N. <br /> Response: Please see revised sheet E-1. <br /> Comment #2: 2007 F.B.C. Plumbing-section422 healthcare fixtures and equipment is <br /> applicable. <br />