Laserfiche WebLink
Zone Sizing Summary for UNIT B1 <br /> Project Name 29122-Meetinghouse @ Zephirhills 12/10/2009 <br /> Prepared by SGM Engineering 10 OSAM <br /> Air System Information <br /> Air System Name UNIT 61 Number of zones � <br /> Equipment Class SPLT AHU Floor Area 900.0 ftz <br /> Air System Type S2CAV Location Tampa, Fiorida <br /> Sizing Calculation Information <br /> Zone and Space Sizing Method: <br /> Zone CFM _. Sum of space airflow rates Calculation Months Jan to Dec <br /> Space CFM Individual peak space loads Sizing Data _ Calculated <br /> Zone Sizing Data <br /> Maximum Design Minimum Time Maximum Zone <br /> Cooling Air Air of Heating Floor <br /> Sensible Flow Flow Peak Load Area Zone <br /> Zone Name �gH <br /> Zone 1 � 1 (CFM} (CFM) Load (MBH) (ftZ) CFM/ft' <br /> 13.2 717 717 Ju11600 7.2 900.0 0.86 <br /> Zone Terminal Sizing Data <br /> No Zone Termina: S;zing Data required for this sysiem. <br /> Space Loads and Airftows <br /> Cooling Time Air Heatirtg Floor <br /> Zone Name ! Sensible of Flow Load Area Space <br /> Space Name Mutt. (MBH) Load (CFM) (MBH) (ft') CFM/ft= <br /> Zone 1 - <br /> UNIT 61 1 13.2 Jul 1600 717 7.2 900.0 0.80 <br /> Hourly Analysis Program v 4.4 <br /> Page 1 of 1 <br />