Laserfiche WebLink
Building Analysis .1ob: 1501 - � <br /> wri htsoft Date: 4119/2010 <br /> ' 9 Entire House B Y' � <br /> ' � • • <br /> For: LENNAR HOMES <br /> � - • • • • <br /> Location: Indoor: Heating Cooling <br /> Tampa Intl AP, FL, US Indoor temperature (°F) 70 75 <br /> Elevation: 10 ft Design TD (°F) 30 17 <br /> Latitude: 28°N Relafve humidity (%) 30 50 <br /> Outdoor: Heating Cooling Moisture difference (gr/Ib) 3.6 51.6 <br /> Dry bulb (°F) 40 92 Infiltration: <br /> Daily range (°F) - 15 ( L ) Method Simplified <br /> Wet bulb (°F) - 77 Construction quality Average <br /> Wind speed (mph) 15.0 7.5 Fireplaces 0 <br /> • <br /> Component Btuh/ftz Btuh % of load <br /> Walls 3.9 4586 23.3 °oCs <br /> Glazing 18.0 3744 19.0 wa"S <br /> Doors 11.7 445 2.3 Infiltratlon <br /> Ceilings 1.0 1456 7.4 <br /> Floors 2.9 4451 22.6 - <br /> Infiltration 2.7 2979 15.1 <br /> Ducts 2062 10.5 <br /> Piping . p Q Glazin9 F��� <br /> Humidification 0 0 <br /> Ventilation 0 0 °o°c ;,;� <br /> Adjustments 0 <br /> Total 19723 100.0 <br /> •• . <br /> Com onent Btuh/ft Btuh % of load <br /> WallS 2.6 3043 15.1 wa��s �nterna� Gains <br /> Glazing 37.2 7729 38.3 <br /> Doors 12.2 465 2.3 <br /> Ceilings 1.8 2665 13.2 p„� <br /> Floors 0 0 0 <br /> Infiltration 0.8 909 4.5 <br /> Ducts 2826 14 0 <br /> Ventilation 0 0 _Infiltration <br /> Internal gains 2520 12.5 <br /> Blower Q Q Glazing <br /> Ad1'ustments 0 Ceilings <br /> Total 20157 100.0 000rs <br /> Latent Cooling Load = 2933 Btuh <br /> Overall U-value = 0.110 Btuh/ft <br /> Data entries checked. <br /> �+�+- wrigtitsoft- Right-Suite� Universal 7 1 19 RSU05714 2011-Feb-Ot 12:27:08 <br /> ACCA VAC Estimating\LOADS\LENNAR NEW 08WAAA 2010 LOADS\1501 TN.rup Calc = MJ8 Orientation = NW Page 1 <br />