Laserfiche WebLink
( NOTA FI E R� ' � � - • <br /> by Honsywell <br /> NFW-50 Fire Alarm Control Panel <br /> Protected Premises: TJ MAXX - ZEPHYRHILLS Date: 4/8/2011 <br /> Address: 7326 GALL BLVD. <br /> City: ZEPHYRHILLS State: FLORIDA Zip: 33541 <br /> Prepared By: LIFE SAFETY DESIGNS, INC Phone: 904-388-1700 <br /> Address: 3038 LENOX AVENUE Email: <br /> City: JACKSONVILLE State: FLORIDA Zip: 32254 <br /> AC Branch Current Requirements 3.00 AMPS @ 120 VAC <br /> Current required by source to power the fire <br /> alarm system. <br /> Primary Standby Load 0.12 Amps <br /> Current load on the primary power supply during <br /> non-alarm conditions. <br /> Primary Alarm Load 1.08 Amps <br /> Current load on the primary power supply during <br /> alarm conditions. <br /> Secondary Load Requirements 3.70 Amp Hours <br /> Total Secondary Load from the calculation table below. <br /> � � � , <br /> Secondary Standby Load X Re uired Standb Time <br /> 0.125 A 24 hours 2.99 <br /> Secondary Alarm Load Re uired Alarm Time hours <br /> 1.082 A X 5 Minutes <br /> 0.084 hours 0.09 <br /> Auxiliary Power Supply Load X Re uired Alarm Time hours <br /> 0.000 A 0.084 hours 0.00 <br /> Total Secondary Load 3.08 <br /> Derating factor x 1.2 <br /> Secondary Load Requirements 3.70 AH <br /> Battery Selection �� Amp Hours <br /> Select batteries from the list below. <br /> 7.0 AH BAT-1270 Batte 12 volt <br /> � Two C Four (iwo 12VDC sets in parallel) <br /> P. 2 2 <br />