Laserfiche WebLink
Zephyrhills Fire F2escue <br /> (�907 Dairy Ilo�td, Lephyrhills. I 335�? <br /> i'ire Marshal 13uti ($13) 78()-0041 <br /> Kerry l�arnetl Fax (�31 �) 780-OU44 <br /> L;-mail; kbarnett(�i %tire.r_.ephyrhills.Fl.us <br /> Plan Review #: I 1-041 <br /> Project: Interior Renovation <br /> Number of Pages: 33 <br /> April 22, 2011 <br /> I have received and reviewed the plans for the renovation located at 38051 Market Square Dr and <br /> will allow this project to move forward. By paying for permit, contractor acknowledges to <br /> comply with the comments below. Should anyone have any questions, please do not hesitate to <br /> contact the Fire Marshal's office. <br /> l. Ensure fire safety practices are adhered to during renovation in accordance to <br /> NFPA 1. <br /> 2. If either the fire alarm or fire sprinkler system is to be out of service for tnore <br /> than 4 hours, this authority shall be notified. <br /> 3. The modification to the fire alarm and fire sprinkler system will require a separate <br /> set of plans, cut sheets, details, etc... from those individual contractors to obtain a <br /> permit to complete the work. <br /> 4. The fire sprinkler FDC will be changed out to a 5" 30 degree turndown Storz. <br /> 5. As information only, there is no page PS on cover page of plans. <br /> 6. Room 110 (electric) shall have a 1 hour rating and l hr door. (NFPA 101, <br /> 38.3.2.1 & 8.7). The door to this room shall have a sign on it "NO STORAGE — <br /> ELECTRTC ROOM" <br /> 7. Install emergency lights in restrooms. <br /> 8. Ensure Address is located on front and rear of building. <br /> 9. Ensure electric meters and panels located outside for this space are addressed <br /> accordingly. <br /> 10. Instali a knox box on the front of the building, if not already there Box shall be <br /> located by main door at a height of 6 feet. An application can be obtained from <br /> this authority. Ifa knox box is present, a key shall be given to this authority to <br /> place in that box. <br /> 1 l. Ensure duct detectors are installed on AHU's and tied into the FA system. <br />