Laserfiche WebLink
Zephyrhills Fire Rescue <br /> (907 Dairy Roaci, Lephyrhilis, I'L �35�2 <br /> I'ier- N1arshal L3us (8l3) 7�i0-0041 <br /> Kerry 13arnett f�t�x (81 ;) 780-OU��I <br /> Gmail: kbarnett(��).fire.�ephyrhills.fl.us <br /> Plan Review #: 11-102 � �� � ���� �� ~� ��� �� <br /> Project: Fire Alarm <br /> Number of Pages: 1 plus calcs and cut sheets <br /> August 10, 201 1 <br /> I have received and reviewed the plans for the installation of the fire alarm system located at 5320 <br /> 1 S` Street and will allow the project to move forward. Paying for permit contractor acknowledges <br /> complying with the items listed below. Should anyone have any questions, please do not hesitate <br /> to contact the Fire Marshal's office. <br /> 1. There were no devices shown in the sanctuary portion of the building. Ensure <br /> the panel is large enough to support adding devices to this area. A system may <br /> be required in that location after the next annual inspection based on occupant <br /> load. <br /> 2. Strobes shall remain on when system is silenced. <br /> 3. Install a knox box at the main doors. Application may be obtained from the <br /> station at the address above. <br /> 4. Ensure all devices are labeled according to the addresses on the panel. <br /> 5. Label telephone jacks. <br /> 6. Date the batteries. <br /> 7. Install breaker lock on breaker to panel. <br /> 8. Labe) location of breaker on FA panel. <br /> 9. Provide a zone map and log book at the panel. <br /> Inspection Required: <br /> 1. Acceptance Test <br /> � <br /> � <br /> v' .•� �" <br /> KERRY ARNETT, FIRE MARSHAL <br /> ***Please be advised this review of plans submitted is a cursory review to assist the contractor in <br /> compliance with applicable fire safety codes. This review is not intended to be a final approval of the <br /> submitted plans. It is tlie contractor's sole responsibility to ensure that the plans are in complete compliance <br /> with all applicable NFPA codes and local ordinances. ln the event that further examination or site <br /> inspection reveals areas of non-compliance, it shall be the contractor's sole responsibility, at their sole <br /> expeiise to bring those areas in compliance. The City assumes no responsibility for the contractor's failure <br /> to be in compliance with all applicable NFPA codes and local ordinances. <br />