GENERAL NOTES
<br />A. EXISTING CONDITIONS SHOWN ON THE DRAWINGS ARE BASED ON A LIMITED AMOUNT OF INFORMATION
<br />AVAILABLE TO THE ENGINEER, ALL SUCH CONDITIONS SHALL BE VERIFIED BY THE CONTRACTOR PRIOR TO
<br />SUBMITTING THE BID AND ADJUSTED IF NECESSARY. NO ADDITIONAL COMPENSATION SHALL BE GRANTED
<br />AFTER AWARDING A BID FOR ANY EQUIPMENT, MATERIAL OR LABOR REQUIRED TO REWORK OR
<br />OTHERWISE MODIFY EXISTING CONDITIONS.
<br />B. ENTIRE ELECTRICAL INSTALLATION SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE
<br />NATIONAL ELECTRICAL CODE, THE LATEST EDITION OF THE APPLICABLE STATE BUILDING CODE AND ANY
<br />OTHER STATE OR LOCAL AUTHORITY HAVING JURISDICTION.
<br />C. THE ELECTRICAL CONTRACTOR SHALL OBTAIN ALL PERMITS AND PAY SUCH FEES AS MAY BE NECESSARY
<br />FOR INSPECTIONS, TESTS AND OTHER SERVICES NECESSARY FOR THE COMPLETION OF HIS WORK.
<br />D. ALL WORK SHALL BE DONE AT SUCH TIMES AND IN SUCH A MANNER AS WILL LEAST INTERFERE WITH THE
<br />MAINTENANCE AND OPERATION OF ALL RELATED OR AFFECTED SYSTEMS. ALL POWER OUTAGES SHALL BE
<br />COORDINATED WITH THE OWNER.
<br />E THE CONTRACTOR SHALL GUARANTEE ALL HIS WORK AND MATERIALS FOR A PERIOD OF ONE YEAR AFTER
<br />ACCEPTANCE BY OWNER,
<br />F. ALL WIRING SHALL BE IN EMT OR FLEXIBLE METALLIC CONDUIT; EMT FITTINGS SHALL BE STEEL. POT METAL
<br />OR DIE CAST TYPE SHALL NOT BE USED. CONNECTORS SHALL HAVE NYLON- INSULATED THROATS,
<br />FITTINGS SHALL BE SET -SCREW TYPE.
<br />G. CONDUITS LEAVING OR ENTERING BUILDING SHALL BE SEALED PER NEC TO PREVENT ENTRANCE OF
<br />MOISTURE.
<br />H. ALL EQUIPMENT SHALL BE NEW AND BEAR THE U.L. LABEL, AND SHALL BE U.L. LISTED AND APPROVED FOR
<br />ITS INSTALLED APPLICATION
<br />I. ALL WIRING SHALL BE RUN IN CONDUIT. CONDUIT RUN UNDERGROUND OR BELOW SLAB SHALL BE PVC
<br />SCHEDULE 40 (1" MINIMUM). INTERIOR CONDUIT SHALL BE EMT (1/2" MINIMUM). EXPOSED EXTERIOR
<br />CONDUIT SHALL BE IMC OR RMC. ALL CONDUIT SHALL BE CONCEALED IN WALLS, CE;LINGS OR
<br />UNDERGROUND UNLESS EXPRESS WRITTEN CONSENT IS RECEIVED FROM THE OWNER.
<br />J. ALL CONDUITS SHALL HAVE A SEPARATE GREEN GROUND CONDUCTOR FOR GROUNDING.
<br />K. ALL CONDUCTORS SHALL BE COPPER WITH TYPE THHN /THWN INSULATION, RATED FOR 600V.
<br />L. WHERE CROSSING DRIVES WITH NEW CIRCUITS, BASE BID SHALL BE PRICED FOR CUTTING AND PATCHING
<br />EXISTING DRIVES AND SIDEWALKS, PROVIDE ALTERNATE PRICING WITH BID FOR DIRECTIONAL BORING,
<br />VERSUS CUT AND PATCH.
<br />M. CONTRACTOR SHALL OBSERVE EXTERIOR LIGHTING AT NIGHT AND NOTIFY OWNER OF SEVERELY
<br />DAMAGED OR INOPERABLE LIGHTS NOT NOTED ON PLANS TO DETERMINE WHETHER REPAIRS SHALL BE
<br />MADE.
<br />N. LAMPS SHALL BE INCLUDED FOR ALL NEW LIGHTING FIXTURES.
<br />r
<br />--j
<br />DESIGN CRITERIA:
<br />CODES: 2006 INTERNATIONAL
<br />BUILDING CODE ASCE 7 -05
<br />BASIC WIND SPEED: 110 MPH
<br />IMPORTANCE FACTOR: .87
<br />WIND EXPOSURE: C
<br />ASSUMED SOIL CLASSIFICATION
<br />(IBC TABLE 1804.2): CLAY,
<br />SANDY CLAY, SILTY CLAY,
<br />CLAYEY SILT, SILT AND
<br />SANDY SILT (CL, ML, I CH)
<br />' IF DIFFERENT SOIL MATERIAL IS
<br />ENCOUNTERED,CONTRACTOR
<br />SHALL CONTACT DESIGN ENGINEER.
<br />PROVIDE DIRECT WIRED SURGE
<br />SUPPRESSOR FOR A 30A, 240V, 1
<br />PHASE CIRCUIT LISTED BY AND
<br />MEETING THE REQUIREMENTS OF
<br />UL 1449, SECOND EDITION
<br />2 "X6" RECTANGULAR
<br />HANDHOLE WITH COVER
<br />2 "X6" CONDUIT ENTRY HOLE
<br />�1II II !I -1'I� i IIIsz�II T r=i
<br />E� I �Az 1 II! ; III I FI'r)
<br />III I � �I�I Ali ; -.-
<br />I—
<br />I�
<br />I I— �I - -I--
<br />I � I rly�
<br />III � � IL' I ICI,, Il�lr .•
<br />�� I I IC I I �El I I I = I I I
<br />— III
<br />R E I 1
<br />x71 III —III = b '
<br />�1=1 I I � I I�~
<br />Ii! 11111 II�III�� a
<br />y � lip — II I 1 =T 11 (
<br />III � I t
<br />UNDISTURBED EXISTING SOIL
<br />DIRECT - BURIAL CONCRETE POLE, BURIAL
<br />DEPTH SHALL BE A MINIMUM OF 6-6 ". CONFIRM
<br />ACTUAL BURIAL DEPTH WITH POLE
<br />MANUFACTURER
<br />LIGHT FIXTURE WITH SLIP - FITTER, COORDINATE
<br />MOUNTING WITH LUMINAIRE MANUFACTURER
<br />CONCRETE POLE WITH SMOOTH FINISH. POLE SHALL HAVE A
<br />MINIMUM EPA CAPACITY OF 4.0 AND SHALL WITHSTAND A
<br />WINDLOAD OF 110 MPH, ASCE 7 -02 EXPOSURE B, CATEGORY I
<br />DESIGN CRITERIA
<br />#2 BARE COPPER GROUND CONDUCTOR.
<br />CONNECT TO GROUND LUG INSIDE POLE
<br />ELECTRICAL SYMBOL LEGEND
<br />_
<br />PANELBOARD
<br />❑E - Xx�
<br />NEW SURFACE - MOUNTED HID CANOPY DOWNLIGHT. LETTER
<br />LAMP
<br />INDICATES TYPE.
<br />O
<br />NEW RECESSED - MOUNTED FLUORESCENT CANOPY DOWNLIGHT.
<br />p_
<br />LETTER INDICATES TYPE,
<br />F
<br />NEW POLE - MOUNTED HID AREA LIGHT. LETTER INDICATES TYPE.
<br />V
<br />-XX
<br />NEW WALL- MOUNTED HID OR FLUORESCENT AREA LIGHT.
<br />4 B
<br />LETTER INDICATES TYPE.
<br />—
<br />NEW UNDERGROUND CONDUIT
<br />WATTAGE
<br />NEW CONCEALED CONDUIT
<br />EXISTING PANELBOARD
<br />X
<br />MIN
<br />EXISTING RECESSED /SURFACE- MOUNTED HID /FLUORESCENT
<br />CANOPY DOWN LIGHT
<br />B
<br />EXISTING POLE - MOUNTED HID AREA LIGHT.
<br />EXISTING WALL - MOUNTED HID OR FLUORESCENT AREA LIGHT,
<br />1
<br />EXISTING RECESSED FLUORESCENT LIGHTING FIXTURE
<br />NOTE: OBJECTS THAT APPEAR SHADED ARE EXISTING TO REMAIN.
<br />PLAN NOTES
<br />P1 NEW LIGHT POLE, POLE BASE AND AREA LUMINAIRE(S) IN LANDSCAPE, REFER
<br />TO DETAIL 2/E1 FOR POLE INSTALLATION DETAILS.
<br />P2 WALL FIXTURE MOUNTING HEIGHT SHALL BE 11' -0" Al MOUNT FIXTURE
<br />BETWEEN SECOND AND THIRD DRIVING LANES. MOUNT FIXTURE JUST INSIDE
<br />OF DECORATIVE PLAQUE
<br />P3 RECESSED DOWNLIGHT SHALL BE MOUNTED 2' -0" IN FRONT OF, AND
<br />CENTERED WITH, BANK ATM UNIT.
<br />CIRCUITRY NOTES
<br />O FIXTURE(S) SHALL BE CIRCUITED TO A NEW 120 -VOLT, 20 -AMP, 1 -POLE
<br />CIRCUIT BREAKER IN PANEL A. ROUTE CIRCUIT THROUGH ANEW 20 -AMP,
<br />120 -VOLT LIGHTING CONTACTOR, EXTEND CONTROL TO NEW CONTACTOR
<br />FROM EXISTING TIMECLOCK AND /OR PHOTOCELL - CONTROLLED LIGHTING
<br />CONTACTOR. CONFIRM DUSK -TO -DAWN OPERATION, INSTALL NEW 2 #8 WIRE,
<br />1 #8 GROUND IN 1" SCHEDULE 40 PVC CONDUIT AS SHOWN ON SITE PLAN 1 /E1
<br />FOR NEW LIGHTING FIXTURE(S),
<br />O CIRCUIT TO EXISTING BUILDING - MOUNTED EXTERIOR LIGHTING CIRCUIT
<br />SERVING ADJACENT BUILDING - MOUNTED LIGHTING. FURNISH AND INSTALL
<br />NEW 2 #12 WIRE, 1 #12 GROUND IN 1/2" CONDUIT FOR NEW LIGHTING FIXTURE.
<br />FIELD MEASUREMENTS INDICATED THAT EXISTING CIRCUITRY HAS CAPACITY
<br />FOR ADDITIONAL LOAD. CONTRACTOR SHALL FIELD VERIFY CAPACITY BY
<br />OPERATING EXISTING LIGHTS AND MEASURING LOAD. NOTIFY PROJECT
<br />MANAGER IMMEDIATELY IF CAPACITY IS FOUND TO BE INSUFFICIENT.
<br />CONFIRM DUSK -TO -DAWN OPERATION.
<br />E-* ,>
<br />I
<br />I I,
<br />I
<br />J
<br />ALL WORK SHALL COMPLY W I TH I aI.
<br />PREVAILINrG CODES, FLORID: BU LI ING
<br />CODE, NATIONAL ELECTRIC C. DD 1 ,�� 1D
<br />CITY OF ZEPHYRHILS ORD]\ N( Fc
<br />- Al : ,, E
<br />B
<br />2 P2
<br />I
<br />i
<br />-. J>
<br />M
<br />I
<br />2 P3 �D
<br />�
<br />" �J I Ed I 1=1 1 Q I IIJII III
<br />FINISHED GRADE
<br />II_, 1
<br />7
<br />� J
<br />15� I l F�:j 1 1 l I
<br />N
<br />��
<br />SIT PLAN
<br />I 31 _ "
<br />dam, II ICI I � I,,_ E1 SCALE: 1 - 20-0
<br />L o n � �—J I r l II III —I I
<br />�111T �s 5/8 "X8' COPPER -CLAD STEEL GROUND
<br />,I y l
<br />+ tir I 1 1 =1 � I I= 3 I CI I � 11. ROD WITH FCI N0. YGLR29C58
<br />`I fir _I —1 COMPRESSION CONNECTOR,
<br />= II�III-
<br />�1� -11 EXOTHERMIC WELD
<br />4{ � E= 1
<br />PROVIDE
<br />PROVIDE 2' 0" DIAMETER HOLE.
<br />BACKFILL WITH 2O0OPS1 CONCRETE
<br />� POLE INSTALLATION DETAIL
<br />SCALE: NTS
<br />DraNing 'r JAXFILE01'Commeraal'P'.Wells Fargo \_Wells Fargo US 5015040657 Wells Fargo FL ATM & AHD Lighting,FL, 144900 - 144999, 144909_Zephyr':Dwgs 144909 Zeptyr dwg
<br />LIGHTING FIXTURE SCHEDULE
<br />TYPE
<br />FIXTURE DESCRIPTION
<br />CATi�l SERIES
<br />FIXTURE
<br />LAMP
<br />LAMP TYPE
<br />BALLAST TYPE
<br />MOUNTING
<br />FIXTURE
<br />REMARKS
<br />VOLTAGE
<br />NO.
<br />WATTAGE
<br />WALL - MOUNTED AREA LUMINAIRE, DARK BRONZE FINISH,
<br />LITHONW WST- 100M- FT- TB -LIPI
<br />B
<br />METAL HALIDE LAMPING WITH FORWARD THROW
<br />120
<br />1
<br />METAL HALIDE
<br />MAGNETIC
<br />SURFACE
<br />100
<br />DISTRIBUTION
<br />D
<br />RECESSED - MOUNTED OPEN DOWNLIGHT, CLEAR TRIM,
<br />GOTHAM: AFV- 26TRT- 6AR- MV /OLT -GSKT
<br />120
<br />COMPACT
<br />COORDINATE WITH EXISTING CANOPY. PROVIDE FLANGE KIT AS
<br />SEMI - SPECULAR REFLECTOR, DAMP LOCATION LISTED
<br />1
<br />FLUORESCENT
<br />ELECTRONIC
<br />RECESSED
<br />26
<br />NEEDED FOR A COMPLETE INSTALLATION
<br />POLE - MOUNTED AREA LUMINAIRE, DARK BRONZE FINISH,
<br />LITHONIA: KVF2- 1000M- SER3FL -TB- SCWA- RP- I2 -LPI
<br />NOMINAL FIXTURE HEIGHT SHALL BE 35-0" Al REFER TO POLE
<br />F
<br />METAL HALIDE LAMPING, SR3 DISTRIBUTION, FLAT GLASS
<br />208
<br />1
<br />METAL HALIDE
<br />SCWA
<br />POLE
<br />1000
<br />INSTALLATION DETAIL FOR FURTHER INFORMATION
<br />LENS, SQUARE TAPERED CONCRETE POLE
<br />NOTE: FIXTURE FINISH OF BUILDING - MOUNTED LIGHTING FIXTURES BASED UPON FIELD OBSERVATICNS OF SURROUNDING FIXTURES AND SHALL BE CONFIRMED PRIOR TO ORDERING EQUIPMENT. MATCH EXISTING NEARBY BUILDING - MOUNTED FIXTURES FOR FINISH, LIGHT POLE TYPE
<br />AND FINISH AND POLE - MOUNTED FIXTURE FINISH BASED UPON FIELD OBSERVATIONS OF EXISTING PJLE'S AND POLE - MOUNTED FIXTURES, AND SHOULD BE CONFIRMED PRIOR TO ORDERING EQUIPMENT, MATCH EXISTING POLES FOR FINISH AND TYPE, AND MATCH EXISTING
<br />POLE - MOUNTED FIXTURES FOR FINISH.
<br />I
<br />I I
<br />I
<br />I I I I
<br />ATM
<br />R48tffo
<br />IMPROVING YOUR WORLD
<br />Reynolds, Smith and Hills, Inc.
<br />10748 Deerwood Park Boulevard South
<br />Jacksonville, FI 32256 -0597
<br />Ph: (904) 256 -2500, Fax: (904) 256 -2502
<br />w,vw.rsandh.com
<br />FL Cert. Nos. AAC001886' IB26000956'
<br />E60005620' LCC000210 ` G3238
<br />ZEPHYR
<br />7780 Gall Blvd (US 301)
<br />Zephyrhills, FL
<br />33541
<br />BE NUMBER :144909
<br />ENVIRONMENT : 2
<br />SCENARIO : D
<br />DISRUPTION : NO
<br />DESCRIPTION:
<br />ADD'L COST NO
<br />DESCRIPTION:
<br />y
<br />=•. �j S fA C
<br />O F •. � ..
<br />a • 9
<br />2y p p • ,{J w .
<br />WELLS FARGO
<br />ATM & AHD
<br />LIGHTING COMPLIANCE
<br />PROGRAM
<br />REVISIONS
<br />DATE ISSUED: 08-08 -2011
<br />REVIEWED BY: MOS
<br />DRAWN BY: DRH
<br />DESIGNED BY: DRH
<br />AEP PROJECT NUMBER
<br />501 - 6040 -657
<br />j 2011 REYNOLDS, SMITH AND HILLS INC.
<br />SHEET TITLE
<br />PARTIAL
<br />ELECTRICAL
<br />PLAN
<br />SHEET NUMBER
<br />E1
<br />Plotted on August 15, 2011 Plotted by Price, Adam