GENERAL NOTES <br />A. EXISTING CONDITIONS SHOWN ON THE DRAWINGS ARE BASED ON A LIMITED AMOUNT OF INFORMATION <br />AVAILABLE TO THE ENGINEER, ALL SUCH CONDITIONS SHALL BE VERIFIED BY THE CONTRACTOR PRIOR TO <br />SUBMITTING THE BID AND ADJUSTED IF NECESSARY. NO ADDITIONAL COMPENSATION SHALL BE GRANTED <br />AFTER AWARDING A BID FOR ANY EQUIPMENT, MATERIAL OR LABOR REQUIRED TO REWORK OR <br />OTHERWISE MODIFY EXISTING CONDITIONS. <br />B. ENTIRE ELECTRICAL INSTALLATION SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE <br />NATIONAL ELECTRICAL CODE, THE LATEST EDITION OF THE APPLICABLE STATE BUILDING CODE AND ANY <br />OTHER STATE OR LOCAL AUTHORITY HAVING JURISDICTION. <br />C. THE ELECTRICAL CONTRACTOR SHALL OBTAIN ALL PERMITS AND PAY SUCH FEES AS MAY BE NECESSARY <br />FOR INSPECTIONS, TESTS AND OTHER SERVICES NECESSARY FOR THE COMPLETION OF HIS WORK. <br />D. ALL WORK SHALL BE DONE AT SUCH TIMES AND IN SUCH A MANNER AS WILL LEAST INTERFERE WITH THE <br />MAINTENANCE AND OPERATION OF ALL RELATED OR AFFECTED SYSTEMS. ALL POWER OUTAGES SHALL BE <br />COORDINATED WITH THE OWNER. <br />E THE CONTRACTOR SHALL GUARANTEE ALL HIS WORK AND MATERIALS FOR A PERIOD OF ONE YEAR AFTER <br />ACCEPTANCE BY OWNER, <br />F. ALL WIRING SHALL BE IN EMT OR FLEXIBLE METALLIC CONDUIT; EMT FITTINGS SHALL BE STEEL. POT METAL <br />OR DIE CAST TYPE SHALL NOT BE USED. CONNECTORS SHALL HAVE NYLON- INSULATED THROATS, <br />FITTINGS SHALL BE SET -SCREW TYPE. <br />G. CONDUITS LEAVING OR ENTERING BUILDING SHALL BE SEALED PER NEC TO PREVENT ENTRANCE OF <br />MOISTURE. <br />H. ALL EQUIPMENT SHALL BE NEW AND BEAR THE U.L. LABEL, AND SHALL BE U.L. LISTED AND APPROVED FOR <br />ITS INSTALLED APPLICATION <br />I. ALL WIRING SHALL BE RUN IN CONDUIT. CONDUIT RUN UNDERGROUND OR BELOW SLAB SHALL BE PVC <br />SCHEDULE 40 (1" MINIMUM). INTERIOR CONDUIT SHALL BE EMT (1/2" MINIMUM). EXPOSED EXTERIOR <br />CONDUIT SHALL BE IMC OR RMC. ALL CONDUIT SHALL BE CONCEALED IN WALLS, CE;LINGS OR <br />UNDERGROUND UNLESS EXPRESS WRITTEN CONSENT IS RECEIVED FROM THE OWNER. <br />J. ALL CONDUITS SHALL HAVE A SEPARATE GREEN GROUND CONDUCTOR FOR GROUNDING. <br />K. ALL CONDUCTORS SHALL BE COPPER WITH TYPE THHN /THWN INSULATION, RATED FOR 600V. <br />L. WHERE CROSSING DRIVES WITH NEW CIRCUITS, BASE BID SHALL BE PRICED FOR CUTTING AND PATCHING <br />EXISTING DRIVES AND SIDEWALKS, PROVIDE ALTERNATE PRICING WITH BID FOR DIRECTIONAL BORING, <br />VERSUS CUT AND PATCH. <br />M. CONTRACTOR SHALL OBSERVE EXTERIOR LIGHTING AT NIGHT AND NOTIFY OWNER OF SEVERELY <br />DAMAGED OR INOPERABLE LIGHTS NOT NOTED ON PLANS TO DETERMINE WHETHER REPAIRS SHALL BE <br />MADE. <br />N. LAMPS SHALL BE INCLUDED FOR ALL NEW LIGHTING FIXTURES. <br />r <br />--j <br />DESIGN CRITERIA: <br />CODES: 2006 INTERNATIONAL <br />BUILDING CODE ASCE 7 -05 <br />BASIC WIND SPEED: 110 MPH <br />IMPORTANCE FACTOR: .87 <br />WIND EXPOSURE: C <br />ASSUMED SOIL CLASSIFICATION <br />(IBC TABLE 1804.2): CLAY, <br />SANDY CLAY, SILTY CLAY, <br />CLAYEY SILT, SILT AND <br />SANDY SILT (CL, ML, I CH) <br />' IF DIFFERENT SOIL MATERIAL IS <br />ENCOUNTERED,CONTRACTOR <br />SHALL CONTACT DESIGN ENGINEER. <br />PROVIDE DIRECT WIRED SURGE <br />SUPPRESSOR FOR A 30A, 240V, 1 <br />PHASE CIRCUIT LISTED BY AND <br />MEETING THE REQUIREMENTS OF <br />UL 1449, SECOND EDITION <br />2 "X6" RECTANGULAR <br />HANDHOLE WITH COVER <br />2 "X6" CONDUIT ENTRY HOLE <br />�1II II !I -1'I� i IIIsz�II T r=i <br />E� I �Az 1 II! ; III I FI'r) <br />III I � �I�I Ali ; -.- <br />I— <br />I� <br />I I— �I - -I-- <br />I � I rly� <br />III � � IL' I ICI,, Il�lr .• <br />�� I I IC I I �El I I I = I I I <br />— III <br />R E I 1 <br />x71 III —III = b ' <br />�1=1 I I � I I�~ <br />Ii! 11111 II�III�� a <br />y � lip — II I 1 =T 11 ( <br />III � I t <br />UNDISTURBED EXISTING SOIL <br />DIRECT - BURIAL CONCRETE POLE, BURIAL <br />DEPTH SHALL BE A MINIMUM OF 6-6 ". CONFIRM <br />ACTUAL BURIAL DEPTH WITH POLE <br />MANUFACTURER <br />LIGHT FIXTURE WITH SLIP - FITTER, COORDINATE <br />MOUNTING WITH LUMINAIRE MANUFACTURER <br />CONCRETE POLE WITH SMOOTH FINISH. POLE SHALL HAVE A <br />MINIMUM EPA CAPACITY OF 4.0 AND SHALL WITHSTAND A <br />WINDLOAD OF 110 MPH, ASCE 7 -02 EXPOSURE B, CATEGORY I <br />DESIGN CRITERIA <br />#2 BARE COPPER GROUND CONDUCTOR. <br />CONNECT TO GROUND LUG INSIDE POLE <br />ELECTRICAL SYMBOL LEGEND <br />_ <br />PANELBOARD <br />❑E - X­x� <br />NEW SURFACE - MOUNTED HID CANOPY DOWNLIGHT. LETTER <br />LAMP <br />INDICATES TYPE. <br />O <br />NEW RECESSED - MOUNTED FLUORESCENT CANOPY DOWNLIGHT. <br />p_ <br />LETTER INDICATES TYPE, <br />F <br />NEW POLE - MOUNTED HID AREA LIGHT. LETTER INDICATES TYPE. <br />V <br />-XX <br />NEW WALL- MOUNTED HID OR FLUORESCENT AREA LIGHT. <br />4 B <br />LETTER INDICATES TYPE. <br />— <br />NEW UNDERGROUND CONDUIT <br />WATTAGE <br />NEW CONCEALED CONDUIT <br />EXISTING PANELBOARD <br />X <br />MIN <br />EXISTING RECESSED /SURFACE- MOUNTED HID /FLUORESCENT <br />CANOPY DOWN LIGHT <br />B <br />EXISTING POLE - MOUNTED HID AREA LIGHT. <br />EXISTING WALL - MOUNTED HID OR FLUORESCENT AREA LIGHT, <br />1 <br />EXISTING RECESSED FLUORESCENT LIGHTING FIXTURE <br />NOTE: OBJECTS THAT APPEAR SHADED ARE EXISTING TO REMAIN. <br />PLAN NOTES <br />P1 NEW LIGHT POLE, POLE BASE AND AREA LUMINAIRE(S) IN LANDSCAPE, REFER <br />TO DETAIL 2/E1 FOR POLE INSTALLATION DETAILS. <br />P2 WALL FIXTURE MOUNTING HEIGHT SHALL BE 11' -0" Al MOUNT FIXTURE <br />BETWEEN SECOND AND THIRD DRIVING LANES. MOUNT FIXTURE JUST INSIDE <br />OF DECORATIVE PLAQUE <br />P3 RECESSED DOWNLIGHT SHALL BE MOUNTED 2' -0" IN FRONT OF, AND <br />CENTERED WITH, BANK ATM UNIT. <br />CIRCUITRY NOTES <br />O FIXTURE(S) SHALL BE CIRCUITED TO A NEW 120 -VOLT, 20 -AMP, 1 -POLE <br />CIRCUIT BREAKER IN PANEL A. ROUTE CIRCUIT THROUGH ANEW 20 -AMP, <br />120 -VOLT LIGHTING CONTACTOR, EXTEND CONTROL TO NEW CONTACTOR <br />FROM EXISTING TIMECLOCK AND /OR PHOTOCELL - CONTROLLED LIGHTING <br />CONTACTOR. CONFIRM DUSK -TO -DAWN OPERATION, INSTALL NEW 2 #8 WIRE, <br />1 #8 GROUND IN 1" SCHEDULE 40 PVC CONDUIT AS SHOWN ON SITE PLAN 1 /E1 <br />FOR NEW LIGHTING FIXTURE(S), <br />O CIRCUIT TO EXISTING BUILDING - MOUNTED EXTERIOR LIGHTING CIRCUIT <br />SERVING ADJACENT BUILDING - MOUNTED LIGHTING. FURNISH AND INSTALL <br />NEW 2 #12 WIRE, 1 #12 GROUND IN 1/2" CONDUIT FOR NEW LIGHTING FIXTURE. <br />FIELD MEASUREMENTS INDICATED THAT EXISTING CIRCUITRY HAS CAPACITY <br />FOR ADDITIONAL LOAD. CONTRACTOR SHALL FIELD VERIFY CAPACITY BY <br />OPERATING EXISTING LIGHTS AND MEASURING LOAD. NOTIFY PROJECT <br />MANAGER IMMEDIATELY IF CAPACITY IS FOUND TO BE INSUFFICIENT. <br />CONFIRM DUSK -TO -DAWN OPERATION. <br />E-* ,> <br />I <br />I I, <br />I <br />J <br />ALL WORK SHALL COMPLY W I TH I aI. <br />PREVAILINrG CODES, FLORID: BU LI ING <br />CODE, NATIONAL ELECTRIC C. DD 1 ,�� 1D <br />CITY OF ZEPHYRHILS ORD]\ N( Fc <br />- Al : ,, E <br />B <br />2 P2 <br />I <br />i <br />-. J> <br />M <br />I <br />2 P3 �D <br />� <br />" �J I Ed I 1=1 1 Q I IIJII III <br />FINISHED GRADE <br />II_, 1 <br />7 <br />� J <br />15� I l F�:j 1 1 l I <br />N <br />�� <br />SIT PLAN <br />I 31 _ " <br />dam, II ICI I � I,,_ E1 SCALE: 1 - 20-0 <br />L o n � �—J I r l II III —I I <br />�111T �s 5/8 "X8' COPPER -CLAD STEEL GROUND <br />,I y l <br />+ tir I 1 1 =1 � I I= 3 I CI I � 11. ROD WITH FCI N0. YGLR29C58 <br />`I fir _I —1 COMPRESSION CONNECTOR, <br />= II�III- <br />�1� -11 EXOTHERMIC WELD <br />4{ � E= 1 <br />PROVIDE <br />PROVIDE 2' 0" DIAMETER HOLE. <br />BACKFILL WITH 2O0OPS1 CONCRETE <br />� POLE INSTALLATION DETAIL <br />SCALE: NTS <br />DraNing 'r JAXFILE01'Commeraal'P'.Wells Fargo \_Wells Fargo US 5015040657 Wells Fargo FL ATM & AHD Lighting,FL, 144900 - 144999, 144909_Zephyr':Dwgs 144909 Zeptyr dwg <br />LIGHTING FIXTURE SCHEDULE <br />TYPE <br />FIXTURE DESCRIPTION <br />CATi�l SERIES <br />FIXTURE <br />LAMP <br />LAMP TYPE <br />BALLAST TYPE <br />MOUNTING <br />FIXTURE <br />REMARKS <br />VOLTAGE <br />NO. <br />WATTAGE <br />WALL - MOUNTED AREA LUMINAIRE, DARK BRONZE FINISH, <br />LITHONW WST- 100M- FT- TB -LIPI <br />B <br />METAL HALIDE LAMPING WITH FORWARD THROW <br />120 <br />1 <br />METAL HALIDE <br />MAGNETIC <br />SURFACE <br />100 <br />DISTRIBUTION <br />D <br />RECESSED - MOUNTED OPEN DOWNLIGHT, CLEAR TRIM, <br />GOTHAM: AFV- 26TRT- 6AR- MV /OLT -GSKT <br />120 <br />COMPACT <br />COORDINATE WITH EXISTING CANOPY. PROVIDE FLANGE KIT AS <br />SEMI - SPECULAR REFLECTOR, DAMP LOCATION LISTED <br />1 <br />FLUORESCENT <br />ELECTRONIC <br />RECESSED <br />26 <br />NEEDED FOR A COMPLETE INSTALLATION <br />POLE - MOUNTED AREA LUMINAIRE, DARK BRONZE FINISH, <br />LITHONIA: KVF2- 1000M- SER3FL -TB- SCWA- RP- I2 -LPI <br />NOMINAL FIXTURE HEIGHT SHALL BE 35-0" Al REFER TO POLE <br />F <br />METAL HALIDE LAMPING, SR3 DISTRIBUTION, FLAT GLASS <br />208 <br />1 <br />METAL HALIDE <br />SCWA <br />POLE <br />1000 <br />INSTALLATION DETAIL FOR FURTHER INFORMATION <br />LENS, SQUARE TAPERED CONCRETE POLE <br />NOTE: FIXTURE FINISH OF BUILDING - MOUNTED LIGHTING FIXTURES BASED UPON FIELD OBSERVATICNS OF SURROUNDING FIXTURES AND SHALL BE CONFIRMED PRIOR TO ORDERING EQUIPMENT. MATCH EXISTING NEARBY BUILDING - MOUNTED FIXTURES FOR FINISH, LIGHT POLE TYPE <br />AND FINISH AND POLE - MOUNTED FIXTURE FINISH BASED UPON FIELD OBSERVATIONS OF EXISTING PJLE'S AND POLE - MOUNTED FIXTURES, AND SHOULD BE CONFIRMED PRIOR TO ORDERING EQUIPMENT, MATCH EXISTING POLES FOR FINISH AND TYPE, AND MATCH EXISTING <br />POLE - MOUNTED FIXTURES FOR FINISH. <br />I <br />I I <br />I <br />I I I I <br />ATM <br />R48tffo <br />IMPROVING YOUR WORLD <br />Reynolds, Smith and Hills, Inc. <br />10748 Deerwood Park Boulevard South <br />Jacksonville, FI 32256 -0597 <br />Ph: (904) 256 -2500, Fax: (904) 256 -2502 <br />w,vw.rsandh.com <br />FL Cert. Nos. AAC001886' IB26000956' <br />E60005620' LCC000210 ` G3238 <br />ZEPHYR <br />7780 Gall Blvd (US 301) <br />Zephyrhills, FL <br />33541 <br />BE NUMBER :144909 <br />ENVIRONMENT : 2 <br />SCENARIO : D <br />DISRUPTION : NO <br />DESCRIPTION: <br />ADD'L COST NO <br />DESCRIPTION: <br />y <br />=•. �j S fA C <br />O F •. � .. <br />a • 9 <br />2y p p • ,{J w . <br />WELLS FARGO <br />ATM & AHD <br />LIGHTING COMPLIANCE <br />PROGRAM <br />REVISIONS <br />DATE ISSUED: 08-08 -2011 <br />REVIEWED BY: MOS <br />DRAWN BY: DRH <br />DESIGNED BY: DRH <br />AEP PROJECT NUMBER <br />501 - 6040 -657 <br />j 2011 REYNOLDS, SMITH AND HILLS INC. <br />SHEET TITLE <br />PARTIAL <br />ELECTRICAL <br />PLAN <br />SHEET NUMBER <br />E1 <br />Plotted on August 15, 2011 Plotted by Price, Adam <br />I I <br />i <br />