Laserfiche WebLink
Zephyrhilis Fire Rescue <br /> 6907 Uairy Road, Gephyrhills, 1'L i35�2 <br /> (� ire Marshal L3us (8 l 3) 78Q-0041 <br /> Kerr•y 13arnetl f�ax (813) 780-004� <br /> �:-mail: kbarnett cr>fire.Lephyrhills.fl.us <br /> Plan Review #: 11-149 <br /> Project: Fire Alarm Modification <br /> Number of Pages: Packet <br /> December 20, 2011 <br /> I have received and reviewed the plans for the fire alarm modification located at 38750 5`" <br /> Avenue (St Joseph Parrish Hall). At this time the project will be allowed to move forward. Paying <br /> for permit, the contractor agrees and will comply with the comments below. Should anyone have <br /> any questions, please do not hesitate to contact the Fire Marshal's office. <br /> l. Installation shall comply with the 2002 edition ofNFPA 72. <br /> 2. Ensure the restrooms have strobes. If not, strobes shall be installed. <br /> 3. Ensure location of fire alarm breaker is indicated on fire alarm panel. <br /> 4. Ensure there is a breaker lock on the fire alarm breaker. <br /> 5. Ensure the batteries are dated and telephone jacks are marked. <br /> 6. Ensure there is a zone map by the panel. <br /> Inspection(s) Required: <br /> 1. Acceptance Test <br /> KERRY BA ETT, FIRE MARSHAL <br /> ***Please be advised this review of plans submitted is a cursory review to assist the contractor in <br /> compliance with applicable fire safety codes. This review is not intended to be a final approval of the <br /> submitted plans. It is the contractor's sole responsibility to ensure that the plans are in complete compliance <br /> with all applicable NFPA codes and local ordinances. In the event that further examination or site <br /> inspection reveals areas of non-compliance, it shall be the contractor's sole responsibility, at their sole <br /> expense to bring those areas in compliance The City assumes no responsibility for the contractor's failure <br /> to be in compliance with all applicable NFPA codes and local ordinances. <br />