., ; <br /> SECTION IV - SYSTEM DESIGN <br /> UL EX3470 ULC EX3470 Page 4-4 <br /> REV.7 7-1-09 <br /> Transition Protection <br /> I <br /> Transitions are protected at a point in the transition where the The 1/2N nozzle(Part No.419334)must be centered 10 to 26 in. <br /> perimeter or the diameter is equal to or less than the maximum (25 to 66 cm)below the precipitator and aimed to discharge at the <br /> size duct that can be protected.The nozzle(s) must be located in center of each precipitator cell.However,it it is physically impossi- <br /> the center of the area at that point, or center of the module pro- ble to mount the noule at 10 to 26 in.(25 to 66 cm)due to pre- <br /> tected when more than one duct noule is required.Note:Nozzles cipitator placement,the noule may be mounted closer than 10 in. <br /> to protect ducts with a transition that Is more than 4 ft(1.2 m) (25 cm).See Figure 5. <br /> in height,will be required to be positioned in the opening of <br /> the transition from the hood 2 to 8 In.(5.1 to 20.3 cm)Into the <br /> opening using standard duct noule destgn parameters. See <br /> .Figure 4. <br /> DUCT SEE DUCT FOR <br /> NOZZLE � TRANSITION <br /> � OUCT PROTECTION <br /> '�. _L <br /> TRANSITION � <br /> ► <br /> ���' PRECIPITATOR <br /> �� � <br /> i� <br /> i � <br /> 4� 10•28 IN' <br /> (12 m) <br /> MAX. I (25-88 cm) <br /> � ( NOZZLE FOR ( <br /> PRECIPITATOR <br /> PROTECTION <br /> 'IF PHYSICALLY IMPOSSIBLE AT 10 TO 2B IN.(25 TO 68 cm),NOaLE MAY BE <br /> FIGURE 4 MOUNTED CLOSER THAN 10 IN.(25 cm). <br /> °0°"� FIGURE 5 <br /> Electrostatic Precipitator Protectlon 00°1B� <br /> ► Note:For protection of Pollution Control Units(PCUs)or air scrub- <br /> Some restaurant ventilating ducts have an electrostatic precipita- ►bers with or without ESPs, contact Ansul Technical Services for <br /> ►tor installed at or near the base.These precipitators are generaliy ►non-UL listed recommended application. <br /> ►small and are used to aid in the cleaning of exhaust air. <br /> Ducts with precipitators located at or near the base can be pro- <br /> tected using duct nozzle(s) above the precipitator and 1/2N noz- <br /> zle(s)(Part No.419334)for the precipitator.One 1/2N nozzle must <br /> be used for each cell being protected.This nozzle tip is stamped <br /> with 1/2N,indicating that it is a 1/2-flow nozzle and must be count- <br /> ed as 1/2 flow number. <br /> When protecting ducts equipped with precipitators,the duct noz- <br /> zle(s) must be installed above the precipitator and aimed to dis- <br /> charge downstream.If the area above the precipitator is a duct,the <br /> nozzle(s) must be positioned according to duct protection guide- <br /> lines.If the area above the precipitator is a transition,the transition <br /> guidelines must be followed. <br /> I <br />