(�J MOTI FI ERa ' • ' - • <br /> by Honeywell <br /> NFW2-100 Fire Alarm Control Panel <br /> Protected Premises: Orthopaedic Spine Institute(Formerly Twelve Oaks) Date 1l18/2012 <br /> Address: 6748 Gall Blvd. <br /> City: Zephyrhills State: FI. Zip� 33542 <br /> Prepared By: The Hartline Alarm Co, Inc.-Chuck Caudill Phone. (863)678-0678 <br /> Address. 401 N. SCeniC Hwy Email. chuck[a�hartlinealarm.com <br /> City� Lake Wales State FI. Zip: 33859 <br /> AC Branch Current Requirements 3.00 AMPS @ 120 VAC <br /> Current required by source to power the fire alarm <br /> system <br /> Primary Standby Load 0.37 Amps <br /> , Current load on the primary power supply during <br /> non-alarm conditions. <br /> Primary Alarm Load 5.33 Amps <br /> Current load on the primary power supply during <br /> alarm conditions. <br /> Secondary Load Requirements 8.75 Amp Hours <br /> Total Secondary Load from the calculation table below <br /> � . • � <br /> Seconday Standby Load Re uired Standb Time <br /> 0.285 A X 24 hours 6.85 <br /> Secondary Alarm Load Re uired Alarm Time(hours) <br /> 5.325 A X 0.084 hours 0 45 <br /> Auxiliary Power Supply Load Required Alarm Time hours) <br /> 0 000 A X 0.084 hours 0.00 <br /> Total Seconda Load 7.30 <br /> Derating factor x 1.2 <br /> Secondary Load Re uirements 8.75 AH <br /> Battery Selection 12 Amp Hours <br /> Select batteries from the list below. <br /> 12 AH BAT-12120 Batte 12 volt) <br /> r: Tv�o �" FoU'(two 12�/DC'9E�5 in per-dllel) <br /> Page 1 of 2 <br />