My WebLink
|
Help
|
About
|
Sign Out
Browse
Search
12-12736
Zephyrhills
>
Building Department
>
Permits
>
2012
>
12-12736
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
1/25/2013 1:19:24 PM
Creation date
1/25/2013 1:16:36 PM
Metadata
Fields
Template:
Building Department
Company Name
FLORIDA HOSPITAL OF ZEPHYRHILLS
Building Department - Doc Type
Permit
Permit #
12-12736
Building Department - Name
FLORIDA HOSPITAL ZEPHYRHILLS
Address
7050 GALL BLVD
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
33
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
� . . . . Duct Sensor Location Considerations: <br /> 1. Proper duct smoke detection location must ensure <br /> Exhaust Damper Sensor OK <br /> r � adequate airflow within the duct housing. <br /> Exhaust.- i �—Retum Air 2• Duct air velocity rating is 300 to 4000 ft/min(91 to <br /> 1220 m/min).Pressure differential between intake and <br /> Do not locate I exhaust tubes is required to be between 0.015 to 1.55 <br /> sensorhere � <br /> inches of water(0.381 to 39.37 mm). <br /> Return air <br /> damper i 3. To avoid air turbulence,a location of six duct widths <br /> ; downsh•eam from bends or inlets is desirable.Ensure <br /> � accessibility for test and service. <br /> � 4. Pro er Locations• downstream side of filters to detect <br /> Fresh air--► � � —►Suppty Air p <br /> � ' fires in the filters;in return ducts,ahead of mixing <br /> or ot io�te Filter bank Sensor OK areas;upstream of air humiditier and cooling coil. <br /> sensor here 5. Other locations and orientations may be required for <br /> Bend or other Top mount,if appropriate proper duct smoke detection depending on duct access, <br /> obstruction ��� system design,and duct airflow testing. Contact your <br /> Return� local Simplex product supplier for assistance. <br /> jair inlet <br /> � s o��� � � 6 o��t � Locations to Avoid: <br /> widths widths <br /> desirab�e-►i ;~desirable ij 1. Where dampers closed for cornfort control would <br /> Additional Information Refer to NFPA 90A,Standar•d for• interfere with airflow. <br /> the Installation ofAi�•Conditioning and Ventilating Systems; 2• Next to outside air inlets(unle;ss the intent is to monitor <br /> NFPA 72�,the National Fire Alarm Code;and the NE�IL4 smoke entry from that area) <br /> Guide for Proper Use of Smoke Detectors in Duct 3. In return air damper branch ducts and mixing areas <br /> Applications,and Installation Instructions 574-776 where airflow may be restrictE;d. <br /> . - _ . <br /> General Mechanical and Environmental <br /> Air Velocity Range(linear ft/min) 300 to 4000 ft/min(91 to 1220 m/min) <br /> Sensor Sensitivity Range 0.2%to 3.7%per foot of obscuration, selectable at host�control panel <br /> UL Listed Temperature Range 32° F to 100°F(0°C to 38°C) <br /> Operating Temperature Range 32°F to 122°F(0°C to 50°C) <br /> Storage Temperature Range 0° F to 140°F(-18°C to 60°C) <br /> Humidity Range 10%to 95%RH, non-condensing <br /> Wiring Connections Terminal blocks, 18 to 12 AWG(0 82 mmz to 3 31 mmZ) <br /> Housing Color Black base with clear cover <br /> Remote Status/Alarm LED and Test Station with Remote Status/Alarm LED <br /> Remote Alarm LED Current 1.2 mA, no impact to 24 VDC alarm current(2098-9808 ur 2098-9806) <br /> Test Station Keyswitch Current 3 3 mA, no impact to 24 VDC alarm current(2098-9806) <br /> Remote Alarm LED and Test Station Distance 250 ft(76 m)maximum <br /> Addressable Operation <br /> Data Communications IDNet or MAPNET II communications, auto-select, one address per housing; <br /> provides operating power to model 4098-9755 <br /> Model 4098-9756 with Supervised Multiple Relay Control,Requires Separate Fused 24 VDC from Fire Alarm Power Supply <br /> Input Voltage 18-32 VDC(24 VDC nominal) <br /> Standby Current 3 mA @ 24 VDC <br /> Alarm Current(one relay activated) 15 mA @ 24 VDC;add 15 mA for each additional remote�4098-9843 relay <br /> For use with 4098-9843 relay only,quantity of 15 maximum,distance of 500 ft <br /> Supervised Remote Relay Control Output (152 m)maximum, requires 4081-9008(ref 733-894) 10 kS2, 1/2 W end-of-line <br /> resistor <br /> 4098-9843 Relay Output Ratings,Single Form C, use with Model 4098-9756 Only <br /> Coil Current 15 mA @ 24 VDC, up to 15 maximum per relay control output <br /> Relay Contacts 7 A at 0 35 PF @ 28 VDC&120 VAC,250µA @ 5 VDC <br /> Location Distance 500 ft(152 m)maximum to relay coils, locate relays within 3 ft(1 m)of device <br /> being controlled per NFPA 72 <br /> Tyco,Simple,r,the Simplex logo,Tr:reAlnrn7,IDNet,and MAPNET II nre trndemarks of Tyco Internnnonnl Services AG or its nffr6ates in the U.S.and'or olher countries.NFPA 72 <br /> nnd Nntionnl Fire Alann Code nre registered trndemarks ojthe Nntional Fire Protection Association(NFPA) <br /> �3 Simplex Tyco Safety Products Westminster•Westminster, MA•01441-0001•USA S4098-0030-6 1/2009 <br /> � www tycosafetyproducts-usa-wm.com <br /> C�2009Tyco SnjetyProc�erc�s Wesm�inster All rights reserned A!!specificarrons and other iirfof��mtiai shown were n�nent a.r ojdocunrem revision date rnr�i nre se�6ject to chnnge without notice. <br />
The URL can be used to link to this page
Your browser does not support the video tag.