PRODUCT INFORMATION 4098 -9792 STANDARD SENSOR BASE
<br />FEATURES:
<br />• UL LISTED, FM APPROVED
<br />• TRUEALARM ANALOG SENSING PROVIDES DIGITAL TRANSMISSION OF ANALOG
<br />SENSOR VALUES VIA MAPNETII, OR IDNet TWO WIRE COMMUNICATIONS
<br />• FIRE ALARM CONTROL PANEL PROVIDES:
<br />- INDIVIDUAL SENSITIVITY SELECTION FOR EACH SENSOR
<br />-PEAK VALUE LOGGING ALLOWING ACCURATE ANALYSIS FOR SENSITIVITY SELECTION
<br />- AUTOMATIC ENVIRONMENTAL COMPENSATION
<br />- DISPLAY OF SENSITIVITY IN PERCENT PER FOOT
<br />- MULTISTAGE ALARM OPERATION
<br />- ABILITY TO DISPLAY AND PRINT DETAILED SENSOR INFORMATION IN PLAIN ENGLISH LANGUAGE
<br />• PHOTOELECTRIC SMOKE SENSOR 4098 -9714:
<br />SEVEN LEVELS OF SENSITIVITY FROM 0.2% TO 3.77.
<br />• IONIZATION SMOKE SENSOR 4098 -9717:
<br />FOUR LEVELS OF SENSITIVITY FROM 0.5% TO 1.7 %.
<br />• HEAT SENSOR 4098 -9733:
<br />- RATE -OF -RISE TEMPERATURE DETECTION IS SELECTABLE AT THE CONTROL PANEL FOR EITHER 15'F
<br />OR 207 PER MINUTE
<br />-FIXED TEMPERATURE SENSING IS INDEPENDENT OF RATE -OF -RISE AND PROGRAMMABLE TO OPERATE
<br />AT 1357 OR 1557
<br />- TRUEALARM HEAT SENSORS CAN BE PROGRAMMED AS A UTILITY DEVICE TO MONITOR
<br />FOR TEMPERATURE EXTREMES IN THE RANGE FROM 32' F TO 120' F.
<br />• UL STANDARD SPACING:
<br />-60 FT SPACING FOR 135' F
<br />-40 FT SPACING FOR 155' F
<br />• INTEGRAL RED LED FOR POWER -ON (PULSING), OR ALARM OR TROUBLE (STEADY ON)
<br />• BASE MOUNTED ADDRESS SELECTION:
<br />- ACCESSIBLE FROM FRONT (DIP SWITCH UNDER SENSOR)
<br />- ADDRESS REMAINS WITH ITS PROGRAMMED LOCATION
<br />• FOR USE WITH SIMPLEX 4010, 4100, 4020, AND 4120 SERIES CONTROL PANELS.
<br />• MAXIMUM QUANTITY OF DEVICES:
<br />-127 FOR 4020, 4100, 4120
<br />-250 FOR 4010, 4100
<br />• MOUNTING: CEILING OR WALL
<br />• COLOR : FROST WHITE
<br />• BASE DIMENSIONS: 15/16" X 4 -7/8"
<br />SPECIFICATIONS:
<br />• UL LISTED TEMPERATURE RANGE: 327 TO 1007
<br />• OPERATING TEMPERATURE RANGE: 32'F TO 129F
<br />• HUMIDITY RANGE: 10% TO 957. RH
<br />• PHOTOELECTRIC SENSOR AIR VELOCITY RANGE: 0 -2000 FT /MIN
<br />• IONIZATION SENSOR AIR VELOCITY RANGE: 0 -300 FT /MIN
<br />• WIRING CONNECTIONS: SCREW TERMINALS FOR IN /OUT WIRING, #18 TO #14 AWG
<br />•
<br />VOLTAGE (MAPNETII /IDNe ):/124 e ADDRESS PER BASE
<br />40VDC
<br />CURRENT: 400uA TYPICAL
<br />DESCRIPTION:
<br />TRUEALARM SENSOR BASES CONTAIN INTEGRAL ADDRESSABLE ELECTRONICS
<br />THAT CONSTANTLY MONITOR THE STATUS OF THE DETACHABLE PHOTOELECTRIC,
<br />IONIZATION, OR HEAT SENSORS. EACH SENSOR'S OUTPUT IS DIGITIZED AND
<br />TRANSMITTED TO THE SYSTEM FIRE ALARM CONTROL PANEL EVERY FOUR SECONDS.
<br />SINCE TRUEALARM SENSORS USE THE SAME BASE, DIFFERENT SENSOR TYPES
<br />CAN BE EASILY INTERCHANGED TO MEET SPECIFIC LOCATION REQUIREMENTS. THIS
<br />FEATURE ALLOWS INTENTIONAL SENSOR SUBSTITUTION DURING BUILDING CONSTRUCTION.
<br />WHEN CONDITIONS ARE TEMPORARILY DUSTY, INSTEAD OF COVERING THE SMOKE SENSORS.
<br />HEAT SENSORS MAY BE INSTALLED WITHOUT REPROGRAMMING THE CONTROL PANEL,
<br />ALTHOUGH THE CONTROL PANEL WILL INDICATE AN INCORRECT SENSOR TYPE, THE HEAT
<br />SENSOR WILL OPERATE AS A DEFAULT SENSITIVITY PROVIDING HEAT DETECTION FOR
<br />BUILDING PROTECTION AT THAT LOCATION.
<br />WIRING:
<br />1. ALL WIRING TO COMPLY WITH LOCAL CODE.
<br />2. CONDUCTORS MUST TEST FREE OF ALL GROUNDS. FROM PREVIOUS
<br />MAPNET(( /IDNet DEVICE
<br />3. MAINTAIN CORRECT POLARITY
<br />4. MAPNETII /IDNet WIRING TO BE #18 AWG TWISTED SHIELDED , PAIR OR FIRE ALARM
<br />5. IF SHIELD IS USED, TWIST SHIELD WIRES TOGETHER AND CAP WITH CONTROL PANEL
<br />WIRE NUT. SHIELD SHOULD BE INSULATED FROM ELECTRICAL BOX.
<br />6. REFER TO INSTALLATION INSTRUCTIONS (574 -707)
<br />7. REFER TO APPLICATION MANUAL (574 -709)
<br />4" X 1 1/02" DEEP OCTAGONAL
<br />4" SQUARE XR 1/2" DEEP, WHICH REQUIRES
<br />A 4098 -9832 ADAPTER PLATE (6 -3/8" X 1/4 ")
<br />BOX SUPPLIED BY CONTRACTOR - , _
<br />MAPNETII /IDNet ADDRESS DIP SWITCHES
<br />SEE BASE INSTALLATION INSTRUCTIONS
<br />574 -709 FOR SETTINGS
<br />4098 -9714 PHOTOELECTRIC SMOKE SENSOR
<br />4098 -9717 IONIZATION SMOKE SENSOR
<br />W9d -9/15 HtAI JtNWt
<br />�-J
<br />o� Ilm
<br />FLUSH MOUNTING
<br />(BOX TO BE FLUSH OR RECESSED 1/4" MAXIMUM)
<br />a
<br />TrueAlertTMNON—ADDRESSABLE MULTI — CANDELA
<br />PRODUCT INFORMATION (WALL MOUNT)
<br />FEATURES:
<br />• UL LISTED TO STANDARD 1971 4905 -9931 ADAPTER PLAT
<br />• ADA COMPATIBLE
<br />SYNCHRONIZATION FLASH RATE MODE FOR USE WITH:
<br />• SEPARATE STROBE SYNCHRONIZATION MODULES THAT ARE AVAILABLE
<br />FOR CLASS B OR CLASS A OPERATION
<br />• SEPARATE SMARTSYNC CONTROL MODULES (SCMS) THAT PROVIDE
<br />CLASS B OR CLASS A OUTPUT FROM CONVENTIONAL NAC INPUTS
<br />SPECIFICATIONS:
<br />• HOUSING DIMENSIONS: 5 -1/8" H X 5" W X 2 -3/4" D (130mm X 127mm X 70mm)
<br />• TEMPERATURE RANGE: 32 -F TO 122 -F (0 TO 50'C)
<br />• HUMIDITY RANGE: 107. TO 93% NON- CONDENSING AT 109F (38 -C)
<br />• TERMINAL BLOCKS FOR 18AWG TO 12AWG; TWO WIRES PER
<br />TERMINAL FOR IN /OUT WIRING.
<br />WIRING:
<br />1. NOTIFICATION APPLIANCES ARE RATED PER INDIVIDUAL NAMEPLATE LABEL. S
<br />2. MAINTAIN CORRECT POLARITY ON TERMINAL CONNECTIONS. DO NOT LOOP
<br />WIRES UNDER TERMINALS.
<br />3, ALL NAC WIRING CONNECTIONS ARE SUPERVISED AND POWER— LIMITED.
<br />4. SEE INSTALLATION INSTRUCTIONS (579 -548) FOR ADDITIONAL INFORMATION.
<br />STROBE:
<br />• RATED VOLTAGE RANGE: UL LISTED: 16 VDC TO 33 VDC PER UL 1971
<br />ULC LISTED: 20 VDC TO 30 VDC PER ULC S526 —M878
<br />• FLASH RATE: 1 Hz
<br />• SYNCHRONIZED MODE NAC LOADING: MAXIMUM OF 35 SYNCHRONIZED STROBES PER NAC CIRCV
<br />+rl IRRFNT nRAWC RFFI F1'T ';TRnRF FI ASHIN(,
<br />PRODUCT INFORMATION
<br />FEATURES:
<br />• UL LISTED
<br />• FM APPROVED
<br />• CALIFORNIA STAiiE FIRE MARSHAL LISTING NUMBERS:
<br />2098 -9163 CONTROL ZAM: 7300 - 0026:182
<br />• ZONE ADAPTER MODULES (ZAMS) PROVIDE
<br />ADDRESSABILITY TO CONVENTIONAL CIRCUITS
<br />• FOR USE WITH SIMPLEX MAPNET II COMMUNICATIONS
<br />• NFPA STYLE 4 OR 6 COMMUNICATIONS
<br />• STYLE 4 WIRING', MAY BE EITHER "T" TAPPED OR IN /OUT
<br />• DIP SWITCH ADDRESS SELECTION, 8 SWITCHES
<br />O • MOUNTING: SURFACE
<br />SPECIFICATIONS:
<br />• DEVICE QTY: 1217 MAPNET II DEVICES ON A SINGLE PAIR OF WIRES
<br />• OPERATING TEMIPERATURE RANGE: 32' F TO 120' F
<br />• HUMIDITY RANG';E: 85% NON- CONDENSING 0 86 F
<br />• CONTROL ZAM RELAY CONTACTS ARE RATED AT: 5A 0 120
<br />VAC OR 2A 0 28 VDC, RESISTIVE
<br />• SUPERVISORY (OCCURRENT: 10 mA MAX LOAD PER ZAM
<br />• ALARM DC CIIFRRENT: 40 mA
<br />DESCRIPTION:
<br />CONTROL ZAMS ARE USED TO PROVIDE ADDRESSABLE
<br />CONTROL FUNCiiiONS SUCH AS ELEVATOR CAPTURE, HVAC
<br />CONTROL, PRESSURIZATION FAN CONTROL, DAMPER CONTROL
<br />WIRING:
<br />1. ALL WIRING TO COMPLY WITH LOCAL CODE.
<br />2. CONDUCTOR °S MUST TEST FREE OF ALL GROUNDS.
<br />3 SHHIIELDEDI LUNES ARE 0 BE J18 AWG (CONSULT STIR SALES ENGINEERING
<br />FOR EXCEP n IONS).
<br />4. MAXIMUM ALLLOWABLE LINE RUN FROM
<br />4020 OR 4000 OR 4120 TO FARTHEST
<br />DEVICE NOTT TO EXCEED 2500 FEET.
<br />5. FOR MAXIM(UM VOLTAGE PROP,ETC.,REFER TO
<br />MAPNET II ADDRESSABLE CONTROL LAM 2190 -9163
<br />2R A O NO. 1 BOX 11 /WSQUARE
<br />SUPPLIED BY CONTRACTOR
<br />(RACO N0. 203) EXTENSION
<br />11 1 2" DEEP
<br />SUP �LIED BY CONTRACTOR
<br />STIR SALES ENGINEERING S 4020 OR 4100 1
<br />OR 4120 FfIELD WIRING GUIDE. 0 2
<br />6. MINIMUM NCO. 14 AWG WIRE FOR 28 VDC WIRING, 0 3
<br />OR TO LOC, AL CODE. 8 4
<br />7. CONTRACTONR WIRING TO RELAY CONTACTS IS 6N
<br />UNSUPERVISED. USE NO. 14 AWG, OR TO SEE WIRING NOTES B sNc
<br />LOCAL CODNE. 7, 8, 9 7No
<br />8. RELAY CONIT,ACTS RATED 2A, 28 VDC. FOR DC e
<br />LOADS. POYNER MUST BE PROVIDED FROM FA 0 ONO
<br />1
<br />CONTROL 41020 OR 4100 OR POWER SUPPLY LISTED o
<br />FOR FIRE FPROTECTNE SIGNALING USE DERATE -- re2
<br />CONTROL 41020 OR 4100 OR POWER SUPPLY LISTED
<br />CURRENT RRATING BY 507. FOR INDUCTIVE LOADING.
<br />9. REFER TO ( INSTALLATION INSTRUCTIONS 575 -279 OR
<br />575 -592.
<br />10. REFER TO FIELD WIRING DIAGRAMS 841 -804 OR
<br />841 -996.
<br />TO ADDITIONAL MAPNETII/IDNet DEVICES 28VDC p
<br />OR RETURN TO FIRE ALARM CONTROL
<br />PANEL FOR A STYLE 6 APPLICATION FROM PREVIOUS DEVICES
<br />OR FIRE ALARM CONTROL
<br />PANEL
<br />MAPNET _0
<br />SHIELD —
<br />VISIBLE NOTIFICATION APPLIANCE
<br />WHEN SURFACE ".AOUNTING USE 4" SQUARE x 1 -1/2" DEEP BOX
<br />RED SKIRT NO. 4905 -9937 OR
<br />WHITE SKIRT NO. 4905 -9940 /
<br />MODEL NUMBER
<br />HOUSING
<br />COLOR
<br />LETTERING
<br />COLOR
<br />STROBE
<br />RATING
<br />RMS CURRENT 0
<br />16 VDC
<br />18 VDC
<br />24 VDC
<br />4906 -9101
<br />1 RED
<br />WHITE
<br />15cd
<br />60 mA
<br />53
<br />mA
<br />40 mA
<br />1070 •
<br />30cd
<br />94 mA
<br />84
<br />mA
<br />63 mA
<br />REMOTE ALARMI LED CURRENT
<br />75cd
<br />186 mA
<br />165
<br />mA
<br />124 mA
<br />ADDRE-SSAB E OPERATION
<br />110cd
<br />252 mA
<br />224 mA
<br />168 mA
<br />4906 -9103 1 WHITE RED
<br />15cd
<br />60 mA
<br />53
<br />mA
<br />40 mA
<br />SINGLE FORM C
<br />30cd
<br />94 mA
<br />84
<br />mA
<br />63 mA
<br />500 FT. 152 N TO RELAY COILS, RELAY MUST BE
<br />WITHIN 3 FT. mF DEVICE BEING CONTROLLED PER
<br />NFPA 72 SEC IO-9.2.1
<br />75cd
<br />186 mA
<br />165
<br />mA
<br />124 mA
<br />110cd
<br />252 mA
<br />1 224
<br />mA
<br />1 168 mA
<br />U
<br />FROM A CO
<br />SMARTSYNC
<br />IMPORTANT!
<br />WALL MOUNT INSTALLATION
<br />HEIGHT REFERENCE
<br />SMARTSYNC
<br />MODULE (SI
<br />OR SIMPLE)
<br />ELECTRICAL BOTTOM OF LENS
<br />BOX OUTLINE IS EITHER EVEN WITH
<br />C
<br />�
<br />OR 9922 S
<br />OR SLIGHTLY ABOVE
<br />i O
<br />w
<br />N N .—
<br />Co 00 m
<br />5 c)
<br />BOTTOM OF
<br />i
<br />mM
<br />I I I
<br />COMPATIBLE BOXES
<br />���
<br />NFPA 72 REQUIRES THAT
<br />M M M
<br />u¢O
<br />000om
<br />THE ENTIRE LENS BE NOT
<br />u
<br />0
<br />Q -
<br />OQ
<br />80" LESS THAN 80" AND NOT
<br />_a
<br />o
<br />J Lu X
<br />MIN. GREATER THAN 96" ABOVE
<br />THE FINISHED FLOOR.
<br />U)U)LL
<br />•
<br />x
<br />t
<br />N
<br />CONDUIT CUTOUTS ARE PROVIDED
<br />ON ALL FOUR SIDES.
<br />APATIBLE SIMPLEX
<br />NAC OR FROM
<br />CONTROL
<br />M) 4905 -9938
<br />4905 -9914
<br />ANC CUBE
<br />WIRE
<br />FOR
<br />N BE
<br />JNTING
<br />ALTERNATE BACK BOXES
<br />1. 2 GANG 1 -1/2" DEEP BOX
<br />2. SINGLE GANG 1 -1/2" DEEP BOX
<br />SEMI —FLUSH MOUNTING
<br />TO ADDITIONAL NOTIFICATION
<br />APPLIANCE DEVICE OR RETURN
<br />TO FACP FOR STYLE Z APPLICATION
<br />IF LAST DEVICE ON CIRCUIT IN A
<br />+� STYLE Y APPLICATION PLACE A
<br />10K 1/2W END -OF LINE RESISTOR
<br />JIRVDC IIVICIVJII I
<br />VIEWING SLOT
<br />FUSE 2
<br />MAPNET II ADDRESS DIP SWITCHES --�
<br />SEE INSTALLATI N INSTRUCTIONS
<br />PER t575 -279) FOR SETTINGS
<br />2 MTG SCREW 8 -32 FHMS
<br />2 SCREWS SIMPLEX P/N 412 -779
<br />SIMPLEX SURFACE COVER
<br />lq
<br />SURFACE MOUNTING
<br />TO ADDITIONAL MAPNET II
<br />SHIELD
<br />DEVICES OR RETURN TO
<br />FIRE ALARM CONTROL
<br />MAPNET PANEL FOR STYLE 6
<br />SYSTEM APPLICATION
<br />28VDC TO NEXT DC
<br />POWERED DEVICE
<br />SHIELD 10 e t SHIELD 10 Is
<br />9 _B 2
<br />o MAPNET- 0 -(B) 4 MAPNET- 8 6
<br />+(C)
<br />MAPNET+ 5 0 +(C) 6NC o MAPNET+ 5 E IS
<br />Ov 4 -�g� 7NO 4 E
<br />3 0 +(R) l5i 8C 3
<br />2 0 9NC 2 6
<br />28VDC 1 e +(R) 10NO 28VDC i
<br />Ts /'j j1 TF2 TB1
<br />SEE WIRING NOTES
<br />5, 6
<br />FUSE 1
<br />SEE WIRING N
<br />3, 4, 5
<br />FUSE 2 FUSE 1
<br />SEE WIRING NOTES
<br />3, 4, 5
<br />SSE WIRING NOTES
<br />5, 6
<br />4098 -9756 ADDRESSABLE 4 —WIRE DUCT SENSOR MAPNET II /IDNet
<br />PRODUCT 'INFORMATION
<br />FEAIURES: DUCT DETECTOR SELECTION CHART
<br />COMPACT AIR DUOCT SENSOR HOUSING WITH CLEAR COVER
<br />TO MONITOR FORZTHE PRESENCE OF SMOKE
<br />INCLUDES FACTOFRY INSTALL TRUEALARM PHOTOELECTRIC SMOKE
<br />DETECTOR VvIIppAND FEATURES: pp pp pp SS��
<br />• CONTROILP(VE OTO IDET8%?NSENSOf SSTADTUBS THE HOST
<br />• DIGITAL TRAN ISMISSION OF ANALOG SENSOR VALUES VIA
<br />MAPNET II OR IDNet 2 -WIRE COMMUNICATIONS
<br />• PROGRAMMAE,BLE SENSITIVITY CONSISTENT ACCURACY
<br />MONITORINEG OF SENSOR DIRTTNaCCUMUTATIONLNG, AD
<br />MoD DUCT EEN COR H USSINGG yyyyITH 8UPERVISE UTpUT FOR
<br />rFR LAYSEAREE UNDEREPANE'L CONTROL SAND CAN 2E VDC
<br />TIVATED UNNUALLY OR BY A SEPARATE ALARM /INPUT)
<br />GENERAL FEATURES:
<br />• UL LISTED TTO STANDARD 268A
<br />•
<br />CLEAR COVggEERpRALLOWS VISUAL INSPECTION
<br />• WITH CSVER� IN pVIDEEFUNCTIONAL SMOKE TESTING ACCESS
<br />•
<br />OUNTS TOI RECT�INGULAR DUCTS OR ROUND DUCTS
<br />MINIMUM SRZE 8 SQUARE OR 18" DIAMETER)
<br />• MAGNETIC TTEST FEATURE FOR ALARM INITIATION AT HOUSING
<br />• OPTIONAL WVEATHERPROOF ENCLOSURE IS AVAILABLE
<br />SEPARATELY' (REFER TO DATA SHEET S4098 -0032
<br />DIAGNOSTIC LEDS3 (ON INTERFACE BOARD):
<br />• RED ALARMLL TROUBLE LED FOR SENSOR STATUS AND
<br />COMMUNICAI, ONS POLLING DISPLAY
<br />DUCT SMOKE SENSOR HOUSING WITH PHOTOELECTRIC SENSOR
<br />MODEL
<br />F min m min
<br />COMPATIBILITY
<br />4098 -9756
<br />DUCT HOUSING WITH SUPERVISED
<br />1�55� 44 gg 84 RE�DESC(RIIPTIO�N SEpq�gTEL R Q I Eg
<br />SEPARATE024 VDC3FIRE AYLAR�iRfQOWFIR LAND RELAYY)ENDE OUFRLINE
<br />RESISTOR
<br />4008, 4010,E40 0 4100, AND 4120.
<br />REMOTE LED INDICATOR AND TEST STATION, SELECT ONE IF REQUIRED
<br />MODEL
<br />DESCRIPTION
<br />MOUNTING
<br />2098 -9808
<br />RED LED STATUS INDICATOR
<br />USE SINGLE GANG BOX,
<br />3" H X 2" W X 2" D
<br />76 mm X 51 mm X 51 mm
<br />2098 -9806
<br />TEST STATION WITH KEYSWITCH AND RED LED STATUS TURNING
<br />SWITCH TO TEST INITIATES ALARM FOR SYSTEM TESTING
<br />TUBE SUPPORT HOLE SHALL BE USED
<br />FOR DUCTS MORE THAN 3 FEET WIDE
<br />INSERT RUBBER PLUG
<br />fn EXHAUST TUBE
<br />CUT TO 1/2 OF
<br />DUCT WHEN < 24"
<br />DO NOT INSERT
<br />RUBBER PLUG
<br />• YELLOW LED) FOR OPEN OR SHORTED TROUBLE INDICATION FOR DUCT WIDTHS FOR DUCT WIDTHS
<br />OF SUPERVI'ISED RELAY CONTROL 2098 -9808 2098 -9806 3' TO 95" 8" TO 3'
<br />SAMPLING TUBES; (ORDERED SEPARATELY REMOTE STATUS/ALARM TEST STATION
<br />:
<br />• AVAILABLE ITN( MULTIPLE LENGTHS T MATCH DUCT SIZE INDICATOR/
<br />• INSTALLED RAND SERVICED WITH HOUSING IN PLACE
<br />REMOTE MODULE: OPTIONS (ORDERED SEPARATELY): S (OPTIONAL)
<br />RED • EST STAT �M
<br />ION1 WITH LED (2098 -98 6))
<br />• RELAYS USEED (4098 -9843) ALARM INDICATOR
<br />SPECIFICATION`,S: RED
<br />ALARM
<br />LED
<br />GENERAL SNECIFICATIONS
<br />R VELOCITY G (LINEAR FT MIN
<br />F min m min
<br />ALTITUDE
<br />m
<br />SENSOR SENSITTrVITY RANGE
<br />AT HOST CONTROL PANEL
<br />UL LISTED TEM4F[RATURE RANGE
<br />32' IF TO 100' IF to 38' C)
<br />OPERATING IFWr'FRATURF RAN-GE
<br />=F-TU- 122' Q 10 by (A
<br />STORAGE TEMPPERATURE RANGE
<br />0' F TO 140' F -18' C TO 69 C
<br />HUMIDITY RANG3E
<br />1070 •
<br />HOUSING 0
<br />,,.
<br />WIRING
<br />TERMINAL BLOCKS, 18 TO 12 AWG
<br />REMOTE STA ALARM LED AND TEST STATION WITH REMOTE STATUSIALARM LED
<br />REMOTE ALARMI LED CURRENT
<br />OR 2098 -9806
<br />TEST STATION I
<br />-
<br />REMOTE ALARMI L D AND TEST
<br />STATION DISTANMC
<br />250 FT. (76m) MAXIMUM
<br />ADDRE-SSAB E OPERATION
<br />DATA COMMUUNICATIONS
<br />ITO
<br />MAPNETII OR IDNet COMMUNICATION AUTO- SELECT
<br />1 ADDRESS PER HOUSING, PROVIDES OPERATING POWER
<br />MODEL 4098 -9755
<br />MODEL 4098 -99756 WITH SUPERVISED MULTIPLE RELAY CONTROL, REQUIRES SEPARATE FUSED
<br />24 VDC FROM FIRE ALARM POWER SUPPLY
<br />INPUT VOLTAGE:
<br />1 17 -32 VDC 24 VDC NOMINAL
<br />STANDBY CURRENT
<br />1 3 mA 0 24 VDC
<br />ALARM CURRENVT
<br />15 mA 0 24 VDC ADD 15 mA ADDITIONAL FOR EACH
<br />4098 -9843 RELAY
<br />4098 -9843 RELAY OUTPUT RATINGS,
<br />SINGLE FORM C
<br />COIL CURRENT
<br />Ito mA 9 24 VDC -UP TO 15 MAX. PER RELAY CONTROL
<br />OUTPUT
<br />RELAY NTACIT RESISTIVE TI S
<br />7 A 0 28 VDC & 120 VAC' 250 uA 0 5 VDC
<br />LOCATION DISTTANCE
<br />500 FT. 152 N TO RELAY COILS, RELAY MUST BE
<br />WITHIN 3 FT. mF DEVICE BEING CONTROLLED PER
<br />NFPA 72 SEC IO-9.2.1
<br />SEE NOT
<br />3, 4
<br />BLK
<br />BLK
<br />WITH 24VDC RELAY
<br />(OPTIONAL)
<br />2098 -9806
<br />REMOTE ALARM
<br />INDICATOR/
<br />ALARM
<br />LED
<br />'I— TEST
<br />SEE NOTES 3,4
<br />1 I ii 1'
<br />D_
<br />J Q
<br />J W
<br />J >
<br />W Q'
<br />ZW
<br />Z cn
<br />Ly
<br />,,.
<br />X17
<br />Lw am
<br />om va
<br />im
<br />CL
<br />05Cf
<br />N J
<br />oQ
<br />LM4
<br />BLK
<br />BLK
<br />WITH 24VDC RELAY
<br />(OPTIONAL)
<br />2098 -9806
<br />REMOTE ALARM
<br />INDICATOR/
<br />ALARM
<br />LED
<br />'I— TEST
<br />SEE NOTES 3,4
<br />RED-JBL1(
<br />4100+ OR 412 `
<br />MAPNET II /IDNet SHIELD
<br />SHIELD _ 1/2 W lOK EOL
<br />SHIELD NOTE 1 BLU-C RESISTOR
<br />(OPTIONAL) 4098 -9843
<br />PAM -SD YEL -N.C. 4081 -9008
<br />POWER CIRCUIT + ® �Y ORG -N.
<br />24 VDC - + 1 1/2 W 10K EOL N.Ct
<br />WIRING NOTES: RE RE 408119008 rN.O�
<br />1. DUCT SENSOR WIRING IS 12 TO 18 AWG, II
<br />2. MAXIMUM QUANTITY OF DEVICES PER CIRCUIT IS 127 FOR 4020, ARE
<br />4100 +, OR 4120, AND 250 FOR THE 4010 PANEL DAMPER IiM
<br />3. THE 2098 -9806 AND 2098 -9808 ARE POLARIZED, OBSERVE COLOR -CODED WIRING. L
<br />4. MAXIMUM WIRE LENGTH TO TEST TERMINALS AND REMOTE LED IS 250 FEET.
<br />® 4098 -9843 PAM -SD RELAY (AIR PRODUCTS & CONTROL LIMITED) ARE RATED AT
<br />7 AMPS 28 VDC /10 AMPS 0 115 VAC. MAXIMUM WIRE LENGTH TO PAM -SD RELAYS IS FSD POWER
<br />500 FT. (15 PAM -SD RELAYS MAX.). WIRING FROM THE RELAY TO THE (BY OTHERS) AHU POWEI
<br />DEVICE IT IS CONTROLLING SHOULD BE NO MORE THAN 3 FT. (PER NFPA 72). (BY OTHER`.
<br />t t
<br />TO OTHER M
<br />IDNet DEVICE
<br />= SEE NOTE 2
<br />RETURN TO I
<br />FOR STYLE E
<br />T
<br />4098 -9843
<br />RREEIAY
<br />+
<br />millill 1•
<br />D_
<br />J Q
<br />J W
<br />J >
<br />W Q'
<br />ZW
<br />Z cn
<br />Ly
<br />X17
<br />Lw am
<br />om va
<br />im
<br />CL
<br />05Cf
<br />RED-JBL1(
<br />4100+ OR 412 `
<br />MAPNET II /IDNet SHIELD
<br />SHIELD _ 1/2 W lOK EOL
<br />SHIELD NOTE 1 BLU-C RESISTOR
<br />(OPTIONAL) 4098 -9843
<br />PAM -SD YEL -N.C. 4081 -9008
<br />POWER CIRCUIT + ® �Y ORG -N.
<br />24 VDC - + 1 1/2 W 10K EOL N.Ct
<br />WIRING NOTES: RE RE 408119008 rN.O�
<br />1. DUCT SENSOR WIRING IS 12 TO 18 AWG, II
<br />2. MAXIMUM QUANTITY OF DEVICES PER CIRCUIT IS 127 FOR 4020, ARE
<br />4100 +, OR 4120, AND 250 FOR THE 4010 PANEL DAMPER IiM
<br />3. THE 2098 -9806 AND 2098 -9808 ARE POLARIZED, OBSERVE COLOR -CODED WIRING. L
<br />4. MAXIMUM WIRE LENGTH TO TEST TERMINALS AND REMOTE LED IS 250 FEET.
<br />® 4098 -9843 PAM -SD RELAY (AIR PRODUCTS & CONTROL LIMITED) ARE RATED AT
<br />7 AMPS 28 VDC /10 AMPS 0 115 VAC. MAXIMUM WIRE LENGTH TO PAM -SD RELAYS IS FSD POWER
<br />500 FT. (15 PAM -SD RELAYS MAX.). WIRING FROM THE RELAY TO THE (BY OTHERS) AHU POWEI
<br />DEVICE IT IS CONTROLLING SHOULD BE NO MORE THAN 3 FT. (PER NFPA 72). (BY OTHER`.
<br />t t
<br />TO OTHER M
<br />IDNet DEVICE
<br />= SEE NOTE 2
<br />RETURN TO I
<br />FOR STYLE E
<br />T
<br />4098 -9843
<br />RREEIAY
<br />+
<br />D_
<br />J Q
<br />J W
<br />J >
<br />W Q'
<br />ZW
<br />Z cn
<br />Ly
<br />im
<br />CL
<br />05Cf
<br />N J
<br />oQ
<br />LM4
<br />°41
<br />U
<br />C
<br />�
<br />i O
<br />w
<br />N N .—
<br />Co 00 m
<br />5 c)
<br />r
<br />i
<br />mM
<br />I I I
<br />Q
<br />���
<br />M M M
<br />u¢O
<br />000om
<br />u
<br />0
<br />Q -
<br />OQ
<br />w
<br />NU
<br />_a
<br />o
<br />J Lu X
<br />�
<br />U)U)LL
<br />0
<br />U
<br />z
<br />0
<br />a
<br />a
<br />U
<br />w
<br />0
<br />z
<br />0
<br />o
<br />o
<br />z
<br />H
<br />w
<br />N
<br />� �
<br />w
<br />W
<br />Q
<br />W
<br />O
<br />Q
<br />�' O
<br />D u-
<br />cn
<br />QO
<br />co j
<br />�0
<br />�-+
<br />° o-
<br />E--i w
<br />° N ul
<br />DRAWN BY:
<br />DATE:
<br />J.SERRANO
<br />10— JAN
<br />-2012
<br />CONFIGURED BY:
<br />DATE:
<br />J.SERRANO
<br />10— JAN
<br />-2012
<br />REVIEWED BY:
<br />DATE:
<br />J.SERRANO
<br />10 —JAN
<br />-2012
<br />PROJECT NUMBER
<br />961923408
<br />SHEET TITLE:
<br />TYPICAL DEVCEC WIRING
<br />FIRE
<br />ALARM SYSTEM
<br />SHEET NUMBER:
<br />FA -701
<br />
|