DN-60054:D
<br /> . Intelligent Bases �J N OT 1 F 1 E R°
<br /> B501(A), B2005(A), 82005R(A),
<br /> �' B71 OLP(A), 62241 BI(A), B224R6(A), by H o n eywe I I
<br /> Mounting Kits, and Accessories
<br /> � -
<br /> ..�;..,m w,v
<br /> General ����. .. . ,.;, $. _ .�r. �� ��
<br /> _;�Z`� E
<br /> Intel�igent FlashScan�and CLIP mounting bases and kits pro- , �y
<br /> vide a variety of ways to install NOTIFIER detectors in any � "_�;
<br /> application. Intelligent detectors can be mounted in either $ �
<br /> flanged or flangeless bases depending on junction box selec- ,��_ � '..��1�
<br /> tion (see Junction Box Selection Guide). Across this product g
<br /> line, detectors plug in easily to the base with SEMS screws; Flangeless Mounting Base � Flangeless Surface
<br /> and models employ various 12 to 24 AWG wire ranges. Mounting Base
<br /> Relay, isolator, and sounder bases can be used to meet ,°,�s�=,���e:. �����qa,; ��
<br /> local code requirements. Relay bases provide one Form-C
<br /> contact relay for control of auxiliary functions such as door clo-
<br /> sure and elevator recall. Isolator bases allow loops to continue ,.�^"' �
<br /> to operate under fault conditions and automatically restore '=��' , � g
<br /> when the fault is removed. Sounder bases are available in � S
<br /> temporal and non-temporal pattern versions depending on
<br /> whether the signal is to be used for evacuation purposes. Flanged Mounting Base �
<br /> Specifications $ -�`���"�
<br /> � `°���:
<br /> x -� .
<br /> Diameter. „�;,,��;,,,$ � t,
<br /> —8501:4.1"(104 mm). _:....-„-��,.-.;�. : fig
<br /> r'�`�r::_..�� � �i
<br /> —822481,B224RB,6710LP:6.1"(155 mm) � '-�'�
<br /> —82005/SR:6.875"(17.46 cm). g� • ��
<br /> Wire gauge: Sounder Base Relay Base
<br /> —8224B1,6224RB:14 to 24 AWG.
<br /> —8710LP, 8501,B200S/SR: 12 to 24 AWG. Sound output:measured in a UL reverberant room at 10 feet,
<br /> Temperature range: 24 Volts(continuous tone).
<br /> —822481, B224R8, 8200S/SR: 32°F to 120°F (0°C to —B200S,high-volume:Greater than 85 dBA minimum.
<br /> 49°C). —B200S,low-volume:Greater than 75 dBA minimum.
<br /> —B710LP,B501�-4°F to 150°F(0°C to 66°C). —8200SR:Greater than 85 dBA minimum.
<br /> Humidity range: 10%to 93%RH,non-condensing. FOR B224RB,B224B1: �
<br /> System temperature and humidity ranges: This system Operating voltage: 15 to 32 VDC(powered by SLC).
<br /> meets NFPA requirements for operation at 0°C to 49°C (32°F
<br /> to 120°F); and at a relative humidity(noncondensing) of 85% Standby ratings:<500 NA maximum � 24 VDC.
<br /> at 30°C (86°F) per NFPA, and 93% t 2% at 32°C t 2°C Set time (8224RB only): short delay 55 to 90 msec; long
<br /> (89.6°F t 1.1°F)per ULC. However,the useful life of the sys- delay 6 to 9 seconds.
<br /> tem's standby batteries and the electronic components may be Reset time(B224RB only):20 msec maximum.
<br /> adversely affected by extreme temperature ranges and humid-
<br /> ity. Therefore, it is recommended that this system and all Relay characteristics(B224RB only):two-coil latching relay;
<br /> peripherais be installed in an environment with a nominal room one Form-C contact; ratings(UUCSA) 0 9 A � 125 VAC,0.9
<br /> temperature of 15°C to 27°C(60°F to 80°F). A� 110 VDC,and 3.0 A� 30 VDC.
<br /> Electrical Ratings Product Line Information
<br /> FOR B200S/SR: INTELLIGENT BASES
<br /> External supply voltage: 16 to 33 VDC(VFWR) 6501:Flangeless mounting base.
<br /> Standby current:500 NA maximum. B501A:Flangeless mounting base,UlC Listed.
<br /> Alarm current: B501 BP:Bulk pack of B501 (10).
<br /> —6200S:25 mA maximum at high-volume setting; B71;OLP:Flanged mounting base.
<br /> 15 mA maximum at low-volume setting. 6710LPA:Flanged mounting base,ULC Listed.
<br /> —6200SR:35 mA maximum. B710LPBP:Bulk pack of B710LPBP(�0).
<br /> SLC operating voltage: 15 to 32 VDC. 6200S: Intelligent addressable sounder base capable of pro-
<br /> SLC standby current:300 NF ducing sound output in high or low volume with ANSI Temporal
<br /> 3,ANSI Temporal 4,continuous tone,marching tone,and cus-
<br /> tom tone.
<br /> DN-60054:D•09/22/2010—Page 1 of 2