dn-60429:b
<br /> �lI �'.,�-� :��.,,;I°�r�pF.,�..�= ,.,s;..�..ti.:,;��;r.�
<br /> �:Innova�rFle;x. N OT 1 F 1 E R°
<br /> r . .�.,. :� � .�.L F �J
<br /> Intelligent Non-Relay Photoelectric
<br /> . Duct Smoke Detector by H o n eywe I I
<br /> . -
<br /> General
<br /> � .�:--� .�
<br /> The Notifier InnovairFlex DNR intelligent non-relay photoelectric
<br /> duct smoke detector and DNRW watertight non-relay photoelec-
<br /> tric duct smoke detector feature a pivoting housing that fits both
<br /> square and rectangular footprints capable of mounting to a
<br /> round or rectangular duct.
<br /> ,�.,,
<br /> DNRW duct smoke detector,with its NEMA-4 rating,is listed as : �
<br /> a watertight,UV resistant enclosure providing protection against =,�'�
<br /> falling dirt, rain, and windblown dust, splashing and hose
<br /> directed water, allowing operators to use the detector in the �
<br /> �
<br /> most extreme environments. �
<br /> `� ! : .
<br /> These units sense smoke in the most challenging conditions, #,�� •• ° ' a .
<br /> operating in airtlow speeds of 100 to 4,000 feet per minute,tem- �?�-Y,� �.- � �F.� � _�¢ ,;,.;• ; � 6
<br /> M'�'•� x �'4��.'4�',,it�^ .,�s,9 ui`t�` .°znn ��
<br /> peratures of -4 degrees F to 158 degrees F, and a humidity ,`;"�;�,;�s���^€v;_.=;��, °�,�;.,=M��' „� , P��N�.,�'S T•`����;,,. F
<br /> range of 0 to 95 percent(non-condensing.) �:. :<�•��:�.�_.�:�:v:�° , e. . � °"..�. '• ; .;. ,. .
<br /> An improved cover design isolates the sensor head, which Specifications
<br /> allows for ease of maintenance. A cover tamper feature indi-
<br /> cates a trouble signal for a removed or improperly installed sen- Size: (Rectangle) 14.38 in (37 cm) l_ength; 5 in (12.7 cm)
<br /> sor cover.The Notifier InnovairFlex housing provides a 3/4-inch Width,2.5 in(6.6 cm)Depth
<br /> conduit knockout and ample space to facilitate easy wiring and Size: (Square)7.75 in(19.7 cm) Length; 9 in(22.9 cm)Width;
<br /> mounting of a relay module. 2.5 in(6.35 cm)Depth
<br /> The Notifier InnovairFlex duct smoke detector can be custom- Weight: 1.6 Ib(0.73 kg)
<br /> ized to meet local codes and specifications without additional Operating Temperature Range:-4 degrees F to 158 degrees F
<br /> wiring. The new InnovairFlex product line is compatible with all �_20 degrees C to 70 degrees C)
<br /> previous Innovair models,including remote test accessories.
<br /> Storage Temperature Range:-22 degrees F to 158 degrees F
<br /> Features (-30 degrees C to 70 degrees C)
<br /> Operating Humidity Range:0%to 95°ro relative humidity(non-
<br /> • Photoelectric,integrated low-flow technology condensing)
<br /> • Air velocity rating from 100 fUmin to 4,000 fUmin (0.5 m/s to Air Duct Velocity: 100 to 4,000 ft/min(0.5 to 20.32 Ms)
<br /> 20.32 m/s)
<br /> • Versatile mounting options: square or rectangular configura- ACC@SSOI'IeS
<br /> tion
<br /> • Broad ranges for operating temperature (-4F to 158F) and Notifier provides system flexibility with a variety of accessories,
<br /> humidity(0%to 95�o non-condensing) including two remote test stations and different means of visible
<br /> • Patented sampling tube installs from front or back of the and audible system annunciation.As with our duct smoke detec-
<br /> detector with no tools required tors,all duct smoke detectors accessories are UL listed.
<br /> • Cover tamper signal �NR(W)s with a date code of 0013 or higher do not require
<br /> • Increased wiring space with a newly added 3/4" conduit external 24VDC for remote test applications when used with a
<br /> knockout remote-test-capable detector
<br /> • Avaiiable space within housing to accommodate mounting of ACCESSORY CURRENT LOADS AT 24 VDC
<br /> a relay module
<br /> • Easily accessible code wheels on sensor head (sold sepa-
<br /> rately) Device Standby Alarm
<br /> • Clear cover for convenient visual inspection RA100Z OmA 12 mA Max
<br /> • Remote testing capability
<br /> • Requires com line power only RTS151/ OmA 12mA Max
<br /> • Accommodates the installation of an addressable relay mod- RTS151 KEY
<br /> ule, sold separately, (FRM-1 or NC-100R) for applications
<br /> requiring a Form-C relay
<br /> dn-60429:b•03J1 Z/10—Page 1 of 2
<br />
|