<br /> C� D N-7112:G
<br /> _ NFS-320(E) �J N OTI F 1 E R°
<br /> Intell�gent Addressable
<br /> _ Fire �►larm System by H o n eywe I I
<br /> Generai
<br /> The NFS-320 intelligent Fire Alarm Control Panel is part of the
<br /> ONYX�Series of Fire Alarm Controls from NOTIFIER.
<br /> In stand-alone or network configurations,ONYX Series products �
<br /> meet virtually every application requirement. ��., �,.
<br /> The NFS-320's modular design makes system planning easier. �i''�� , �
<br /> The panel can be configured with just a few devices for small
<br /> building applications,or networked with many devices to protect
<br /> a large campus or a high-rise office block.Simpy add additional
<br /> peripheral equipment to suit the application.
<br /> For installations using NFS-320C, an optional ACM Series $
<br /> annunciator can be mounted in the same cabinet (up to 48 0
<br /> zones/points,order separately;see DN-6008�. �
<br /> The FireWatch Series internet monitoring modules IPDACT-2 �
<br /> and IPDACT2UD permit monitoring of alarm signals over the
<br /> Internet,saving the monthly cost of two ded(cated business tele- NFS-320
<br /> phone lines. Although not required, the secondary telephone
<br /> line may be retained providing backup communication over the
<br /> public switched telephone line. • Alarm Verification se�ectlon per point,with tally.
<br /> NOTE:Un/ess called out with a version-specific H" "C"o�E'at • Presignal/Positive Alarm Sequence(PAS).
<br /> the end ol the part number, NFS-320"refers to mode/s NFS-320, . Silence inhibit and Auto Silence tfiner options.
<br /> NFS-320R,NFS-320C,and NFS-320E. • NAC coding functions:
<br /> Fe1tY1'@S -March time.
<br /> -Temporal.
<br /> • Certified for seismic applications when used with the appro- _California rivo-stage coding.`
<br /> priate seismic mounting kit. -Canadian two-stage.
<br /> • Approved for Marine applications when used with listed com- _Strobe synchronization.
<br /> patible equipment(see DN-60688).
<br /> • One isolated intelligent Signaling Line Circuit(SLC)Style 4,6 ' Field-programmable on panel or on PC,with VeriFire�Toois
<br /> or 7 program check,compare,simulate.
<br /> • Up to 159 detectors(any mix of ion,photo,thermal,or multi- ' Full QWERTY keypad.
<br /> sensor) and 159 modules (Addressable pull stations, nor- • Battery charger supports 18-200 AH batteries.
<br /> maliy open contact devices, two-wire smoke, notiflcation, or • Non-alarm points for tower prioriiy functions.
<br /> relay).318 devices maximum. • Remote ACK/Signal Silence/System ReseUDrill via monitor
<br /> • Standard 80-character display. modules.
<br /> • Network options: • Automatic time control functions,with hotiday exceptions.
<br /> -High-speed network for up to 200 nodes (NFS2-3030, . Extensive,built-in transient protection.
<br /> NFS2-640, NFS-320(C), NFS-320SYS, NCA-2, DVC, . Powerfui Boolean logic equations.
<br /> ONYXWorks, NFS-3030,NFS-640,and NCA).
<br /> -Standard network for up to 103 nodes(NFS2-3030, NFS2- FLASHSCAN�INTELLIGENT FEATURES
<br /> 640, NFS-320(C), NFS-320SYS, NCA-2, DVC, ONYX- • Poll up to 318 devices in less than two seconds.
<br /> Works, NCS, NFS-3030, NFS-640, NCA, AFP-200, AFP- . Activate up to 159 outputs in less than five seconds.
<br /> 300/400, AFP-1010, and AM2020). Up to 54 nodes when Multicolor LEDs blink device address durin Walk Test.
<br /> DVC is used in network paging. ' 9
<br /> • 6.0 A power supply with four Class A/B built-in Notification ' Fully digital,high-precision protocol(IJ.S.Patent 5,539,389).
<br /> Appliance Circuits (NAC). Selectable System Sensor, • Manual sensitivity adjustment—nine levels.
<br /> Wheelock,or Gentex strobe synchronization. • Pre-alarm ONYX intelligent sensing--nine levels.
<br /> • Built-in Alarm,Trouble,Security,and Supervisory relays. • Day/Night automatic sensitivity adjustment.
<br /> • VeriFire�Tools online or offline programming utility. Upload/ • Sensitiviry windows:
<br /> Download, save, store, check, compare, and simulate panel -lon-0.5 to 2.5%/foot obscuration.
<br /> databases.Upgrade panel firmware. -photo-0.5 to 2.35%/foot obscuration.
<br /> • Autoprogramming and Walk Test reports. -Laser(VIEW�)-0.02 to 2.0°/Jfoot obscuration.
<br /> • Optional universal 31 S-point DACT -AccUmate(�PIusT"'-0.5 to 4.0%/foot obscuration.
<br /> • 80-character remote annunciators(up to 32). -Intelli�uad-1.0 to 4.0%/foot obscuration.
<br /> • EIA-485 annunciators,including custom graphics. -IntelliQuadT"'PLUS-1.0 to 4.0%/foot obscuration
<br /> • Printer interface(80-column and 40-column printers). . Drift compensation(U.S. Patent 5,764,142).
<br /> • History fife with 800-event capacity in nonvolatile memory,
<br /> plus separate 200-event alarm-only file.
<br /> DN-7112:G•12/19/2011—Page 1 of 6