Laserfiche WebLink
Zephyrhills Fire Rescue <br /> 6907 Dairy Road, Zephyrhills, FL 33542 <br /> Fire Chief Bus (813) 780-0041 <br /> Keith Williams Fax (813) 780-0044 <br /> 29 June 2012 <br /> Plan Number 12-024 <br /> Project: Bullfrog Performance, 5037 Gall Blvd <br /> Number of Pages: 3 with supporting documents <br /> Date received by this Office: 06-24-2012 <br /> This Officer has reviewed the plan for renovation and construction of retail sales <br /> occupancy located at 5037 Gall Blvd, Zephyrhills. Plans are approved as submitted with <br /> the following conditions: <br /> 1. No Smoking signs must be posted at each entrance, and at fuel storage <br /> locations. <br /> 2. Fuel tank installation must be to NFPA 30 requirements (explosian proof <br /> electrical, set back distances, vent location, emergency shut-off, etc). Shut-off <br /> may be located adjacent to roll-up door outside of the confines of covered <br /> storage. <br /> 3. Remote semi-bulk transfer station may be constructed to allow fuel transfer. <br /> This shall require a static grounding and bonding system to be installed in that <br /> location. Any nearby electrical shall meet explosion proof requirements. <br /> Storage of semi-bulk fuels shall be limited to one fifty five (55) gallon drum <br /> of each type of fuel dispensed. Maximum of 3 drums present. Empty drums <br /> shall be removed to secured covered storage exterior to the building and <br /> properly disposed in a timely manner. <br /> 4. Sales floor area requires ABC extinguisher(s), fuel storage and exterior fuel <br /> tanks require BC extinguishers at each location. <br /> 5. Emergency lighting required in sales floor area, restroom and warehouse area, <br /> may field locate after layout/showroom design. <br /> 6. Smoke alarms required in warehouse storage area and sales floor. <br /> 7. Two hour firewall shall be constructed between showroom and wa.rehouse <br /> storage. Fire rated door shall be installed between show room and warehouse <br /> area. It shall be labeled at 10 foot intervals with: "2-Hour Firewall Do Not <br /> Penetrate, Protect All Openings" on any unfinished areas or side. l"Warehouse <br /> side and above ceiling, if so installed). ` <br /> 8. Exit lights required for exit doors and exit access. (May be combination <br /> Emergency/Exit lights) <br /> 9. Fire rated door required for fuel can storage room at rear of structi�re. <br /> 10. Lightweight truss sign required to be installed. <br /> Payment of permit fee indicates acceptance of the requirements of these review <br /> comments. <br />