ELECTRICAL SPECIFICATIONS <br />1. ENGINEER: <br />THIS ENGINEER SHALL BE THE SOLE INTERPRETER OF THE ELECTRICAL DRAWINGS AND SPECIFICATIONS. <br />2. CONTRACTOR: <br />CONTRACTOR SHALL MEAN BOTH THE GENERAL CONTRACTOR AND ALL SUBCONTRACTORS. CONTRACTOR <br />SHALL BE RESPONSIBLE FOR ALL WORK SHOWN AND ADDRESSED. BY SIGNING THE CONTRACT, <br />CONTRACTOR ACKNOWLEDGES THAT HE UNDERSTANDS ALL REQUIREMENTS CONTAINED IN THE DRAWINGS <br />AND SPECIFICATIONS CLEARLY AND THOROUGHLY. IF THE CONTRACTOR HAS ANY QUESTIONS OR <br />REQUIRES CLARIFICATIONS, HE SHALL BRING THOSE TO THE ATTENTION OF THIS ENGINEER IN WRITING <br />PRIOR TO BIDDING. CONTRACTOR SHALL BE RESPONSIBLE FOR THE IMPLEMENTATION OF WORK <br />ADDRESSED IN ALL CONSTRUCTION DOCUMENTS, COVERING ALL DISCIPLINES. ALL CONTRACTORS SHALL <br />BE LICENSED IN THE STATE OF FLORIDA AND IN THE LOCALITY IN WHICH THE WORK IS PERFORMED. <br />3. VERIFY: <br />VERIFY SHALL MEAN THAT THE CONTRACTOR SHALL CAREFULLY REVIEW AND INSPECT THE DRAWINGS, <br />SPECIFICATIONS AND ALL EXISTING SITE CONDITIONS PRIOR TO BIDDING. IF THERE ARE ANY <br />DISCREPANCIES BETWEEN SAID ITEMS, CONTRACTOR SHALL BRING THOSE TO THE ATTENTION OF THE <br />ENGINEER IN WRITING PRIOR TO BIDDING. NO MONETARY COMPENSATION SHALL BE AWARDED TO THE <br />CONTRACTOR DUE TO UNAVAILABILITY OF SPACE, CAPACITY OR ANY OTHER EXISTING CONDITIONS OR <br />DISCREPANCIES IN THE CONSTRUCTION DOCUMENTS. <br />4. GENERAL: <br />PROVIDE MATERIAL, EQUIPMENT, ACCESSORIES, INCIDENTALS, ARTICLES, ITEMS, OPERATIONS, INCLUDING <br />LABOR, NECESSARY OF COMPLETION OF WORK INDICATED AND /OR CALL FOR ON THESE DRAWINGS. <br />5. REGULATORY REQUIREMENTS: <br />ALL WORK SHALL BE PER 2007 FLORIDA BUILDING CODE, NEC 2008 OR AS ADOPTED BY THE LOCAL <br />AUTHORITIES HAVING JURISDICTION. <br />6. COORDINATION: <br />INSTALLATION OF ALL WORK SHALL BE COORDINATED WITH THE BUILDING'S EXISTING CONDITIONS AND <br />BUILDING STANDARDS. ALL NEW WORK INSTALLED SHALL MATCH THE BUILDING STANDARD. <br />COORDINATE WITH THE OWNER. <br />7. WARRANTEES: <br />CONTRACTOR SHALL PROVIDE A WRITTEN ONE YEAR WRITTEN WARRANTY FOR ALL MATERIALS AND LABOR <br />FROM THE DATE OF SUBSTANTIAL COMPLETION. WARRANTEES SHALL COVER ALL LABOR AND MATERIAL <br />TO REPLACE DEFECTIVE MATERIALS AND TO ENSURE PROPER OPERATION OF ALL SYSTEMS. <br />8. INSTALLATION: <br />ALL EQUIPMENT AND MATERIAL SHALL BE INSTALLED PER THEIR RESPECTIVE MANUFACTURER'S WRITTEN <br />INSTRUCTIONS. PROVIDE ADEQUATE CLEARANCE FOR ALL EQUIPMENT AND MATERIAL FOR REGULAR <br />MAINTENANCE, REMOVAL AND AIR FLOW. <br />9. FEES AND PERMITS: <br />CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS AND FEES. <br />10. INSURANCE AND DAMAGE: <br />CONTRACTOR SHALL CARRY INSURANCE NOT LESS THAN 200% OF THE TOTAL COST OF THE PROJECT. <br />ALL DAMAGES CAUSED BY THE CONTRACTOR SHALL BE PAID FOR BY THE CONTRACTOR. <br />11. EXCAVATION, DEWATER AND BACKFILL: <br />CONTRACTOR SHALL BE RESPONSIBLE FOR EXCAVATING, DEWATERING AND BACKFILLING. ALL <br />EXCAVATION SHALL BE BY HAND. PIPING AND CONDUIT RUN UNDERGROUND SHALL BE INSTALLED AT A <br />MINIMUM OF 24" BELOW FINISHED GRADE. ROUTING OF UNDERGROUND PIPING AND CONDUIT SHALL BE <br />VERIFIED PRIOR TO BIDDING AND THE COST OF BYPASSING ALL EXISTING VISIBLE OBSTRUCTIONS SHALL <br />BE INCLUDED IN THE BID. ENTIRE ROUTING SHALL BE VIDEO TAPED PRIOR TO START OF WORK TO <br />DOCUMENT THE CONDITION OF THE EXISTING SURFACES. ALL AREAS AFFECTED SHALL BE RESURFACED <br />TO THEIR ORIGINAL CONDITION. A COPY OF THE VIDEO TAPE INDICATING THE DATE TAKEN SHALL BE <br />PROVIDED TO THE ARCHITECT PRIOR TO START OF WORK. <br />12. PHASING: <br />ALL PHASES AND SCHEDULING OF DEMOLITION AND RENOVATION WORK SHALL BE COORDINATED WITH <br />THE OWNER OR OWNER'S REPRESENTATIVE. <br />CONTRACTOR. TEMPORARY POWER SHALL BE PROVIDED BY THE <br />13. EXISTING CONDITIONS: <br />SCOPE OF WORK UNDER THIS CONTRACT INCLUDES WORK IN AN EXISTING BUILDING. PRIOR TO <br />BIDDING, CONTRACTOR SHALL VISIT THE JOB SITE AND SHALL VERIFY SIZE, CAPACITY, PERFORMANCE <br />AND LOCATION OF ALL EXISTING WORK. CONTRACTOR SHALL ALSO VERIFY ALL AVAILABLE CLEARANCES <br />PRIOR TO BIDDING. EXISTING WORK IS OBTAINED FROM EXISTING DRAWINGS AND HAS NOT BEEN <br />VERIFIED BY THIS ENGINEER. EXISTING WORK IS SHOWN FOR REFERENCE ONLY. CONTRACTOR SHALL <br />PAY FOR ANY AND ALL CHANGES DUE TO EXISTING CONDITIONS REQUIRED TO COMPLETE THE WORK AS <br />SHOWN IN THE CONSTRUCTION DOCUMENTS. ALL WORK SHALL BE PERFORMED BY CONTRACTORS <br />LICENSED IN THE AREA OF DISCIPLINE IN WHICH THEY WORK. VERIFY STATUS OF ASBESTOS EXISTENCE <br />OR CONTAINMENT WITH THE ARCHITECT. <br />14. DEMOLITION: <br />ALL WORK TO BE REMOVED SHALL BE TURNED OVER TO THE OWNER FOR OWNER'S USE. CONTRACTOR <br />SHALL DISPOSE ALL EXISTING WORK NOT USED OR ACCEPTED BY THE OWNER PROPERLY PER LOCAL, <br />STATE AND FEDERAL CODES AS APPLICABLE. <br />15. SCOPE OF WORK: <br />WORK SHALL INCLUDE FURNISHING AND INSTALLING OF ALL MATERIAL AND LABOR; WIRING, <br />CONDUCTORS, CONDUITS, JUNCTION BOXES, PULL BOXES, RECEPTACLES, SWITCHES, SAFETY SWITCHES, <br />PANELS, APPLIANCES AND ALL OTHER LABOR AND MATERIAL AND ACCESSORIES AND SPECIFIED OR <br />REQUIRED FOR A COMPLETE POWER AND LIGHTING SYSTEM. <br />16. SUBSTITUTION: <br />CONTRACTOR SHALL BID THE PROJECT AS SHOWN AND SPECIFIED. CONTRACTOR, AT HIS OPTION, MAY <br />CHOOSE TO USE SUBSTITUTED EQUIPMENT AND MATERIAL IN LIEU OF THOSE SPECIFIED. IF SO, <br />CONTRACTOR SHALL USE A SEPARATE LINE IN HIS BID PROPOSAL FOR EACH SUBSTITUTED MATERIAL <br />AND EQUIPMENT WITH AN ASSOCIATED ADD OR DEDUCT COST. SUBSTITUTED ITEMS SHALL NOT BE <br />FURNISHED AND INSTALLED UNLESS APPROVED IN WRITING BY THIS ENGINEER. <br />17. MATERIAL & WORKMANSHIP: <br />ALL MATERIAL SHALL BE NEW AND SHALL CONFORM TO THE STANDARDS OF IEEE, NEMA AND THE <br />UNDERWRITER'S LABORATORIES. <br />18. COMPLIANCE WITH CONSTRUCTION DOCUMENTS: <br />CONTRACTOR SHALL FOLLOW THE CONSTRUCTION DOCUMENTS CLOSELY WITHOUT EXCEPTION. IF THE <br />CONTRACTOR WISHES TO MAKE ANY CHANGES TO THE CONSTRUCTION DOCUMENTS, HE MUST OBTAIN <br />WRITTEN PERMISSION FROM THIS ENGINEER AND WAIT UNTIL DIRECTED BY THIS ENGINEER IN WRITING <br />TO MAKE THE REQUESTED CHANGES. IF THE WORK INSTALLED IS REJECTED BY THIS ENGINEER OR <br />THE BUILDING OFFICIALS DUE TO NONCOMPLIANCE OF THE WORK INSTALLED WITH THE WORK SHOWN IN <br />THE CONSTRUCTION DOCUMENTS, THE CONTRACTOR SHALL PAY THE ENGINEER $200 PER HOUR, IN <br />ADVANCE, FOR ANY WORK THAT THE ENGINEER AND THE ARCHITECT MAY HAVE TO DO TO OBTAIN THE <br />NECESSARY PERMITS FROM THE BUILDING OFFICIALS. THE ENGINEER WILL GIVE THE CONTRACTOR THE <br />ANTICIPATED NUMBER OF HOURS, PRIOR TO MAKING ANY CHANGES TO THE CONSTRUCTION DOCUMENTS. <br />IF THE CONTRACTOR REFUSES TO PAY THE ENGINEER FOR THE ENGINEER AND ARCHITECT'S ADDITIONAL <br />TIME, THE CONTRACTOR SHALL HAVE TO REMOVE ALL NONCOMPLIANT WORK AND INSTALL WORK AS <br />ORIGINALLY SHOWN IN THE CONSTRUCTION DOCUMENTS AT CONTRACTOR'S EXPENSE. <br />19. WORK INCLUDED: <br />CONTRACTOR SHALL BE RESPONSIBLE FOR THE IMPLEMENTATION OF WORK ADDRESSED IN ALL <br />CONSTRUCTION DOCUMENTS, COVERING ALL DISCIPLINES. <br />20. PAINTING: <br />ALL EXPOSED PIECES OF EQUIPMENT & CONDUIT, INCLUDING THOSE MOUNTED ON THE ROOF SHALL BE <br />PAINTED TO MATCH SURROUNDING SURFACES. SEE ARCHITECTURAL FOR PAINT SPECIFICATIONS. <br />21. ARCHITECT APPROVAL: <br />ALL WORK, INCLUDING BUT NOT LIMITED TO LIGHT FIXTURES, SWITCHING, OUTLETS, RECEPTACLES AND <br />EQUIPMENT SHALL BE APPROVED BY THE ARCHITECT. WHERE THERE ARE CONFLICTS BETWEEN THIS <br />SET OF SPECIFICATIONS AND THE ARCHITECT'S, THE ARCHITECT'S SPECIFICATIONS SHALL TAKE <br />PRECEDENCE. <br />22. BALANCING OF PHASES: <br />IT IS UNDERSTOOD THAT SOME CIRCUITING MAY BE CHANGED DUE CONSTRUCTION CONDITIONS. THIS IS <br />ACCEPTABLE. HOWEVER, ALL PHASES SHALL BE BALANCED TO WITHIN 10% OF EACH OTHER AS <br />ORIGINALLY DESIGNED. <br />23. CONDUITS: <br />A. RIGID GALVANIZED STEEL CONDUIT SHALL BE USED FOR ALL EXPOSED & ABOVE GROUND AREAS. <br />B. ALL BRANCH CIRCUIT WIRING RUN IN CONCEALED WALLS AND CEILING SHALL RUN IN ELECTRICAL <br />METALLIC TUBING. <br />C. ALL UNDERGROUND WIRING SHALL RUN IN SCHEDULE 40 PVC PIPING. UG CONDUITS SHALL BE <br />INSTALLED A MINIMUM OF 24" BELOW GRADE. <br />D. REAM ALL CONDUITS TO REMOVE ANY SHARP EDGES. <br />E. ALL CONDUITS SHALL RUN PARALLEL AND PERPENDICULAR TO BUILDING WALLS, STRUCTURAL <br />MEMBERS AND CEILING LINES. DIAGONAL RUNS SHALL NOT BE ACCEPTED. RUNNING OF CONDUITS <br />OVER AND THRU LIGHT FIXTURES SHALL NOT BE ACCEPTED. <br />F. ALL CONDUITS SHALL BE SECURED IN PLACE PER NEC CHAPTER 3. <br />G. ALL CONDUITS BETWEEN BUILDINGS SHALL RUN UNDERGROUND UNLESS OTHERWISE NOTED. <br />24. WIRING: <br />ALL WIRING SHALL BE NEW AWG OR KCMIL THWN COPPER UNLESS OTHERWISE NOTED. ALUMINUM <br />WIRING SHALL NOT BE ACCEPTABLE UNLESS OTHERWISE NOTED. WIRE SIZES 8, 10 & 12 SHALL BE <br />SOLID COPPER. LARGER SIZES MAY BE STRANDED COPPER. ABANDONED WIRING IN CONDUIT RUNS <br />ABOVE CEILING SHALL BE REMOVED BACK TO TERMINATION POINTS AT BREAKER PANEL TO FREE UP <br />PANEL SPACE FOR FUTURE CONSTRUCTION. MC CABLE SHALL BE USED ABOVE GROUND, INDOORS, <br />PER 2008 NEC ARTICLE 330, ONLY WHERE SPECIFICALLY ADDRESSED. <br />NOTE TO PLAN REVIEWER <br />THIS IS AN EXISTING SINGLE STORY FACILITY. TO THE BEST OF THE KNOWLEDGE OF THIS ENGINEER, <br />NEW ELECTRICAL WORK IS LIMITED TO ADDITION OF NEW EXTERIOR SIGNS. PLEASE VERIFY WITH THE <br />ARCHITECTURAL CONSTRUCTION DOCUMENTS. EXISTING WORK IS SHOWN FOR REFERENCE. THIS FACILITY <br />HAS NO FIRE ALARM SYSTEM. <br />SERVICE CA CUl aTintic <br />* HIGHEST DEMAND OVER THE PREVIOUS 12 MONTHS AS OBTAINED FROM THE OWNER IS 16.0 KW. <br />* NEW LOADS ADDED ARE: <br />1.0 AMPS NEW CHANDELIER <br />6.9 AMPS NEW EXTERIOR WALL MOUNTED SIGN <br />21.1 AMPS NEW ONE MONUMENT SIGN <br />29.0 AMPS TOTAL NEW LOAD <br />* 29.0 AMPS X 1.25 = 36.3 AMPS OR 4.4 KW NEW LIGHTING LOAD <br />* 16.0 KW X 1.25 = 20.0 KW EXISTING PEAK LOAD <br />* 20.0 KW + 4.4 KW = 24.4 KW OR 102 AMPS TOTAL CALCULATED NEW LOAD <br />* EXISTING SERVICE IS 400 AMPS <br />25. GROUNDING: <br />EACH CIRCUIT SHALL BE PROVIDED WITH AN EQUIPMENT GROUNDING CONDUCTOR THE SIZE OF WHICH <br />SHALL NOT BE LESS THAN #12 AWG OR AS INDICATED ON THE DRAWINGS. ALL ISOLATED GROUND <br />RECEPTACLES SHALL BE PROVIDED WITH ORANGE COLOR COVER PLATE. <br />26. MULTIBRANCH CIRCUITING: <br />MULTI BRANCH CIRCUITS SHALL MEET THE REQUIREMENTS OF NEC 2008, PARAGRAPH 210.4 <br />27. DEVICES: <br />SWITCHES; 20 AMP, 120/277 VOLT RATING, COMMERCIAL GRADE, GROUNDED, WHITE DECORA, QUIET <br />FLUSH TYPE <br />RECEPTACLES; FLUSH TYPE, 20 AMP, 125 VOLT RATING WITH PARALLEL SLOTS AND DOUBLE SIDE <br />CONTACTS, GROUNDED, COMMERCIAL GRADE, WHITE. FLOOR MOUNTED RECEPTACLES SHALL BE GFCI, <br />BRASS OR BRONZE, WITH COVER PLATES. VERIFY MATERIAL WITH THE ARCHITECT. <br />PLATES; WALL AND CEILING PLATES SHALL BE WHITE, HIGH IMPACT NYLON. <br />ALL DEVICES SHALL BE SECURELY FASTENED IN PLACE. DEVICES INSTALLED IN STUD WALLS SHALL BE <br />SECURED IN PLACE BY TWO STUDS. <br />28. OUTLET BOXES: <br />OUTLET BOXES FOR SWITCHES AND WALL RECEPTACLES SHALL BE 4" SQUARE GALVANIZED STEEL WITH <br />A MINIMUM DEPTH OF 1 -1/2 ". ABOVE CEILING OUTLET BOXES SHALL BE FOUR INCH OCTAGON TYPE <br />OF GALVANIZED STEEL ALL OUTLET BOXES SHALL BE SECURED TIGHTLY. <br />29. EXTERIOR GRADE IN- GROUND PULL BOXES: <br />PULL BOXES SHALL BE 18"X18'7(12" DEEP FIBERGLASS, OPEN BOTTOM WITH LOCKABLE HEAVY TRAFFIC <br />NONSKID TOP PULL BOX AS MANUFACTURED BY BROOKS PRODUCTS OR APPROVED EQUAL, AS <br />REQUIRED. PROVIDE AS CONDITIONS REQUIRE. <br />30. LIGHT FIXTURES: <br />ALL LIGHT FIXTURES SHALL BE APPROVED BY THE ARCHITECT. ALL LIGHT FIXTURES SHALL BE <br />PROPERLY ALIGNED AND SUPPORTED. PROVIDE JUNCTION BOXES AS REQUIRED. GRID CEILING <br />SUPPORTING LIGHT FIXTURES SHALL BE SUPPORTED PER NEC ARTICLE 410- 36(B). <br />31. TESTING: <br />ALL WORK INSTALLED SHALL BE TESTED AND CERTIFIED BY THE CONTRACTOR IN WRITING THAT ALL <br />WORK HAS BEEN INSTALLED PER CONSTRUCTION DOCUMENTS AND IN PERFECT CONDITION. <br />32. CLOSEOUT DOCUMENTS: <br />PROVIDE THE OWNER WITH THREE SETS OF WARRANTIES, RELEASE OF LIENS, <br />MAINTENANCE MANUALS, CERTIFICATE OF COMPLETION, TESTING CERTIFICATE AND AS -BUILTS. ANY <br />DEVIATIONS FROM THE CONSTRUCTION DOCUMENTS SHALL BE NOTED ON THE AS -BUILT SETS. ALL <br />RECIRCUITING SHALL BE CLEARLY SHOWN ON THE PLANS & PANEL SCHEDULES, WARRANTIES SHALL <br />INCLUDE EQUIPMENT MANUFACTURER WARRANTEES PLUS ONE YEAR LABOR FROM THE SUBSTANTIAL <br />COMPLETION DATE. AS BUILTS SHALL BE PROVIDED BY THE CONTRACTOR IN ELECTRONIC FORM, <br />COMPATIBLE WITH THIS ENGINEER'S VERSION OF AUTOCAD, USING THE OWNER'S PREFERRED LAYERING <br />SYSTEM. FREEHAND CORRECTIONS /MARK UPS AND NON- ELECTRONIC AS BUILTS SHALL NOT BE <br />ACCEPTABLE. <br />ELECTRICAL LEGEND <br />SYMrl <br />AFF <br />TO <br />DESCRIPTION <br />44" <br />ILING RECESSED OR SURFACE LIGHT FIXTURE <br />TO <br />EILING <br />RECESSED OR SURFACE LIGHT FIXTURE <br />AFF <br />D <br />LING SURFACE OR HUNG LIGHT FIXTURE <br />�+ <br />DED FIXTURE INDICATES NIGHT LIGHT <br />U <br />O <br />RECESSED LIGHT FIXTURE <br />N <br />-+� <br />CEILING SURFACE LIGHT FIXTURE <br />N <br />WALL MOUNTED LIGHT FIXTURE <br />N <br />U <br />CEILING SURFACE OR HUNG TRACK LIGHTING <br />L <br />CEILING FAN /LIGHT <br />m <br />® <br />EXIT LIGHT <br />Q� <br />U <br />EMERGENCY LIGHT <br />A <br />Df.74 <br />EMERGENCY LIGHT <br />a <br />COMBINATION EXIT SIGN & EMERGENCY LIGHT <br />a <br />N d <br />Ch L <br />LIGHT SWITCH, SINGLE POLE, GROUNDED <br />Q p N <br />$3 <br />LIGHT SWITCH, SINGLE POLE, GROUNDED, THREE -WAY <br />-� O c) <br />LIGHT SWITCH, SINGLE POLE, GROUNDED WITH DIMMER <br />V) <br />cd <br />LIGHT SWITCH, SINGLE POLE, GROUNDED, MOTOR RATED <br />a) <br />U <br />JO <br />JUNCTION BOX <br />CM <br />I <br />DUPLEX RECEPTACLE, GROUNDED <br />C <br />m <br />N c",-4 <br />N <br />DUPLEX RECEPTACLE, GROUNDED <br />0 <br />COL o <br />-1 0 <br />.- <br />o ~ <br />00 <br />o <br />N <br />QUADPLEX RECEPTACLES, GROUNDED <br />QUADPLEX RECEPTACLES, GROUNDED <br />SIMPLEX RECEPTACLE, GROUNDED <br />1 <br />SIMPLEX RECEPTACLE, GROUNDED <br />RECEPTACLE, SPECIAL USE, VERIFY WITH EQUIP MANUFACTURER <br />DATA /PHONE /COMMUNICATIONS OUTLET <br />® <br />DATA /PHONE /COMMUNICATIONS OUTLET <br />FL <br />nI <br />L� <br />DISCONNECT SWITCH <br />6 <br />® <br />RELAY <br />D <br />DOOR BELL <br />4 <br />T c <br />RECEPTACLE, TRANSFORMER & CHIME <br />OS OS <br />P <br />® ® <br />OCCUPANCY SENSOR <br />SE <br />E ER <br />E: EXISTING TO BE RELOCATED ER: EXISTING RELOCATED <br />EXISTING WORK TO REMAIN <br />-X- -X- <br />EXISTING WORK TO BE REMOVED <br />GFCI GROUND FAULT CIRCUIT INTERRUPTER <br />IG <br />ISOLATED GROUND <br />WP WEATHER PROOF <br />44" INDICATES CENTERLINE INSTALLATION ELEVATION ABOVE FINISHED FLOOR <br />UG UNDERGROUND <br />MOUNTING <br />SEE SCHEDULE <br />SEE SCHEDULE <br />SEE SCHEDULE <br />SEE SCHEDULE <br />SEE SCHEDULE <br />SEE SCHEDULE <br />SEE SCHEDULE <br />SEE SCHEDULE <br />CEILING <br />96" AFF TO CL <br />84" AFF TO CL <br />CEILING MNTD <br />84" AFF TO CL <br />44" <br />AFF <br />TO <br />CL <br />44" <br />AFF <br />TO <br />CL <br />44" <br />AFF <br />TO <br />CL <br />AS REQUIRED <br />18" AFF TO CL <br />FLOOR MOUNTED <br />18" AFF TO CL <br />FLOOR MOUNTED <br />8" AFF TO CL <br />FLOOR MOUNTED <br />SEE NOTES <br />OOR MOUNTED <br />0'• AFF TO CL <br />CEILING <br />8" AFG TO CL <br />ER ARCHITECT <br />E SCHEDULE <br />U <br />LO <br />LO <br />N <br />� <br />M <br />J <br />LL <br />V) <br />a� <br />�+ <br />von <br />=tea` <br />U <br />E <br />H M Co <br />M <br />N <br />-+� <br />CU <br />N <br />O <br />N <br />U <br />W <br />L <br />Q <br />m <br />U <br />� <br />Q� <br />U <br />Y) <br />A <br />C <br />v <br />�L <br />a <br />N d <br />Ch L <br />U <br />Q p N <br />Q <br />0) N <br />-� O c) <br />c <br />V) <br />cd <br />0 _` p x <br />w <br />a) <br />U <br />E � <br />a� <br />cu <br />CM <br />I <br />W i S <br />C: `- -0 LO <br />C <br />m <br />N c",-4 <br />N <br />0 <br />COL o <br />-1 0 <br />.- <br />o ~ <br />00 <br />o <br />N <br />fit <br />W <br />�i�- avaZw�mzcW.�zUC=.�dz� Zzo <br />oa >o�w awa9 <br />c�a°c�o vwds� w�mo�� °�i <br />� W= <br />z w <br />o z y° m xa O o o zo 0 0° <br />W U <° -YUUtn Q. <br />u <br />LO <br />LO <br />c <br />� <br />M <br />J <br />LL <br />V) <br />.U� <br />�+ <br />von <br />=tea` <br />E <br />H M Co <br />M <br />N <br />z <br />U <br />N <br />O <br />L <br />c0°o� <br />W <br />=3 <br />O <br />m <br />U <br />� <br />E <br />U <br />a) <br />N <br />A <br />-C <br />� S Co <br />U a� <br />0 <br />cd <br />0) N <br />..0 <br />0 <br />o <br />V) <br />cd <br />o o <br />00 a <br />"Ne <br />LO <br />LO <br />Z <br />M <br />J <br />LL <br />M <br />W <br />.U� <br />L <br />N <br />z <br />U <br />O <br />> <br />W <br />=3 <br />O <br />m <br />O <br />� <br />Cis <br />0 <br />U <br />a) <br />N <br />M <br />Project Number <br />1127.11 <br />Distribution <br />E DATE <br />A IT 02.10, 2012 <br />o%1111111111 I <br />v Q` • ��C E NSA •.. /y'ii <br />* : No. 33700 <br />�p0 STATE OF CL, Specifications, <br />°,'��s•••::�o►oP..••'���'e Notes, Legend <br />'04 TONAL <br />re�al�aWyekhi <br />fl license no 33700 <br />