Laserfiche WebLink
� � � • . � • • � � � <br /> AED Graph <br /> 30000 <br /> 20000 <br /> � <br /> � <br /> 0 <br /> r <br /> 10000 <br /> 0 <br /> 8am 9am l0am 12am 12pm lpm 2pm 3pm 4pm Spm 6pm 7pm 8pm <br /> — Hourly Loads —Average <br /> � � � � � • <br /> System equipment selection wiil be made using the following derived values <br /> Summer Outdoor 91°F <br /> Summer Wet Bulb 77°F <br /> Summer Indoor �5�F <br /> Summer Design Grains 50% <br /> Winter Outdoor 40°F <br /> Winter Indoor �poF <br /> Sensible Cooling 29,008 Btuh <br /> Latent Cooling 5 343 Btuh <br /> , <br /> Required Cooling Airflow 1 319 CFM <br /> , <br /> Sensible Heating 21,498 Btuh <br /> Required Heaing Airflow 279 CFM <br /> All calculations are based upon approved hvac industry standards and procedures,and comply with all local, <br /> state and federal code requirements All computed results are Estimates Product provided by Energy Design <br /> Systems and Idea Tree <br />