Laserfiche WebLink
� � � • . � • • � � � <br /> AED Graph ', <br /> 60000 <br /> 40000 <br /> a <br /> m <br /> S <br /> 20000 <br /> 0 <br /> 8am 9am l0am llam 12pm lpm 2pm 3pm 4pm Spm 6pm 7pm 8pm <br /> �__Hourly Loads =Average , <br /> � � � � � � <br /> System equipment selection will be made using tf�e following derived values. <br /> Summer Outdoor 91°F <br /> Summer Wet Bulb 77°F <br /> Summer Indoor 75°F <br /> Summer Design Grains 50% <br /> Winter Outdoor 40°F <br /> Winter Indoor 70°F <br /> Sensible Cooling 60,012 Btuh <br /> Latent Cooling 10,143 Btuh <br /> Required Cooling Airflow 2,728 CFM <br /> Sensible Heating 42,032 Btuh <br /> Required Heating Airflow 546 CFM <br /> All calculations are based upon approved hvac industry standards and procedures,and comply with all local, <br /> state and federal code requirements.All computed results are Estimates.Product provided by Energy Design <br /> Systems and Idea Tree <br />