<br /> Total Buildin Summar Loads
<br /> �. ��, .�.
<br /> „ti,w
<br /> ;, .�.a�.
<br /> � 2A-m-d:Glazing-Double pane low-e (e =0.60), sliding 114 0 0 6,371 6,371
<br /> glass door, metal frame no break, u-value 0.84,
<br /> SHGC 0.61
<br /> I11 D: Door-Wood - Solid Core 21 0 0 254 254 I
<br /> 13BA-Oocw:Wall-Block, framing with R-11 in 2 x 4 stud 1161 0 0 2,117 2,117
<br /> cavity, open core, wood studs
<br /> 16A-25: Roof/Ceiling-Under Attic with Insulation on Attic 864 0 0 2,462 2,462 I
<br /> Floor (also use for Knee Walls and Partition Ceilings),
<br /> ' Unvented Attic, No Radiant Barrier, Any Roofing
<br /> Material,Any Roof Color, R-25 insulation
<br /> CustomFloori: Floor-Over open crawl space or garage, 864 0 0 648 648
<br /> Custom, My first example custom floor
<br /> I Subtotals for structure: 0 0 11,852 11,852
<br /> �' People: 3 600 690 1,290
<br /> Equipment: 0 1,200 1,200
<br /> i Lighting: 100 341 341
<br /> I Ductwork: 0 732 2,986 3,719
<br /> Infiltration:Winter CFM:0, Summer CFM: 0 0 0 0 0
<br /> Ventilation:Winter CFM:0, Summer CFM: 100 0 3,154 2,198 5,352
<br /> Total Building Load Totals: 0 4,486 19,268 23,754
<br /> � . . ..
<br /> _.. . .. _ _..
<br /> _ ,
<br /> . .�r: ,.. y� .t:#° - �- � }.
<br /> . ,
<br /> ��... :s�:�.�F'?�r ':��-,L,..'�'v .. ':�, ._. :�, . .,Rx.;• ""4Pa�.'-�;.'. �-�s x„
<br /> #� :�y','.�.. .4'�;�.. �fi�:.t, �w`�ti,: i�,�n.�' "'3Y`.;'"'�`%.�':a��~�.�.�i .'i,{.�'"�i i.. ��,';'�,-*r,;
<br /> Total Building Supply CFM: 776 CFM Per Square ft.: ✓ p,ggg i*
<br /> � Square ft. of Room Area: 864 Square ft. Per Ton: 436
<br /> Volume (ft3) of Cond. Space: (clg.) 7,776 �
<br /> * Based on area of rooms being heated or cooled (whichever governs system) rather than entire floor area.
<br /> � - � . .,����`�;`�,x:. ��� � „,�..�a� �� ,�
<br /> y�.> s
<br /> ITotal Sensible Gain: 19,268 Btuh� � g1� %o� ,�6
<br /> Total Latent Gain: 4,486 Btuh 19 %
<br /> Total Cooling Required Including Ventilation Air: 23,754 Btuh 1.98 Tons(Based On Sensible + Latent) ,
<br /> � . . , .- - . ... :,�. ..m;�;y�,. �,,y^, .t„ ;����; ;�_.���:� - I
<br /> �?s:..k 'Y+", , ' �+�s �,.�.A'�'�� M1`x����';�•x Y�'`S;"-'�1'`'�'tr,gR $ F#�`tR_��-;P
<br /> i Rhvac is an ACCA approved Manual J and Manual D computer program.
<br /> Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
<br /> All computed results are estimates as building use and weather may vary.
<br /> Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at I
<br /> your design conditions. I