Laserfiche WebLink
Project: FMC-Urgent Care <br /> Title: FMC- Urgent Care <br /> Type: Healthcare-Clinic <br /> (WEA File: FL_TAMPA INTERNATIONAL AP.tm3) <br /> System Report Compliance <br /> RTU-1 RTU-1 Constant Volume Packaged No. of Units <br /> System � <br /> Component Category Capacity Design Eff Design IPLV Comp- <br /> Eff Criteria lPLV Criteria liance <br /> Cooling System Air Conditioners Evap 12 60 11.50 12.60 11.70 PASSES <br /> Cooled 65000 to 135000 <br /> Btu/h Cooling Cap <br /> Heating System Electric Furnace 1.00 1 00 PASSES <br /> Air Handling Air Handler(Supply)- 0.34 0 82 PASSES <br /> System -Supply Constant Volume <br /> Air Distribution ADS System (Sup) 6.00 PASSES <br /> System (Sup) <br /> RTU-2 RTU-2 Constant Volume Packaged No. of Units <br /> System � <br /> Component Category Capacity Design Eff Design 1PLV Comp- <br /> Eff Criteria lPLV Criteria liance <br /> Cooling System Air Conditioners Evap 14.00 12.10 14.00 12.30 PASSES <br /> Cooled<65000 Btu/h <br /> Cooling Capacity <br /> Heating System Electric Furnace 1.00 1 00 PASSES <br /> Air Handling Air Handler(Supply)- 0 39 0.82 PASSES <br /> System-Supply Constant Volume <br /> Air Distribution ADS System (Sup) 6.00 PASSES <br /> System (Sup) <br /> RTU-3 RTU-3 Constant Volume Packaged No. of Units <br /> System � <br /> Component Cate�ory Capacity Design Eff Design IPLV Comp- <br /> Eff Criteria lPLV Criteria liance <br /> Cooling System Air Conditioners Evap 12 60 11.50 12.60 11.70 PASSES <br /> Cooled 65000 to 135000 <br /> Btu/h Cooling Cap <br /> Heating System Electric Furnace 1 00 1.00 PASSES <br /> Air Handling Air Handler(Supply)- 0.35 0.82 PASSES <br /> System-Supply Constant Volume <br /> Air Distribution ADS System (Sup) 6 00 PASSES <br /> System (Sup) <br /> EnergyGauge Summit0 Fla/Com-2010. Section 506.4 Compliant Software. Effective Date: March 15, 2012 <br /> 6/12/2012 Page 8 of 16 <br />