Laserfiche WebLink
AHU/CU-1 AHU-1 Constant Volume Air Cooled No. of Units <br /> Single Package System< 1 <br /> 65000 B �/hr <br /> Component Category Capacity Design Eff Design IPLV Comp- <br /> Eff Criteria lPLV Criteria liance <br /> Cooling System Air Conditioners Air Cooled 13.00 12.23 8.00 PASSES <br /> Single Pkg<65000 Btu/h <br /> Cooling Capacity <br /> Heating System Heat Pumps Air Cooled 7.70 7.70 PASSES <br /> (Heating Mode) Single Pkg <br /> <65000 Btu/h Cooling <br /> Capacity <br /> Air Handling Air Handler(Supply)- 0.38 0.82 PASSES <br /> System-Supply Constant Volume <br /> Air Distribution ADS System(Sup) 6.00 4.20 PASSES <br /> System(Sup) <br /> Air Distribution ADS System(Ret) 6.00 4.20 PASSES <br /> System(Ret) <br /> Energy Recovery Compliance Not Applicable PASSES <br /> Unit <br /> AHU/CU-5 AHU-5 Constant Volume Air Cooled No.of Units <br /> Single Package System< 1 <br /> _ 65000 R �/hr <br /> Component Category Capacity Design Eff Design IPLV Comp- <br /> Eff Criteria lPLV Criteria liance <br /> Cooling System Air Conditioners Air Cooled 13.00 12.23 8.00 PASSES <br /> Single Pkg<65000 Btu/h <br /> Cooling Capacity <br /> Heating System Heat Pumps Air Cooled 7J0 7.70 PASSES <br /> (Heating Mode) Single Pkg <br /> <65000 Btu/h Cooling <br /> Capacity <br /> Air Handling Air Handler(Supply)- 0.38 0.82 PASSES <br /> System-Supply Constant Volume <br /> Air Distribution ADS System(Sup) 6.00 4.20 PASSES <br /> System(Sup) <br /> Air Distribution ADS System(Ret) 6.00 4.20 PASSES <br /> System(Ret) <br /> Energy Recovery Compliance Not Applicable PASSES <br /> Unit <br /> AHLT/CU-6 AHU-6 Constant Volume Air Cooled No. of Units <br /> Single Package System< 1 <br /> �sonn Rt�ihr <br /> Component Category Capacity Design Eff Design IPLV Comp- <br /> Eff Criteria lPLV Criteria liance <br /> EnergyGauge Summit0 Fla/Com-2010.Section 506.4 Compliant Software.Effective Date:March 15,2012 <br /> 3/13/2013 Page 10 of 13 <br />