My WebLink
|
Help
|
About
|
Sign Out
Browse
Search
13-14152
Zephyrhills
>
Building Department
>
Permits
>
2013
>
13-14152
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
3/25/2014 11:36:03 AM
Creation date
3/25/2014 11:35:10 AM
Metadata
Fields
Template:
Building Department
Company Name
FIRST CHURCH OF NAZARENE
Building Department - Doc Type
Permit
Permit #
13-14152
Building Department - Name
FIRST CHURCH OF NAZARENE
Address
6151 12TH ST
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
21
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
SpectrAlert Advance Specfications <br /> . , <br /> Generaf <br /> SpectrAlert Advance horns,strobes,and horn strobes shall mount to a standard 4 x 4 x 1 Yz-inch back box,4-inch octagon back box,or <br /> double-gang back box.Two-wire products shall also mount to a single-gang 2 x 4 x 17B-inch back box.A universal mounting plate shall <br /> be used for mounting ceiling and wall products.The notification appliance circuit wiring shall terminate at the universal mounting plate. <br /> Also,SpectrAlert Advance products.when used with the Sync•Circuit"'Module accessory,shall be powered from a non-coded notification <br /> appliance circuit output and shall operate on a nominal 12 or 24 volts.When used with the Sync•Circuit Module, 12-volt rated notification <br /> appliance circuit outputs shall operate between 8 and 17.5 volts;24volt-rated notification appliance circuit outputs shall operate between 16 <br /> and 33 volts.Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or fuli-wave <br /> rectified unfiltered power suppiy.Strobes and horn strobes shall have field-selectable candela settings including 15, 15/75,30,75,95,110, <br /> 115,135, 150, 177,and 185. <br /> Strobe <br /> The strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and shail be approved for fire protective service. <br /> The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for <br /> visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash <br /> tube and associated lens/reflector system. <br /> Hom Strobe Combination <br /> The horn strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and UL 464 and shall be approved for <br /> fire protective service.The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with <br /> Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light <br /> shall consist of a xenon flash tube and associated lens/reflector system.The horn shall have three audibility options and an option to switch <br /> between a temporai three pattern and a non-temporal(continuous)pattern.These options are set by a muftipie position switch.On four-wire <br /> products,the strobe shall be powered independently of the sounder.The horn on horn strobe models shall operate on a coded or non-coded <br /> power supply. <br /> Synchroniza4ion Module <br /> The module shall be a System Sensor Sync•Circuit model MDL listed to UL 464 and shall be approved for fire protective service.The module <br /> shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three.Also,while operating the strobes,the module shall silence the horns <br /> on horn strobe modeis over a single pair of wires.The module shall mount to a 411/16 x 411/16 x 21B-inch back box.The module shall also <br /> control two Style Y(class 6)circuits or one Style Z(class A)circuit.The module shall synchronize multipie zones.Daisy chaining rivo or more <br /> synchronization modules together will synchronize all the zones they control.The module shall not operate on a coded power supply. <br /> Standard Operating Temperature 32°F to 120°F(0°C to 49°C) <br /> Humidity Range 10 to 93°�non-condensing <br /> Strobe Flash Rate 1 flash per seCOnd <br /> Nominal Vo4tage Regulated�2 DC/FWR or regulated 24 DC/FWR' <br /> Operating Yoltage Range2 8 to 17.5 V{12 V nominal)or 16 to 33 V(24 V nominal) <br /> Input Terminai Wtre Gauge 12 to 18 AWG <br /> Wall-Mount Dimensions(including lens) 5.6"L x 4 7"W x 2.5"D(142 mm L x 119 mm W x 64 mm D) <br /> Hom Dimensions 5.6"L x 4.7"W x 1.3"D(142 mm L x 119 mm W x 33 mm D) <br /> Wail-Mount Back Box Skirt Dimensions(BBS-2,BBSW 2) 5.9"L x 5.0"W x 2.2"D(151 mm L x'128 mm W x 56 mm D) <br /> Wall-Mount Trim Ring Dimenslons(sold as a 5 pack){TR-HS,TRW- 5.7"L x 4.8`W x 0.35"D(145 mm L x 122 mm W x 9 mm D) <br /> Hs) <br /> Notes: <br /> 1 Full Wave Rectified(FWR)voltage is a non-regulated,time-varying power source that is used on some power supply and panel outputs. <br /> 2.P,S,PC,and SC products will operate at 12 V nominal only for 15 and 15/75 cd. <br /> AVDS00601 <br />
The URL can be used to link to this page
Your browser does not support the video tag.