<br /> Tota/Building Summary Loads -�
<br /> 1 D-hv-o:Glazing-Double pane,operable window, heat- 380 0 0 14,664 14,664
<br /> absorbing,vinyl frame, u-value 0.57, SHGC 0.44
<br /> 11 F: Door-Wood -Solid Core With Metal Storm 21 p � 182 182
<br /> 13A6-Ofcs:Wall-Block, no blanket or board insulation, 1039 0 0 4,260 4,260
<br /> filled core, siding finish
<br /> 16A-15: Roof/Ceiling-Under Attic with Insulation on Attic 1391.9 0 0 6,368 6,368
<br /> Floor(also use for Knee Walls and Partition Ceilings),
<br /> Unvented Attic, No Radiant Barrier, Any Roofing
<br /> Material,Any Roof Color, R-15 insulation
<br /> 22C-5rl-t: Floor-Slab on grade, Horizontal board 144 0 i� 0 0
<br /> insulation e�ends 4'under slab,tile covering, R-5
<br /> insulation, radiant, light dry soil
<br /> Subtotals for structure: 0 0 25,474 25,474
<br /> People: 2 400 460 860
<br /> Equipment: (l 1,200 1,200
<br /> Lighting: 0 0 0
<br /> Ductwork: 0 657 2,951 3,608
<br /> Infiltration:Winter CFM:0, Summer CFM:64 0 2,019 1,408 3,427
<br /> Ventilation:Winter CFM:0, Summer CFM:0 0 0 0 0
<br /> AED Excursion: 0 0 1,048 1,048
<br /> Total Building Load Totals: 0 3,076 32,542 35,618
<br /> Total Building Supply CFM: 1,480 CFM Per Square ft.: 1.063 '
<br /> Square ft. of Room Area: 1,392 Square ft. Per Ton: 469
<br /> Volume (ft3) of Cond. Space:(clg.) 16,703
<br /> ' Based on area of rooms being heated or cooled (whichever governs system) rather than entire floor area.
<br /> Total Sensible Gain: 32,542 Btuh g1 %
<br /> Total Latent Gain: 3,076 Btuh g %
<br /> Total Cooling Required Including Ventilation Air: 35,618 Btuh 2.97 Tons (Based On Sensible+ Latent)
<br /> Rhvac is an ACCA approved Manual J and Manual D computer program.
<br /> Calculations are performed per ACCA Manual J 8th Edition, Version 2,and ACCA Manual D.
<br /> All computed results are estimates as building use and weather may vary.
<br /> Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
<br /> your design conditions.