Laserfiche WebLink
' • - • . - • � - � - <br /> AED Graph <br /> �0000 <br /> 15000 <br /> q 10000 <br /> � <br /> 5000 <br /> 0 <br /> Sam 9am l0am llam 12pm lpm 2pm 3pm 4pm Spm 6pm 7pm 8pm <br /> — Hourly Loads —Average <br /> � � � � � • <br /> System equipment selectio�will be made using the following derived values <br /> Glass (E) 151 sq. ft. <br /> Glass (S) 21 sq. ft. <br /> Glass (N) 21 sq. ft. <br /> Glass (W) 106 sq. ft. <br /> Summer Outdoor g1�F <br /> Summer Wet Bulb 77°F <br /> Summer Indoor �5�F <br /> Summer Design Grains 50% <br /> Winter Outdoor 40°F <br /> Winter Indoor �poF <br /> Sensible Cooling 35,585 Btuh <br /> Latent Cooling 7 090 Btuh <br /> , <br /> Required Cooling Airflow 1 617 CFM <br /> . <br /> Sensible Heating 29,315 Btuh <br /> Required Heating Airflow 381 CFM <br /> All calculatians are based upon approved hvac industry standards and procedures,and comply with all local, <br /> state and federal code requirements.All computed results are Estimates.Product provided by Energy Design <br /> Systems and Idea Tree <br />