SECTIONS IV - SYSTEM DESIGN <br /> ■Ul.EX3470 ULC EX3470 Page 4-46 <br /> REV.6 7-1-U9 <br /> OVERLAPPING NO2ZLE COVERAGE{Continued) 4. On protected appliances, all hazard surfaces locaked in a <br /> Overlapping Qppliance Nozzle and Hazard 2one locations- 9roup must be within 40-45 in.(1-1.1 m)from the nozzle(s). <br /> Group Protectian(Continued) Once that dimension is exceeded,a new group must be start- <br /> ► ed.See Figure 99. <br /> 2. When obstructions are located adjacent to app6ance(s) pro- <br /> tected by over3apping nozzles,the overfapping appliance noz- Note:The supply pipe feeding nozzle groups is to be at ihe <br /> zle spacing must start with the appliance(s) adjacent to the same elevation.Adjust height for each graup oniy by varying <br /> . obstruction.See Figure 97. IengEhs of nozzle drops. <br /> 25.5 IN 25.5 IN. 25.5 IN. 25.5 IN. � 11.5 SN.(28.2 em) <br /> ► 71.5 IN. (gq.8 cm) (84.8 cm) (64.8 cm) (64.8 cm)I MAXIMUM <br /> ► (292 cm) _� 11.5 IN. <br /> MAX. + MAX. + MAX. MAX. + MAX ,� (2g2 cm) � <br /> 245 26D 280 280 245 M�� � � � 1 i I` � END OF <br /> � � I f � I/�ZONE <br /> ! NOZZLES f <br /> OUTSIDE � � � NOZZLES <br /> � EDGE OF � I ao iN. i � <br /> COOKING 45IN. � ��.0 m) � <br /> Hn7AR� (>>m� END OF � aD ItJ. � <br /> ZON£ ^-� (1.0 m) 45 ItJ. <br /> I ' � 1 � (1.1 m) <br /> t r I� <br /> � �---HAZARD AREA-�----►I <br /> O6S7RUCTION <br /> NOTE;On continuous appliance protactbn,slart and end with 245 <br /> nozzles and 260 nozzle(5)in lhe midale. <br /> � FIGURE 97 �--GHOUP'A'--►�+-GROUP`B'---r� <br /> 001)53 <br /> N07E:On group appGance proteclion,stazt antl end of EACH zone <br /> 3. When an appliance requires dedicated protection with a pro- y,o�P mus�ne P�oc�ciea wun a zas�ouie. <br /> tected area intended for overlapping appliance nozzie protec- , <br /> tion,the group protection opEion will be required for appliances FIGURE 99 <br /> ��� <br /> on either side of the appliances using dedicated protection. <br /> Group protection using overlapping appliance nozzies must petectton Requirements For Overtapping Appllance <br /> begin with the protected appliance(s)adjacent to the dedtcat- protection <br /> ed appllance protected. An overlapping appliance nozzle(s) y�hen utillzing overlapping appliance protection,fusible link detec- <br /> ► must be positioned within 11.5 in.(29.2 cm)of the edge(s)of tors must be installed on a maximum of 2 fl (O.6i m) centers, <br /> the appliance hazard surface area(s)adJacent to the dedicat- starting wilh detectors locafed in(under}the duct opening(s). <br /> ► ed nozzle protection.See Figure 98. <br /> Starting from the detector under the duct opening,add detectors <br /> on 2 it(0.61 m)maxlmum spacing until the complete length of the <br /> plenum area is covered,from one enc!to the other.The bcation of <br /> the last detector on each end of the plenum must not exceed <br /> EDGE OF COOKtNG 2 ft(0.61 m)irom end of plenum. <br /> HAZARD <br /> � Note: Standard detector placement can also be utitized when <br /> i zs.s�w.i y using overlapping proiection. However, Ehe overlapping detector <br /> 11.5 IN. r 25_5 IN. 25.5 IN.t o tion cannot be used when utilfzEn standard R-102 rotection. <br /> ► (292 cm)-► (64.6 cm) (64.8 cm)(fi4.8 an) i 1.5 IN. P 9 P <br /> MAX. MAX. � � MAX MAX. 1282 cm) ►Refer to Pages 4-57 and 4-58 for detector placement. <br /> MAX. <br /> � HDGE� 11.51N. 1S.5IN.(292 cm) EDGE <br /> OOOKING {292 cm�MAX. MAXtMUM OF <br /> CAOKING <br /> HAZARD HAZARD <br /> QEDICATE�NOZZLE <br /> APPLIANCE <br /> NOTE:On group appliance pro�ection,slan and end of EACH zone <br /> � group m�st be protected wiih a 2as nozzle. FIGURE 98 <br /> ooi�sc <br />