File area 1 ti�e Page 1 of 1 <br /> Hydraulic Summary <br /> WATER SUPPLY iNFORMATiON <br /> Static (psi) 50 00 <br /> Residuai (psi) 40 00 <br /> @ (gpm) 2,550 00 <br /> Hose (gpm) 100 00 <br /> System req (gpm) 232 19 <br /> @ (psi} 24 20 <br /> Supply available 49 88 psi <br /> Safety margin 25 69 psi <br /> Maximum velocity in the system is 10 73 ft/sec in the pipe between Nodes 17 and 11 <br /> Continuity at all nodes satisfied to 0 01 gpm <br /> Pipe Type Legend Fitting Type Legend <br /> 40 = Schedule 40 EE =45 degree elbow <br /> DF =Allied Dyna-Flow/Super Flo E = 90 degree standard elbow <br /> B2 = Blue Brute PVC Class 200 T = Tee (flow turned 90 degrees <br /> D2 = Ductile Iron Class 52 BV = ButterFly valve <br /> GV = Gate valve <br /> NOTES <br /> 06/06/13 "THE" Sprinkler Program 2001 <br />