Laserfiche WebLink
` - s . - • � - i - <br /> AED Graph <br /> 30000 <br /> 20000 <br /> r <br /> 10000 <br /> D <br /> 8am 9am 10am llam 12pm lpm 2pm 3pm 4pm Spm 6pm 7pm 8pm <br /> — Hourly Loads — Average <br /> � � � � � ` <br /> System equipment selection wiil be made using the foliowing derived values <br /> Glass (E) 152 sq. ft. <br /> Glass (5) 21 sq. ft. <br /> Glass (N) 21 sq. ft. <br /> Glass (W) 107 sq. ft. <br /> Summer Outdoor 91°F <br /> Summer Wet Bulb 77°F <br /> Summer Indoor 75°F <br /> Summer Design Grains 50% <br /> Winter Outdoor .�p�F <br /> Winter indoor 70�F <br /> Sensible Cooling 40,251 Btuh <br /> Latent Cooling 7,153 Btuh <br /> Req ui red Cool i n g Ai rfl ow l,830 CF M <br /> Sensible Heating 26,119 Btuh <br /> Required Heating Airfiow 339 CFM <br /> AI!calcufations are based upon approved hvac industry standards and proc2dures,and comply with all local, <br /> state and fed�ral code reguirements.All computed resul� are Estimates Product provided by Energy Design <br /> Sy�stems and Id=_a T,�e <br />