Laserfiche WebLink
� • • • . - • • � � � <br /> AED Graph <br /> 15000 <br /> 10000 <br /> � \\ <br /> O <br /> � <br /> 5000 <br /> 0 <br /> 8am 9am l0am llam 12pm lpm 2pm 3pm 4pm Spm 6pm 7pm 8pm <br /> — Hourly Loads —Average <br /> � � � � � � <br /> System equiprnent selectio�will be made using the following derived values <br /> Glass (E) 88 sq. ft. <br /> Glass (5) 12 sq. ft. <br /> Glass (N) 12 sq. ft. <br /> Glass (W) 62 sq. ft. <br /> Summer Outdoor 91°F <br /> Summer Wet Bulb 77°F <br /> Summer Indoor 75°F <br /> Summer Design Grains 50% <br /> Winter Outdoor 40°F <br /> Winter Indoor 70°F <br /> Sensible Cooling 21,723 Btuh <br /> Latent Cooling 4,336 Btuh <br /> Required Cooling Airflow 987 CFM <br /> Sensible Heating 18,191 Btuh <br /> Required Heating Airflow 236 CFM <br /> AU talculations are based upon approved hvac industry standards and procedures,and comply with all Iocal, <br /> state and feder�l code requirements All computed results are Estimates Product provided by Energy De�sign <br /> Systems and Id�ea Tree <br />