<br /> iC-cm:Glazing-Single pane windowwith storm, clear, 176 0 0 13,185 13,185
<br /> metal frame no break, u-value 0.87, SHGC 0.67
<br /> 11 F: Door-Wood-Solid Core With Metal Storm 21 0 0 182 182
<br /> 13AB-Ofcs:Wall-Block, no blanket or board insulation, 955 0 0 3,914 3,914
<br /> filled core,siding finish
<br /> 16A-13: Roof/Ceiling-Under Attic with Insulation on Attic 1134 0 0 5,954 5,954
<br /> Floor(also use for Knee Walls and Partition Ceilings),
<br /> Unvented Attic, No Radiant Barrier,Any Roofing
<br /> Material,Any Roof Color, R-13 insulation
<br /> FLOOR ON SLAB: Floor-Over open crawl space or 1134 0 0 561 561
<br /> garage,Custom, FLOOR ON THE SLAB
<br /> Subtotals for structure: 0 0 23,796 23,796
<br /> People: 2 400 460 860
<br /> Equipment: 0 1,200 1,200
<br /> Lighting. 215 733 733
<br /> Ductwork. 0 727 2,996 3,723
<br /> Infiltration:Winter CFM:0, Summer CFM:0 0 0 0 0
<br /> Ventilation:Winter CFM:0, Summer CFM:215 0 6,781 4,727 11,508
<br /> System 1 System 1 Load Totals: 0 7,908 33,912 41,820
<br /> a ..: .
<br /> Supply CFM: 1,327 CFM Per Square ft.: 1.171 `
<br /> Square ft. of Room Area: 1,134 Square ft. Per Ton: 325
<br /> Volume(ft3) of Cond. Space: (clg.) 9,072
<br /> ` Based on area of rooms being heated or cooled (whichever governs system) rather than entire floor area.
<br /> i � �.Pi'= a' . .
<br /> Total Sensible Gain• 33,912 Btuh 81 %
<br /> Total Latent Gain• 7,908 Btuh 19 %
<br /> Total Cooling Required Including Ventilation Air: 41,820 Btuh 3.48 Tons(Based On Sensible+ Latent)
<br /> . ..
<br /> Rhvac is an ACCA approved Manual J and Manual D computer program.
<br /> Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
<br /> All computed results are estimates as building use and weather may vary.
<br /> Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
<br /> your design conditions.
<br /> C:\Users�.laosn\Desktop\ELITE�ACEVEDO.rhv Monday,August 26,2013, 11:53 AM