Laserfiche WebLink
� Qa� NOTIFIER� . � . . � <br /> by Honeywell <br /> NFW2-100 Fire Alarm Control Panel <br /> Protected Premises: Zephyrhills Dialisys Date: 7/31/2013 <br /> Address: <br /> City: State: Zip• <br /> Prepared By MC Phone: <br /> Address: Email: <br /> City: State: Zip: <br /> AC Branch Current Requirements 20.00 AMPS @ 120 VAC <br /> Current required by source to power the fire <br /> alarm system. <br /> Primary Standby Load 0.05 Amps <br /> Current load on the primary power supply during <br /> non-alarm conditions. <br /> Primary Alarm Load 5.08 Amps <br /> Current load on the primary power supply during <br /> alarm conditions. <br /> Secondary Load Requirements 5.42 Amp Hours <br /> Total Secondary Load from the calculation table below. <br /> � . , . <br /> Secondary Standby Load Re uired Standb Time <br /> 0.169 A x 24 hours 4.06 <br /> Secondary Alarm Load R uired Alarm Time hours <br /> 5.355 A X <br /> 0.084 hours 0.45 <br /> Total Secondary Load 4.51 <br /> Derating factor x 1.2 <br /> Secondary Load Requirements 5.42 AH <br /> Battery Selection 12 Amp Hours <br /> Select batteries from the list below. <br /> 12 AH BAT-12120 Batte 12 voft <br /> �Two �Four(iwo 12VDC sets in parallel) <br /> Page 1 of 2 <br />