10. MINIMUM WIRE SIZE SHALL BE #12 AWG, EXCLUDING CONTROL WIRING. UNLE55 OTHERWISE NOTED, <br />CONDUCTORS SHALL BE COPPER WITH THWN/THHN INSULATION. CONDUCTORS #12 AND SMALLER <br />MAY BE SOLID; ALL THOSE #10 AND LARGER TO BE STRANDED. <br />II. ALL UNDERGROUND RAGEWAY5 SHALL BE GALVANIZED RIGID STEEL CONDUIT OR SCHEDULE 40 <br />PVC. ALL OTHER RAGEWAY5 TO COMPLY WITH GOVERNING CODES. MINIMUM CONDUIT <br />UNDERGROUND SHALL BE 3/4" CONDUIT UNLESS OTHERWI5E NOTED. <br />12. OUTLET 'BOXE5 SHALL BE PRE55ED STEEL IN DRY LOCATIONS, CAST ALLOY WITH THREADED <br />HUB5 IN WET OR DAMP LOCATIONS, AND BE OF SPECIAL CONSTRUCTION FOR OTHER GLA551FIED <br />AREAS. ALL BOXES SHALL BE RECESSED (FLUSH) IN WALLS OR CEILING5 WHENEVER POSSIBLE. <br />13. DISCONNECT SWITCHES SHALL BE H.P. RATED, GENERAL DUTY, QUICK -MAKE, QUICK -BREAK TYPE, <br />ENCLOSURES SHALL BE AS REQUIRED BY N,E.G. AND LOCATION (WEATHERPROOF, EXPLOSION - <br />PROOF, ETC.). <br />14. ALL GENERAL PURPOSE SWITCHES AND RECEPTACLES SHALL BE THE PRODUCT OF A SINGLE <br />MANUFACTURER. LEVITON, HUBBELL, PASS d SEYMOUR, OR ARROW HART WILL BE ACCEPTED. <br />DEVICE TYPES AND COLOR SHALL MATCH BUILDING STANDARD. <br />15. ALL RACEWAYS AND PIPES, SPACED IN OR THROUGH ANY CONCRETE SLAB, SHALL BE 5PAGED <br />A MINIMUM OF THREE TIMES THE DIAMETER OF THE LARGEST RAGEWAY. <br />16. IT 15 NOT THE INTENT OF THESE PLANS TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION. THE <br />GONTRAGTOR IS EXPECTED TO FURNI5H AND INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL <br />SYSTEM, AND PROVIDE ALL NEGE55ARY DEVICES AND COMPONENTS FOR EQUIPMENT TO BE <br />PLACED IN PROPER WORKING ORDER, <br />17. ALL ELECTRICAL RAGEWAY5 (METALLIC AND NONMETALLIC) SHALL HAVE AN EQUIPMENT <br />GROUND CONDUCTOR 51ZED IN ACCORDANCE WITH THE LATEST EDITION OF THE N.E.G. <br />15. LOAD DATA 15 BASED ON INFORMATION GIVEN ENGINEER AT THE TIME OF DESIGN. VERIFY ALL <br />EQUIPMENT NAMEPLATE RATINGS BEFORE ORDERING. <br />Iq. CIRCUITS SHOWN ON PLANS ARE TO DETERMINE LOAD UATA AND PANEL SIZES. THE <br />GONTRACTOR IS TO PROVIDE CIRCUITS AND ROUTING OF CONDUITS TO SUIT JOB CONDITIONS. <br />20. TANDEM AND HALF -SPACE CIRCUIT BREAKERS SHALL NOT BE USED. <br />21. ALL UNDERGROUND PVG CONDUIT RUNS SHALL HAVE RiO19 STEEL ELBOW5 AND RIGID STEEL <br />SECTIONS AT SLAB PENETRATIONS. WHERE RIGID STEEL 6 USED, IT SHALL BE COMPLETELY <br />COATED WITH AN ALKALI AND RUST - RESISTANT BITUMA5TIG PAINT, AND THREADS SHALL BE <br />COATED WITH ZING CHROMATE. <br />22. ALL ELECTRICAL CONDUCTORS SHALL BE INSTALLED IN AN APPROVED RACEWAY. <br />23. CONTRACTOR SHALL BE RESPONSIBLE FOR SEALING ALL CONDUIT PENETRATIONS MADE <br />THROUGH FIRE RATED WALLS, CEILINGS, 5LAB5, ETC. PENETRATION SEALS SHALL Be PER U.L. <br />ASSEMBLY STANDARDS. <br />24. CONDUIT SYSTEM REQUIREMENTS: <br />UNDERGROUND - PVG WITH RIGID qO THROUGH SLAB. <br />ABOVE FIN15H FLOOR, CEILINGS, ETC. (INDOOR) - EMT WITH DIECA5T SET 5CREW FITTINGS. <br />GALVANIZED RIGID CONDUITS - ABOVE GRADE AND WHERE SUSCEPTIBLE TO PHYSICAL <br />DAMAGE. <br />FLEXIBLE CONDUITS - INDOOR, ONLY SHORT RUNS NOT TO EXCEED 6-0 ". <br />5EALTITE - OUTDOOR, ONLY SHORT RUNS NOT TO EXCEED 6-0 ". <br />25. CONDUCTOR COLOR CODING: <br />THE FOLLOWING APPLICABLE COLOR CODES SHALL BE IMPLEMENTED AND P05TED IN ALL <br />PANELS, DISCONNECT 5WITGHE5, ETC., PER NEC ARTICLEE5 200.6(D) AND 215.12: <br />120 1205\1., 3 -PH. <br />PHASE 'A' BLACK <br />PHASE 'B' RED <br />PHASE 'G' BLUE <br />NEUTRAL WHITE <br />GROUND GREEN <br />ISOL. GROUND GREEN/YELLOW <br />+ MG GABLE: METAL -GLAD GABLE <br />• FOR ALL CIRCUITS; GABLE SHALL BE 'HEALTH GARS <br />FACILITY METAL GLAD GABLE' TYPE (HGF) ONLY, IN <br />COMPLIANCE WITH NEG 51-7.13 (A)(B). <br />• FOR ALL LIGHTING CIRCUITS ABOVE 8'-0" ONLY; <br />GABLE MAY BE 'METAL GLAD GABLE' TYPE (MG). <br />• HOME RUNS SHALL REMAIN IN CONDUITS. <br />• MG GABLE MAY BE USED FOR 20 AMP CIRCUITS IN <br />WALLS OR ABOVE AGGE551BLE CEILINGS. <br />• FOR ALL LIGHTING CONTROL SWITCHES, GABLE <br />SHALL BE 'HEALTH CARE FACILITY METAL GLAD <br />GABLE' TYPE (HGF) ONLY, IN COMPLIANCE WITH NEG <br />51 -7.13 (A)(B). <br />Ng E3 <br />• MG GABLE WIRE 0AUGE5 SHALL BE AS 5HOWN ON <br />PANEL SCHEDULE. <br />• MG GABLE SHALL ONLY BE USED WHERE ALLOWED <br />BY N.E.G. 5EGTION 330.10 AND /OR AS 5HOWN <br />ABOVE, WHIGHEVER IS MORE STRINGENT. <br />• WHERE ALLOWED, MG GABLE SHALL BE INSTALLED <br />PER N.E.G. 330. <br />• MG GABLE MAY NOT BE U5ED IN OPEN STRUCTURE <br />AREA. <br />Na3A <br />DEMOLITION NOTE5 <br />v <br />5PEG I F I GAT I ON5 <br />L <br />I. <br />ALL WORK SHALL BE IN 5TRICT ACCORDANCE WITH THE LATEST EDITION OF THE NATIONAL <br />COORDINATE WITH THE GENERAL CONTRACTOR ON SITE TO THE <br />N <br />ELECTRICAL CODE (N.E.G.) AND ALL LOCAL GODE5 AND ORDINANCES. <br />E <br />2. <br />ALL MATERIALS SHALL BE NEW AND OF DOMESTIC ORIGIN AND SHALL BEAR UNDERWRITERS' <br />G <br />L <br />LABEL WHERE APPLICABLE. <br />T <br />3. <br />ALL WORK SHALL BE PERFORMED BY A LICENSED ELEGTRIGAL CONTRACTOR IN A FIRST -CLASS <br />2. ELECTRICAL DEMOLITION WORK SHALL INCLUDE, MT NOT BE LIMITED TO, <br />A <br />WORKMANLIKE MANNER. THE COMPLETED SYSTEM 15 TO BE FULLY OPERABLE AND <br />L <br />INSTALLATION OF NEW EQUIPMENT AS INDICATED ON THE PLANS. <br />ACCEPTANCE OF TH15 SYSTEM BY THE ENGINEER/ARCHITECT MUST BE A CONDITION OF THE SUB <br />3. CONTRACTOR SHALL REMOVE ANY EXPOSED WIRE, CONDUIT, HANGERS, <br />FLUORESCENT L16HT FIXTURE, LETTER INDICATE-5 TYPE <br />GONTRAGT, <br />MAIN 5WITGH113OARD <br />4. <br />ALL WORK TO BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE WITH THE <br />G <br />MDP <br />PROGRE55 OF CONSTRUCTION. <br />T <br />5. <br />CONTRACTOR TO GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM DEFECTS FOR A <br />5. REV15E ALL EX15TINO PANEL DIRECTORIES TO REFLECT ALL REVI5ION5. <br />KEYNOTES <br />PERIOD OF NOT LE55 THAN ONE (1) YEAR FROM DATE OF ACCEPTANCE. <br />L. <br />6. <br />CORRECTION OF ANY DEFECTS TO BE COMPLETED WITHOUT ADDITIONAL CHARGE AND TO <br />CONSTRUCTION. VERIFY SPECIFIC LOCATIONS WITH OWNER'S AUTHORIZED <br />Q <br />INCLUDE REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHIGH MAY <br />EXIT L164T (ARROW INDICATES DIRECTION) <br />-7. ALL WORK SHALL BE PERFORMED DURING TIME PERIOD5 ACCEPTABLE <br />HAVE BEEN DAMAGED THEREBY. <br />TO THE OWNER. SCHEDULE ALL WORK WITH THE OIWNER'5 AUTHORIZED <br />T <br />ALL REQUIRED INSURANCE TO BE PROVIDED FOR PROTECTION AGAINST PUBLIC LIABILITY OF <br />8. CONTRACTOR SHALL V151T THE JOB 51TE AND BE 'THOROUGHLY FAMILIAR <br />PROPERTY DAMAGE FOR THE DURATION OF THE WORK. <br />WITH EXISTING CONDITIONS UNDER WHIGH THE WORK MUST BE PERFORMED. <br />5. <br />CONTRACTOR TO PAY FOR ALL PERMITS, FEES, INSPECTIONS AND TESTING. <br />CONDUCTORS AS SHOWN ON PANEL SCHEDULE U.D. <br />.N <br />q. <br />ELECTRICAL INSTALLATION TO MEET ALL STANDARD REQUIREMENTS OF LOCAL POWER AND <br />TRACK LIGHTING <br />4 <br />TELEPHONE COMPANIES. <br />10. MINIMUM WIRE SIZE SHALL BE #12 AWG, EXCLUDING CONTROL WIRING. UNLE55 OTHERWISE NOTED, <br />CONDUCTORS SHALL BE COPPER WITH THWN/THHN INSULATION. CONDUCTORS #12 AND SMALLER <br />MAY BE SOLID; ALL THOSE #10 AND LARGER TO BE STRANDED. <br />II. ALL UNDERGROUND RAGEWAY5 SHALL BE GALVANIZED RIGID STEEL CONDUIT OR SCHEDULE 40 <br />PVC. ALL OTHER RAGEWAY5 TO COMPLY WITH GOVERNING CODES. MINIMUM CONDUIT <br />UNDERGROUND SHALL BE 3/4" CONDUIT UNLESS OTHERWI5E NOTED. <br />12. OUTLET 'BOXE5 SHALL BE PRE55ED STEEL IN DRY LOCATIONS, CAST ALLOY WITH THREADED <br />HUB5 IN WET OR DAMP LOCATIONS, AND BE OF SPECIAL CONSTRUCTION FOR OTHER GLA551FIED <br />AREAS. ALL BOXES SHALL BE RECESSED (FLUSH) IN WALLS OR CEILING5 WHENEVER POSSIBLE. <br />13. DISCONNECT SWITCHES SHALL BE H.P. RATED, GENERAL DUTY, QUICK -MAKE, QUICK -BREAK TYPE, <br />ENCLOSURES SHALL BE AS REQUIRED BY N,E.G. AND LOCATION (WEATHERPROOF, EXPLOSION - <br />PROOF, ETC.). <br />14. ALL GENERAL PURPOSE SWITCHES AND RECEPTACLES SHALL BE THE PRODUCT OF A SINGLE <br />MANUFACTURER. LEVITON, HUBBELL, PASS d SEYMOUR, OR ARROW HART WILL BE ACCEPTED. <br />DEVICE TYPES AND COLOR SHALL MATCH BUILDING STANDARD. <br />15. ALL RACEWAYS AND PIPES, SPACED IN OR THROUGH ANY CONCRETE SLAB, SHALL BE 5PAGED <br />A MINIMUM OF THREE TIMES THE DIAMETER OF THE LARGEST RAGEWAY. <br />16. IT 15 NOT THE INTENT OF THESE PLANS TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION. THE <br />GONTRAGTOR IS EXPECTED TO FURNI5H AND INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL <br />SYSTEM, AND PROVIDE ALL NEGE55ARY DEVICES AND COMPONENTS FOR EQUIPMENT TO BE <br />PLACED IN PROPER WORKING ORDER, <br />17. ALL ELECTRICAL RAGEWAY5 (METALLIC AND NONMETALLIC) SHALL HAVE AN EQUIPMENT <br />GROUND CONDUCTOR 51ZED IN ACCORDANCE WITH THE LATEST EDITION OF THE N.E.G. <br />15. LOAD DATA 15 BASED ON INFORMATION GIVEN ENGINEER AT THE TIME OF DESIGN. VERIFY ALL <br />EQUIPMENT NAMEPLATE RATINGS BEFORE ORDERING. <br />Iq. CIRCUITS SHOWN ON PLANS ARE TO DETERMINE LOAD UATA AND PANEL SIZES. THE <br />GONTRACTOR IS TO PROVIDE CIRCUITS AND ROUTING OF CONDUITS TO SUIT JOB CONDITIONS. <br />20. TANDEM AND HALF -SPACE CIRCUIT BREAKERS SHALL NOT BE USED. <br />21. ALL UNDERGROUND PVG CONDUIT RUNS SHALL HAVE RiO19 STEEL ELBOW5 AND RIGID STEEL <br />SECTIONS AT SLAB PENETRATIONS. WHERE RIGID STEEL 6 USED, IT SHALL BE COMPLETELY <br />COATED WITH AN ALKALI AND RUST - RESISTANT BITUMA5TIG PAINT, AND THREADS SHALL BE <br />COATED WITH ZING CHROMATE. <br />22. ALL ELECTRICAL CONDUCTORS SHALL BE INSTALLED IN AN APPROVED RACEWAY. <br />23. CONTRACTOR SHALL BE RESPONSIBLE FOR SEALING ALL CONDUIT PENETRATIONS MADE <br />THROUGH FIRE RATED WALLS, CEILINGS, 5LAB5, ETC. PENETRATION SEALS SHALL Be PER U.L. <br />ASSEMBLY STANDARDS. <br />24. CONDUIT SYSTEM REQUIREMENTS: <br />UNDERGROUND - PVG WITH RIGID qO THROUGH SLAB. <br />ABOVE FIN15H FLOOR, CEILINGS, ETC. (INDOOR) - EMT WITH DIECA5T SET 5CREW FITTINGS. <br />GALVANIZED RIGID CONDUITS - ABOVE GRADE AND WHERE SUSCEPTIBLE TO PHYSICAL <br />DAMAGE. <br />FLEXIBLE CONDUITS - INDOOR, ONLY SHORT RUNS NOT TO EXCEED 6-0 ". <br />5EALTITE - OUTDOOR, ONLY SHORT RUNS NOT TO EXCEED 6-0 ". <br />25. CONDUCTOR COLOR CODING: <br />THE FOLLOWING APPLICABLE COLOR CODES SHALL BE IMPLEMENTED AND P05TED IN ALL <br />PANELS, DISCONNECT 5WITGHE5, ETC., PER NEC ARTICLEE5 200.6(D) AND 215.12: <br />120 1205\1., 3 -PH. <br />PHASE 'A' BLACK <br />PHASE 'B' RED <br />PHASE 'G' BLUE <br />NEUTRAL WHITE <br />GROUND GREEN <br />ISOL. GROUND GREEN/YELLOW <br />+ MG GABLE: METAL -GLAD GABLE <br />• FOR ALL CIRCUITS; GABLE SHALL BE 'HEALTH GARS <br />FACILITY METAL GLAD GABLE' TYPE (HGF) ONLY, IN <br />COMPLIANCE WITH NEG 51-7.13 (A)(B). <br />• FOR ALL LIGHTING CIRCUITS ABOVE 8'-0" ONLY; <br />GABLE MAY BE 'METAL GLAD GABLE' TYPE (MG). <br />• HOME RUNS SHALL REMAIN IN CONDUITS. <br />• MG GABLE MAY BE USED FOR 20 AMP CIRCUITS IN <br />WALLS OR ABOVE AGGE551BLE CEILINGS. <br />• FOR ALL LIGHTING CONTROL SWITCHES, GABLE <br />SHALL BE 'HEALTH CARE FACILITY METAL GLAD <br />GABLE' TYPE (HGF) ONLY, IN COMPLIANCE WITH NEG <br />51 -7.13 (A)(B). <br />Ng E3 <br />• MG GABLE WIRE 0AUGE5 SHALL BE AS 5HOWN ON <br />PANEL SCHEDULE. <br />• MG GABLE SHALL ONLY BE USED WHERE ALLOWED <br />BY N.E.G. 5EGTION 330.10 AND /OR AS 5HOWN <br />ABOVE, WHIGHEVER IS MORE STRINGENT. <br />• WHERE ALLOWED, MG GABLE SHALL BE INSTALLED <br />PER N.E.G. 330. <br />• MG GABLE MAY NOT BE U5ED IN OPEN STRUCTURE <br />AREA. <br />Na3A <br />DEMOLITION NOTE5 <br />v <br />I, ELECTRICAL PLANS DO NOT INCLUDE A DEMOLITION PLAN FOR THE <br />L <br />RENOVATED AREAS. CONTRACTOR SHALL REVIEW THESE PLANS AND <br />E <br />COORDINATE WITH THE GENERAL CONTRACTOR ON SITE TO THE <br />N <br />DETERMINE THE EXTENT OF THE DEMOLITION WORK AND PROJECT <br />N <br />PHASING REQUIRED AND PROVIDE ACCORDINGLY. ALL ELECTRICAL <br />REVIEW <br />DEMOLITION WORK SHALL BE PART OF THE ELECTRICAL <br />L <br />CONTRACTOR'S WORK. <br />ALTERED WITHOUT WRITTEN AUTHORIZATION. <br />WIRING DEVICES. <br />ITEMS WHIGH APPLY TO TH15 PROJECT. <br />2. ELECTRICAL DEMOLITION WORK SHALL INCLUDE, MT NOT BE LIMITED TO, <br />A <br />REMOVING, RECEPTACLES, WIRE, CONDUIT, ETC., AS REQUIRED FOR THE <br />L <br />INSTALLATION OF NEW EQUIPMENT AS INDICATED ON THE PLANS. <br />L <br />3. CONTRACTOR SHALL REMOVE ANY EXPOSED WIRE, CONDUIT, HANGERS, <br />FLUORESCENT L16HT FIXTURE, LETTER INDICATE-5 TYPE <br />CLAMPS, ETC., WHIGH ARE NOT BEING UTILIZED FOIR THE NEW <br />MAIN 5WITGH113OARD <br />INSTALLATION. <br />Og <br />4. EXISTING WIRE AND CONDUITS CONGEALED ABOVE: CEILING OR IN WALL5 <br />MDP <br />AND NOT BEING REUSED SHALL BE REMOVED. EX15TINO CONDUITS, <br />T <br />WHERE APPLICABLE, MAY BE REUSED. <br />WALL BRACKET LIGHT FIXTURE, LETTER INDICATES TYPE <br />5. REV15E ALL EX15TINO PANEL DIRECTORIES TO REFLECT ALL REVI5ION5. <br />KEYNOTES <br />6. THE CONTRACTOR SHALL PROVIDE RUBBER MATS AND PLYWOOD <br />® ®NL <br />COVERS TO ALL OWNER'S EQUIPMENT 505CEPTI13LE TO DAMAGE DURING <br />CONSTRUCTION. VERIFY SPECIFIC LOCATIONS WITH OWNER'S AUTHORIZED <br />Q <br />REPRESENTATIVE. <br />EXIT L164T (ARROW INDICATES DIRECTION) <br />-7. ALL WORK SHALL BE PERFORMED DURING TIME PERIOD5 ACCEPTABLE <br />AS SHOWN ON PANEL 56HEDULE. U.O.N. <br />TO THE OWNER. SCHEDULE ALL WORK WITH THE OIWNER'5 AUTHORIZED <br />O <br />REPRESENTATIVE 48 HOURS BEFORE PROGEEDINa. <br />8. CONTRACTOR SHALL V151T THE JOB 51TE AND BE 'THOROUGHLY FAMILIAR <br />G <br />WITH EXISTING CONDITIONS UNDER WHIGH THE WORK MUST BE PERFORMED. <br />J � <br />THESE NOTES APPLY TO ALL ELEGTRIGAL SHEETS. <br />N,5A <br />NOTE5 <br />v <br />LEO END <br />I6 <br />I. THE CONTRACTOR SHALL REMOVE ALL EXISTING WIRING AND EQUIPMENT <br />E <br />MADE UNNECESSARY BY THE RENOVATION. ALL MATERIALS REMOVED <br />MOUNTING HEIGHTS 5HOWN ARE MAXIMUM/MINIMUM <br />SHALL BE 015POSED OF BY THE CONTRACTOR. <br />N <br />AGGES5IBILITY 5TANDARD5 - THEY SHALL <br />REVIEW <br />2. CONTRACTOR SHALL VERIFY WITH VARIAN INSTALLER FOR COORDINATION <br />L <br />OF MOUNTING HEIGHT5 AND /OR LOCATIONS OF ALL NEW OUTLETS AND <br />ALTERED WITHOUT WRITTEN AUTHORIZATION. <br />WIRING DEVICES. <br />ITEMS WHIGH APPLY TO TH15 PROJECT. <br />E <br />A <br />3. ALL TELEPHONE/DATA JACKS AND GABLING TO BE PROVIDED AND <br />INSTALLED <br />BY OWNER'S VENDOR. <br />L <br />4. GROUND CONDUCTOR SHALL BE INSTALLED IN ENTIRE RAGEWAY SYSTEM. <br />FLUORESCENT L16HT FIXTURE, LETTER INDICATE-5 TYPE <br />5. REUSE EXISTING JUNCTION BOXES, CONDUIT AND WIRING WHERE <br />MAIN 5WITGH113OARD <br />APPLICABLE. REMOVE AND DISPOSE OF ALL UNUSED CONDUIT AND <br />Og <br />WIRING BACK TO ITS SOURCE. <br />MDP <br />(b. ELECTRICAL CONTRACTOR SHALL VERIFY AND 000)RDINATE ALL DEVICE <br />T <br />TYPE5, LOCATIONS AND QUANTITIES WITH VARIAN REPRESENTATIVE AND <br />WALL BRACKET LIGHT FIXTURE, LETTER INDICATES TYPE <br />PROVIDE ACCORDINGLY. <br />N24A <br />NOTE5 <br />G <br />IT IS THE CONTRACTOR'S RESPONSIBILITY TO REVIEW ALL DRANIN65 <br />O AND SPECIFICATIONS PRIOR TO 5UBMITTING A BID, REPORT ANY <br />N D156REPANGIE5 TO ENGINEER PRIOR TO BID, <br />BIDDERS ARE TO VISIT THE 51TE AND FAMILIARIZE THEM5ELVE5 WITH <br />T EXISTING CONDITIONS AND SATISFY THEM5ELVE5 AS TO THE NATURE AND <br />SCOPE OF THE WORK. THE SUBMISSION OF A BID WILL BE EVIDENCE THAT <br />R 5UGH AN EXAMINATION HAS BEEN MADE. LATER CLAIMS FOR LABOR, <br />AEQUIPMENT, OR MATERIALS REQUIRED, OR FOR ANY DIFFICULTIES <br />ENCOUNTERED WHIGH GOULD HAVE BEEN FORESEEN HAD AN EXAMINATION <br />G BEEN MADE, WILL NOT BE ALLOWED. <br />IT 15 THE RE5PON51BILITY OF THE CONTRACTOR TO NOTIFY THE ENGINEER <br />T OF ANY DISCREPANCIES ENCOUNTERED ON THE PLANS OR IN EX15TINO SITE <br />O GONDITIONS PRIOR TO 5013M15510N OF BID, <br />ALL EXISTING GIRGUIT5 TO REMAIN SHALL BE RECONNECTED WHETHER <br />INDICATED OR NOT ON PROJECT DOCUMENT5, <br />NEW AND EXISTING CIRCUIT DE5IGNATION5 MAY NOT REPRESENT ACTUAL <br />FIELD CONDITIONS. THEY ARE INTENDED FOR REFERENCE ONLY. <br />GONTRACTOR SHALL COORDINATE WITH OTHER TRADES IN REGARDS TO <br />THEIR 56OPE OF WORK WHIGH WILL REQUIRE ELEGTRIGAL WORK SUCH AS <br />DISCONNECTION AND /OR RECONNECTION OF EQUIPMENT, AND WHICH MAY <br />NOT BE 5HOWN OR INDICATED ON THE DRAWINGS. <br />THESE NOTES APPLY TO ALL ELECTRICAL 5HEI✓T5. <br />N3A <br />■ <br />® FLOOR MOUNTED TELEPHONE RECEPTACLE DEVICE AS NOTED <br />E..: TELEPHONE BACKBOARD WITH #6 U. GROUND (SIZE AS NOTED) <br />K <br />E6 <br />EQUIPMENT GROUND <br />LEO END <br />I6 <br />E <br />FJF -EF <br />NOT ALL DEVIGE5 5HOWN IN LEGEND ARE REQUIRED. <br />MOUNTING HEIGHTS 5HOWN ARE MAXIMUM/MINIMUM <br />L <br />HANDICAPPED <br />AGGES5IBILITY 5TANDARD5 - THEY SHALL <br />REVIEW <br />POWER 4 LIGHTING PLANS AND DETAILS <br />ELECTRIC WATER HEATER <br />NOT BE <br />ALTERED WITHOUT WRITTEN AUTHORIZATION. <br />FOR <br />ITEMS WHIGH APPLY TO TH15 PROJECT. <br />E <br />Of <br />® <br />FLUORESCENT L16HT FIXTURE, LETTER INDICATE-5 TYPE <br />M58 <br />MAIN 5WITGH113OARD <br />G <br />Og <br />INCANDESCENT OR HID LIGHT FIXTURE, LETTER INDICATES TYPE <br />MDP <br />MAIN D15TRIBUTION PANEL <br />T <br />I-O C, <br />WALL BRACKET LIGHT FIXTURE, LETTER INDICATES TYPE <br />O <br />KEYNOTES <br />® ®NL <br />LIGHT FIXTURE ON EMERGENCY CIRCUIT/NIGHT LIGHT NU <br />CONDUIT CONCEALED IN WALL OR ABOVE CEILING WITH CONDUCTORS <br />Q <br />® <br />EXIT L164T (ARROW INDICATES DIRECTION) <br />V <br />AS SHOWN ON PANEL 56HEDULE. U.O.N. <br />J <br />O <br />BATTERY POWERED EMERGENCY LIGHT <br />CONDUIT CONCEALED BELOW FLOOR SLAB OR FINISHED GRA WI <br />DE TH <br />G <br />Q <br />J � <br />CONDUCTORS AS SHOWN ON PANEL SCHEDULE U.D. <br />.N <br />4�� <br />TRACK LIGHTING <br />4 <br />CONDUIT EXPOSED ON WALL OR CEILING WITH GONDUGTOR5 A5 SHOM <br />ON PANEL `SCHEDULE. U.O.N. <br />T <br />Q <br />51NGLE POLE SWITCH, LOWER CASE LETTER INDICATES L16HT <br />TV <br />0 <br />L <br />CONTROLLED, MOUNT 46' A.F.F. U.O.N. <br />TELEVISION SYSTEM EMPTY CONDUIT WITH PULL WIRE <br />52 <br />DOUBLE POLE SWITCH, MOUNT 48" A.FF. U.O.N. <br />FLEXIBLE CONDUIT NOT TO EXCEED 6 FEET IN LENGTH <br />Z <br />W <br />53 <br />THREE -WAY 5WITCH, MOUNT 48' AF.F. U.O.N, <br />/DC, <br />D.G. VOLTAGE WIRING (#10 WIRE IN I/2' CONDUIT) <br />54 <br />FOUR -WAY SWITCH, MOUNT 46' A.F.F. U.O.N. <br />�=I <br />HUREMOLD (SIZE AND LENGTH AS NOTED) <br />5P <br />51N6LE POLE 5WITCH WITH PILOT LIGHT, MOUNT 48" A.F.F. U.O.N. <br />CONDUIT 5EAL -OFF FITTING <br />5K <br />KEY OPERATED SINGLE POLE SWITCH, MOUNT 48' A.F.F. UO.N. <br />PADDLE FAN WITH BACKBOX CAPABLE OF SUPPORTTN6 100 LB. LOAD <br />5F <br />FAN CONTROLLER, MOUNT 46" A.F.F. U.O.N. <br />o� <br />® <br />DIMMER 5WITCH, WATT5 AS NOTED, MOUNT 48" A.F.F. U.UN. <br />D4 <br />T.V. CAMERA <br />9H <br />MOTOR RATED SWITCH <br />© <br />T.V. MONITOR <br />8- <br />51NGLE RECEPTACLE, AMPS AS NOTED, MOUNT 18" A.F.F. U.O.N. <br />TELEVISION OUTLET, PROVIDE SINGLE 6AN6 BOX WITH 3/4' CONDUIT <br />Om <br />DUPLEX RECEPTACLE, MOUNT 18' A.F.F. U,ON <br />HSI <br />WITH PULL WIRE AND INSU.-ATTNG BUSHING STUBBED INTO CEILING <br />SPACE. MOUNT BOX 18' A.F.F. U.O.N. <br />DUPLEX RECEPTACLE, MOUNT ABOVE COUNTER HEIGHT U,O.N. <br />QUADRAPLEX RECEPTACLE, MOUNT 18' A.F.F, U.O.N. <br />`fl <br />D15CONNEGT 5WIT6H <br />DUPLEX RECEPTACLE, ONE HALF SWITCHED, MOUNT 18" A.F.F. U.O.N. <br />10013160 <br />DISCONNECT DESIGNATION (51ZE/POLES/FUSE) 'NF' INDICATES <br />NON-FUSED; "DE' INDICATES DUAL ELEMENT FUSES. <br />30A <br />I PH, 250V, RECEPTACLE, AMPS AS NOTED, MOUNT 18' A.F.F. UD N <br />® <br />MA6NETIG MOTOR STARTER <br />SPECIAL RECEPTACLE AS NOTED <br />`z <br />COMBINATION MAGNETIC MOTOR STARTER/01SCONNECT SWITCH <br />Q <br />FLOOR MOUNTED DUPLEX RECEPTACLE <br />Q <br />DRY TYPE TRANSFORMER <br />eFl <br />6ROUND FAULT INTERRUPTER RECEPTACLE, LEVITON 068g8 -1, MO,lNT <br />17- <br />CONTACTOR (A5 NOTED) <br />ABOVE COUNTER HEIGHT U.ON <br />�B• <br />DUPLEX RECEPTACLE, ISOLATED GROUND TYPE, LEVITON #5362 -161 <br />HI <br />TIME CLOCK <br />MOUNT AT 16" A.F.F. U.O.N. <br />P,c <br />PHOTO -CELL <br />DUPLEX RECEPTACLE, SPLIT WIRED, MOUNT 18' A.F.F. U.O.N. <br />MOTOR PERMANENTLY CONNECTED WITH FLEXIBLE CONDUIT <br />I� <br />CRT OUTLET, PROVIDE SINGLE GANG BOX WITH 3/4" 00NOUITWITI4 <br />FULL WIRE AND <br />° <br />INSULATING BUSHING STUBBED INTO CEILING SPACE. <br />® <br />ELECTRIC DUCT HEATER <br />MOUNT BOX 18" A.F.F. U.O.N. <br />® <br />2T1/4WV, 30 PANELBOARD <br />TO <br />THERMOSTAT. PROVIDE SINGLE 6AN6 BOX WITH 112' G. STUBBED <br />INTO CEILING SPACE, MOUNT 60" A.F.F. U.C.N. (COORDINATE WITH <br />L16HTIN(9 OR POWER PANELBOARD <br />MECHANICAL DRA 4IN65 PRIOR TO ROUGH -IN) <br />0 <br />TELEPHONE WALL OUTLET, PROVIDE 51NGLE 6AN6 BOX WITH 314' <br />P1)5HBUTTON, MOUNT 48' A.F,F. U,O.N. <br />CONDUIT WITH PULL WIRE AND INSULATING BUSHING 5TUeeED INTO' <br />CEILING SPACE. MOUNT BOX 18' A.F.F. U.O.N. <br />DOOR CHIME WITH TRAN51FORMER <br />. <br />TELEPHONE WALL OUTLET, PROVIDE SINGLE GANG BOX WITH 3/4" <br />05 <br />SPEAKER <br />CONDUIT WITH FULL WIRE AND INSULATING BUSHING 5TUBBE9 INTO <br />CEILING SPACE. MOUNT BOX ABOVE COUNTER, U.ON. <br />JO <br />,JtRJGTION BOX (FLUSH MOUNT IN FINISHED AREAS U.ONJ <br />■ <br />® FLOOR MOUNTED TELEPHONE RECEPTACLE DEVICE AS NOTED <br />E..: TELEPHONE BACKBOARD WITH #6 U. GROUND (SIZE AS NOTED) <br />K <br />E6 <br />EQUIPMENT GROUND <br />EWC <br />I6 <br />150LATED GROUND <br />FJF -EF <br />HP <br />WEATHERPROOF <br />A/H -AHU <br />EC <br />EMPTY CONDUIT <br />ACG -OU <br />EWH <br />ELECTRIC WATER HEATER <br />RTU <br />:0 0 �i►r, <br />ELECTRIC WATER COOLER <br />NL <br />EXHAUST FAN <br />PC <br />AIR HANDLING UNIT <br />C/f <br />CONDEN51 NG UNIT <br />EX <br />ROOF TOP UNIT <br />AFF <br />N16HT L16HT <br />PULL CHAIN <br />CURRENT TRANSFORMER <br />EXI5TIN6 DEVICE <br />ABOVE FINISH FLOOR <br />NOTE MOUNTING HEIGHT5 NOTED ARE TO TOP LINE OF DEVICE SNOHN U.O.N. <br />AF& <br />ABOVE FINISH GRADE <br />U.O.N. <br />UNLESS OTHERVII5E NOTED <br />N.T.5. <br />NOT TO 5GALE <br />WG <br />NOT IN CONTRACT <br />Issued for: <br />Date; <br />❑ PRELIMINARY <br />❑ PRICING <br />❑ BIDDING <br />■ PERMIT <br />07-23 -13 <br />❑ CONSTRUCTION <br />W <br />NOW <br />00 00 <br />Of <br />Z <br />0 <br />w <br />0 <br />r� <br />v <br />y <br />m <br />>- <br />O <br />Q <br />V <br />0 <br />J <br />O <br />q <br />Q <br />J � <br />W <br />4 <br />U <br />U <br />T <br />oa <br />z <br />Q <br />0 <br />M <br />M <br />Z <br />W <br />U-) <br />� <br />z <br />U <br />� � <br />Issued for: <br />Date; <br />❑ PRELIMINARY <br />❑ PRICING <br />❑ BIDDING <br />■ PERMIT <br />07-23 -13 <br />❑ CONSTRUCTION <br />W <br />f Seal <br />1' <br />1EILS CH A E <br />:N5f� .49 21 <br />Project No.: <br />1'3-106_ <br />Drawing No: <br />E -1 <br />lDrawn by. T.M. Checked py: S.C. i <br />co <br />N <br />ti <br />O <br />W <br />D <br />co <br />co <br />,W <br />VI <br />W <br />a <br />W <br />W <br />NOW <br />0��- <br />Z <br />0 <br />0 <br />Q <br />V) <br />V <br />J <br />O <br />q <br />Q <br />�WU <br />W <br />z <br />° <br />U <br />U <br />:b <br />oa <br />Q <br />M <br />Z <br />W <br />� <br />z <br />J <br />o� <br />f Seal <br />1' <br />1EILS CH A E <br />:N5f� .49 21 <br />Project No.: <br />1'3-106_ <br />Drawing No: <br />E -1 <br />lDrawn by. T.M. Checked py: S.C. i <br />co <br />N <br />ti <br />O <br />W <br />D <br />co <br />co <br />,W <br />VI <br />W <br />a <br />