� ABOVE ELECTRIC LLC <br /> 1727 Coachman Plaza Dr,Suite 212-213 <br /> Clearwater,FI 33759 <br /> � 727-726 5484 /813-506 3789 <br /> ER13014683 <br /> LOAD CALCULATION <br /> Doc#: AE1127134 <br /> ELABORATED BY: FABIO FONTANARI/ER13014683 <br /> PROJECT: 4549 Eagle Ranch Dr,Zephyrhills,FI 33542 <br /> AREA: 1295 SF <br /> MODEL: LEAH II <br /> GENERAL LOAD: <br /> TOTALS(VA) <br /> GENERAL IIGHTING 1295 SF AT 3VA/SF 3885 <br /> SMALL APPLIANCE CKT 2 AT 1500 VA 3000 <br /> LAUNDRY CKT 1 AT 1500 VA 1500 <br /> GENERAL LIGHTING LOAD(VA): 8385 <br /> DEMAND FACTOR PER NEC: <br /> FIRST 3000W @ 100% 3000 <br /> FROM 3000W TO 120000 @ 35% 1884.75 <br /> LIGHTING LOAD DEMAND(VA): �HH�.75 <br /> RANGE UNDER 12KW 1 AT 8000 VA 8000 <br /> CLOTHES DRYER 1 AT 5000 VA �� <br /> OTHER LOADS <br /> WATER HEATER 1 AT 4500 VA 4500 <br /> DISHWASHER 1 AT 1440 VA 1440 <br /> GARBAGE DISPOSAL 1 AT 1440 VA 1440 <br /> MICROWAVE OVEN 1 AT 1440 VA 1440 <br /> TOTAL OTHER LOADS(VA): 8820 <br /> DEMAND FACTOR PER NEC ART 220.53: <br /> OTHER LOAD DEMAND(VA�: 6615 <br /> AC&HEATING LOAD: <br /> ELECTRIC HEAT 7.2 Kw AT 100% 7200 <br /> SIZE <br /> AC 2.5 TON AT 2600VA AT 1259�0 3250 <br /> TOTAL NET AC AND HEAT(VA): 7`ZOO <br /> SERVICE LOAD(Kva): 31.70 <br /> SERVICE AMPS: 13�2.08 <br />