Laserfiche WebLink
'� ABOVE ELECTRIC LLC <br /> 1727 Coachman Plaza Dr,Suite 212-213 <br /> Clearwater, FI 33759 <br /> � 727-726 5484 /813-506 3789 <br /> ER13014683 <br /> LOAD CALCU LATI O N <br /> Doc#: AE1127135 <br /> ELABORATED BY: FABIO FONTANARI/ER13014683 <br /> PROJECT: 4620 Eagle Ranch Dr,Zephyrhills,FI 33542 <br /> AREA: 1327 SF <br /> MODEL: CORRIE NAOMI <br /> GENERAL LOAD: <br /> TOTALS(VA) <br /> GENERAL LIGHTING 1327 SF AT 3VA/SF 3981 <br /> SMALI APPLIANCE CKT 2 AT 1500 VA 3000 <br /> LAUNDRY CKT 1 AT 1500 VA 1500 <br /> GENERAL LIGHTiNG LOAD(VA): 8481 <br /> DEMAND FACTOR PER NEC: <br /> FIRST 3000W @ 100% 3000 <br /> FROM 3000W TO 120000 @ 3596 1918.35 <br /> LIGHTING LOAD DEMAND(VA�: 4918.35 <br /> RANGE UNDER 12KW 1 AT 8000 VA gppp <br /> CIOTHES DRYER 1 AT 5000 VA 5000 <br /> OTHERLOADS <br /> WATER HEATER 1 AT 4500 VA 4500 <br /> DISHWASHER 1 AT 1440 VA 1440 <br /> GARBAGE DISPOSAL 1 AT 1440 VA 1440 <br /> MICROWAVE OVEN 1 AT 1440 VA 1440 <br /> TOTAL OTHER LOADS(VA): 8820 <br /> DEMAND FACTOR PER NEC ART 220.53: <br /> OTHER LOAD DEMAND(VA�: 6615 <br /> AC&HEATING LOAD: <br /> ELECTRIC HEAT 7.2 Kw AT 100% 7200 <br /> SIZE <br /> AC 2.5 TON AT 2600VA AT 125% 3250 <br /> TOTAL NET AC AND HEAT(VA�: 7200 <br /> �SERVICE LOAD(Kva): 31.73 <br /> SERVICE AMPS: 132.22 <br />