My WebLink
|
Help
|
About
|
Sign Out
Browse
Search
14-14834
Zephyrhills
>
Building Department
>
Permits
>
2014
>
14-14834
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
11/12/2014 9:52:34 AM
Creation date
11/12/2014 9:48:23 AM
Metadata
Fields
Template:
Building Department
Company Name
ADVENTIST HEALTH SYSTEM
Building Department - Doc Type
Permit
Permit #
14-14834
Building Department - Name
ADVENTIST HEALTH SYSTEM
Address
7350 DAIRY RD
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
32
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
Specifications — (continued) <br /> . Strobes <br /> — Strobe appliances shall produce a minimum flash rate of 60 flashes per minute <br /> (1 flash per second)over the Regulated Input Voltage Range, and shall incorporate a <br /> Xenon flashtube enclosed in a rugged Lexan� lens <br /> — Strobes shall be available with two or four field-selectable settings in one unit, and shall be <br /> rated —per BUL 1971 —for up to: <br /> . 15130I751110cd for wall mounted <br /> . 1351185cd for wall mounted <br /> • 1 513 017 519 5cd for ceiling mounted <br /> . 1151177cd for ceiling mounted <br /> — Strobes shall operate over an extended temperature range of 32°F to 120°F (0°C to 49°C), and be listed <br /> for maximum humidity of 95% RH <br /> — Strobe inputs shall be polarized for compatibility with standard reverse-polarity supervision of circuit <br /> wiring by a Fire Alarm Control Panel (FACP) <br /> . Audibles and Audible/Strobe Combinations <br /> — Horns and horn 1 strobes shall be listed for Indoor use under 6�UL Standard 464 <br /> — Horns shall be able to produce continuous synchronized output or a <br /> temporal code-3 synchronized output <br /> — Horns shall have at least 2 sound-level settings of 90 and 95 dBA <br /> • Svnchronization Modules <br /> — The strobe portion,when synchronization is required, shall be compatible with <br /> DSC sync modules, FS-250 panel, XLS panel, or PAD-3 power supply with built-in sync protocol <br /> — The strobes shall not drift out of synchronization at any time during operation <br /> — Audibles and strobes shall be able to synchronize on a 2-wire circuit with the capability <br /> to silence the audible, if required <br /> — Strobes shall revert to a non-synchronized flash-rate, if the sync module or <br /> Power Supply should fail to operate (i.e. —contacts remain closed) <br /> — All notification appliances shall be listed for Special Applications: <br /> ■ Strobes are designed to flash at 1-flash-per-second minimum over their <br /> "Regulated Input Voltage Range" <br /> ➢ Note: NFPA-72 specifies a flash rate of 1-to-2 flashes per second, and ADA Guidelines <br /> specify a flash rate of 1-to-3 flashes per second <br /> ■ All candela ratings represent minimum-effective Strobe intensity, based on AUL Standard 1971 <br /> ■ Series ZH Strobe products are listed under BUL Standards 1971 and 464 for indoor use <br /> with a temperature range of 32°F to 120°F (0°C to 49°C)and maximum humidity of 930�0 �+20�� <br /> ■ Series ZH horns are listed under 0UL Standard 464 for audible signal appliances (Indoor use only) <br /> SIEMENS Industry, Inc. <br /> Building Technologies Division <br />
The URL can be used to link to this page
Your browser does not support the video tag.