<br />U10l't hyrhillb Healt e & Rehab
<br />GENERAL NOTES
<br />1, ALL SMOKE DETECTOR LOCATIONS ARE DIAGRAMMATIC. THE FOLLOWING RULES MUST BE OBSERVED
<br />FOR SMOKE DETECTOR PLACEMENT.
<br />A. SMOKE DETECTORS SHALL NOT BE INSTALLED CLOSER THAN 3' FROM AN AIR CONDITIONING
<br />VENT PER NFPA 72 (2007 EDITION).
<br />B. IN ROOMS SMALLER THAN 30'x30' THE DETECTOR SHALL BE CENTERED IN THE ROOM IF
<br />POSSIBLE BY OBSERVING THE ABOVE RULE. C. IN ROOMS WHERE MULTIPLE DETECTORS ARE
<br />SHOWN, ONE OF THE FOLLOWING SHALL APPLY PER NFPA 72 (2007 EDITION):
<br />1) THE DISTANCE BETWEEN DETECTORS SHALL NOT EXCEED THEIR LISTED SPACING, AND
<br />THERE SHALL BE DETECTORS WITHIN A DISTANCE OF ONE -HALF THE LISTED SPACING,
<br />MEASURED AT A RIGHT ANGLE, FROM ALL WALLS OR PARTITIONS EXTENDING TO WITHIN
<br />460MM (18 IN.) OF THE CEILING.
<br />2) ALL POINTS ON THE CEILING SHALL HAVE A DETECTOR WITHIN A DISTANCE EQUAL
<br />TO 0.7 TIMES THE LISTED SPACING.
<br />2. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NEC ARTICLE 760, LOCAL CODES, NFPA
<br />72 (2007 EDITION), AND /OR AUTHORITY HAVING JURISDICTION, ALL EQUIPMENT SHALL BE UL LISTED
<br />ALL DEVICES SHALL BE COMPATIBLE WITH THE CONTROL PANELS, SYSTEM IS POWER LIMITED PER
<br />NEC 760 AND UL 864 REQUIREMENTS.
<br />3. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS
<br />CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS. THE ELECTRICAL
<br />CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE
<br />ALARM BACK BOXES AND JUNCTION BOXES BEFORE COMPLETION OF THEIR INSTALLATION.
<br />4. ELECTRICAL CONTRACTOR MUST SET ADDRESSES FOR ADDRESSABLE DEVICES PRIOR TO INSTALLING
<br />THE DEVICE. FOR SMOKE DETECTORS, DO NOT MARK ID NUMBERS ON DEVICES LABEL BASE ONLY
<br />5. THE DESIGN INSTALLATION COMPLIES WITH FBC11 -4 -28.3, REFER TO SPECIFICATION SHEETS
<br />AND /OR INSTALLATION MANUALS.
<br />6. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. AUDIBLE /VISUAL AND INITIATING
<br />CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE.
<br />7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE AND TYPE, CONDUCTORS SHALL BE
<br />PERMANENTLY AND UNIQUELY MARKED AT FACP, JUNCTION BOXES, POWER EXTENDERS AND DEVICES
<br />FOR FUTURE IDENTIFICATION.
<br />8. MINIMUM CONDUIT SIZE WILL BE 3/4 ". CONDUIT SHALL BE NO MORE THAN 40% FILLED PER NEC
<br />REQUIREMENTS.
<br />9. ALL 'WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF
<br />SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM,
<br />10. UNDERGROUND WIRING IS ACCEPTABLE PROVIDED N.E.C. REQUIREMENTS FOR UNDERGROUND WIRING
<br />IS MET,
<br />11, INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS
<br />BUILT" PURPOSES TO SIEMENS.
<br />12. THE 120voc POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH
<br />ARTICLE 725 AND 760 OF NFPA 70 (2008 EDITION), N.E.C. AND NFPA 72; IN REFERENCE TO
<br />DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM
<br />PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN.
<br />SEQUENCE OF OPERATION
<br />13. THE FIRE ALARM CONTROL PANEL SHALL NOT BE USED TO POWER ANY UNAUTHORIZED EXTERNAL
<br />DEVICE PER NFPA 72; DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION
<br />CLEAN -UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE
<br />AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION.
<br />14. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN -UP BY ALL TRADES SHALL BE
<br />CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 (2007 EDITION) CHAPTER 7. FAILURE TO
<br />COMPLY WITH THIS NOTE WILL VOID ALL WARRANTIES.
<br />15. FIRE ALARM COMPONENTS AND DEVICES MUST BE RATED FOR TEMPERATURE AND HUMIDITY IN THE ENVIRONMENT
<br />IN WHICH IT IS LOCATED.
<br />16, DAMPER MOTOR AND FAN SHUTDOWN CONNECTIONS (IF ANY) ARE TO BE COORDINATED IN FIELD WITH HVAC
<br />CONTRACTOR.
<br />17. FIRE ALARM POWER SUPPLIES AND ALL REMOTE SUPPLIES MUST BE CONNECTED TO BUILDING POWER OR
<br />COLD -WATER GROUND VIA 1 GREEN #12 THHN OR EQUIVALENT.
<br />18. ALL SURGE /TRANSIENT SUPPRESSORS MUST BE CONNECTED TO BUILDING COLD -WATER GROUND. USE SURGE
<br />SUPPRESSION ON ALL CIRCUIT CONDUCTORS LEAVING AND ENTERING THE BUILDING. SURGE SUPPRESSION SHALL
<br />BE SUITABLE FOR THE INTENDED USE. CIRCUITS SHALL BE PROTECTED FROM INDUCED TRANSIENT VOLTAGE.
<br />19. VERIFY MOUNTING LOCATIONS FOR THE FIRE ALARM CONTROL PANEL, REMOTE PANEL, SIGNAL EXTENDER, AND
<br />ANNUNCIATOR PANEL WITH ELECTRICAL CONTRACTOR.
<br />20. THE TRI -D IS A DUAL INPUT MODULE WITH A SINGLE ADDRESS. THE FACP ANNUNCIATES EACH INPUT SEPARATELY.
<br />21. HEAT DETECTORS MUST BE WITHIN 24" OF SPRINKLER HEAD IN ELEVATOR MACHINE ROOM. SMOKE DETECTORS IN
<br />THE ELEVATOR MACHINE ROOM SHALL RECALL THE ELEVATOR TO THE DESIGNATED LANDING. IF THE ELEVATOR
<br />MACHINE ROOM IS AT THE DESIGNATED LANDING THEN THE ELEVATOR SHALL BE RECALLED TO AN ALTERNATE
<br />LANDING.
<br />22. WHERE AUDIBLE APPLIANCE ARE INSTALLED TO PROVIDE SIGNALS FOR SLEEPING AREAS, THEY SHALL HAVE A
<br />SOUND LEVEL OF AT LEAST 15 dB ABOVE THE AVERAGE AMBIENT SOUND LEVEL OR 5 dB ABOVE THE MAXIMUM
<br />SOUND LEVEL HAVING A DURATION OF AT LEAST 60 SECONDS OR A LEVEL OF AT LEAST 75 dBA, WHICHEVER IS
<br />GREATER, U E P L W L E I O G PI D S EPIN F, SING THE A- WEIGHTED SCALE
<br />(dBA). rA SOUND LEVEL OF 75dBA SHALL BE ACHIEVED AT ALL SLEEPING AREAS. Q
<br />23. CIRCU'TS LEAVING THE FIRE ALARM CONTROL AND ANY REMOTE PANELS MUST BE INSTALLED TO BE PROTECTED
<br />FROM PHYSICAL DAMAGE, AS WELL AS ATTACK FROM FIRE BY PROVIDING AS ATTACK FROM FIRE BY PROVIDING 2
<br />HOUR RATED PROTECTION AS PER NFPA 72 6.9.4.3. (2007 EDITION).
<br />24. THE 20 VAC CIRCUIT NUMBER FOR THE FIRE ALARM PANELS SHALL BE CONFIRMED IN THE FIELD, USING THE
<br />FOLLCENING INFORMATION:
<br />A. PER NFPA 72 SECTION 4.4.1.4 (2007 ED.)
<br />1) THE CIRCUIT BREAKER SHALL HAVE A RED MARKING, SHALL BE ACCESSIBLE ONLY BY
<br />AUTHORIZED PERSONNEL, AND SHALL BE IDENTIFIED AS "FIRE ALARM CIRCUIT ",
<br />2) THE LOCATION OF THE CIRCUIT DISCONNECT MEANS (CIRCUIT BREAKER) SHALL BE PERMANENTLY
<br />IDENTIFIED ON THE FIRE ALARM PANEL,
<br />B. THE MAIN FIRE ALARM PANEL REQUIRES AN AC INPUT CURRENT OF 3.5 AMPS PER EACH PSC -12 AND
<br />EACH PSX -12 POWER SUPPLY.
<br />C THE PAD -3 POWER EXTENDER PANELS REQUIRE AN AC INPUT CURRENT OF 2.5 AMPS.
<br />D. 1*HE BREAKER FOR THE FIRE ALARM CIRCUIT SHALL NOT BE GREATER THAN 20 AMPS AND NOT LOADED
<br />ABOVE 80% OF ITS VALUE.
<br />E. ALL A.C. POWER FOR THE FIRE ALARM PANELS SHALL BE PROVIDED FROM LIFE SAFETY
<br />(EMERGENCY) BRANCH CIRCUITS. INFORMATION REGARDING THE CORRECT BRANCH CIRCUIT SHALL BE
<br />PROVIDED BY THE INSTALLER SHALL BE INCLUDED IN THE AS -BUILT DRAWING SET,
<br />1. ACTIVATION OF ANY AUTOMATIC SMOKE DETECTOR, AUTOMATIC HEAT DETECTOR, OR SPRINKLER WATER -FLOW
<br />SWITCH SHALL CAUSE THE FOLLOWING EVENTS, ACTIONS, AND INDICATIONS:
<br />A. DISPLAY A CUSTOM MESSAGE DESCRIBING THE DEVICE ORIGINATING THE ALARM CONDITION AT THE FIRE ALARM CONTROL PANEL
<br />AND STORE THE EVENT IN THE HISTORY LOG OF THE PANEL.
<br />B. SOUND AN ALERT TONE AT THE FIRE ALARM CONTROL PANEL UNTIL THE ALARM CONDITION IS ACKNOWLEDGED.
<br />D. ACTIVATE AUDION /VISUAL ALARM CIRCUITS AS PROGRAMMED, UNTIL PANEL IS RESET.
<br />E. ACTIVATE RELAYS TO PERFORM THE FOLLOWING ACTIONS:
<br />F. ACTIVATE DIALER TO CALL OFF -SITE MONITORING STATION.
<br />2. ACTIVATION OF ANY MANUAL PULL STATION SHALL CAUSE THE EVENTS, ACTIONS, AND INDICATIONS; AS DESCRIBED NUMBER 1 ABOVE,
<br />EXCEPT FOR THE ACTIONS AS DESCRIBED IN NOTE (E).
<br />3. ACTIVATION OF ANY SUPERVISORY DEVICE WITHIN THE SYSTEM SHALL CAUSE THE FOLLOWING ACTIONS AND INDICATIONS:
<br />A. ACTIVATE THE SUPERVISORY LIGHT AND SOUNDER AT THE FIRE ALARM CONTROL PANEL AND ANNUNCIATORS, IF ANY.
<br />B. DISPLAY A CUSTOM MESSAGE DESCRIBING THE LOCATION OF THE DEVICE INITIATING THE EVENT.
<br />C. ANY DUCT MOUNTED SMOKE DETECTORS SHALL, CAUSE THE SHUTDOWN OF THE ASSOCIATED AIR
<br />HANDLER OR CLOSURE OF THE ASSOCIATED DAMPER. SYSTEM WILL SHOW A SUPERVISORY ALARM.
<br />D. ACTIVATE DIALER TO CALL OFF -SITE MONITORING STATION.
<br />4. ACTIVATION OF ANY TROUBLE CONDITION SHALL CAUSE THE FOLLOWING EVENTS, ACTIONS AND INDICATIONS.
<br />A. DISPLAY A CUSTOM MESSAGE DESCRIBING THE TROUBLE CONDITION AT THE FIRE ALARM CONTROL CONTROL PANEL AND STORE
<br />THE EVENT IN THE HISTORY LOG OF THE PANEL.
<br />B. SOUND AN ALERT TONE AT THE FIRE ALARM CONTROL PANEL UNTIL THE TROUBLE CONDITION IS ACKNOWLEDGED,
<br />C. ACTIVATE THE COMMON TROUBLE RELAY FOR OFF -SITE MONITORING STATION.
<br />SYMBOL LEGEND
<br />SYM
<br />DESCRIPTION
<br />MODEL
<br />NOTES
<br />FACP
<br />FIRE ALARM CONTROL PANEL
<br />XLS
<br />(SUPPLIED BY SIEMENS)
<br />PWR
<br />AUXILIARY SIGNAL POWER BOOSTER
<br />FIRE ALARM
<br />(SUPPLIED BY SIEMENS)
<br />FA_N_N1
<br />REMOTE ANNUNCIATOR PANEL
<br />AUDIBLE /VISUAL DEVICE
<br />(SUPPLIED BY SIEMENS)
<br />7' -0" AFF
<br />PHOTOELECTRIC DETECTOR WYITH STANDARD BASE
<br />FDOT
<br />(SUPPLIED BY SIEMENS)
<br />©
<br />DUAL ACTION MANUAL PULL 'STATION
<br />MSI - LOB
<br />EXISTING TO REMAIN
<br />DM
<br />ADDRESSABLE INTERFACE MOUDULE W/ RELAY
<br />TRI -R
<br />EXISTING TO REMAIN
<br />T
<br />CHIME /STROBE SELECT CD MALL MOUNT
<br />CH -MZ
<br />(SUPPLIED BY SIEMENS)
<br />48" AFF
<br />STROBE SELECT CD
<br />ZR -MC
<br />(SUPPLIED BY SIEMENS)
<br />TO TOP OF
<br />FLOW SWITCH
<br />BY OTHERS
<br />EXISTING TO REMAIN
<br />ACTIVATION
<br />TAMPER SWITCH
<br />BY OTHERS
<br />EXISTING TO REMAIN
<br />FINISHED FLOOR
<br />DUCT DETECTOR
<br />AD2 -P
<br />EXISTING TO REMAIN
<br />®
<br />HEAT DETECTOR
<br />FPT -11
<br />EXISTING TO REMAIN
<br />TYPICAL ELEVATION DETAIL
<br />TYPICAL ELEVATION DETAIL
<br />OF AUDIBLE /VISUAL ALARM DEVICE
<br />OF VISUAL ALARM DEVICE
<br />OF MANUAL PULL STATION
<br />OF AUIDIBLE DEVICE
<br />NOTE: SEE PRODUCT INSTALL - ATION INSTRUCTIONS FOR SPECIFIC MOUNTING, WIRING AND SETTINGS DETAILS FOR EACH DEVICE.
<br />A.Js;vil7'fE:l FtANOIS) 11AVE)1EEN RE4?`EW'
<br />)'f Z1 PIT`S Hl
<br />LS TARE MARSHAL, S OFFICE
<br />('lease be advised this review of plans submitted is a
<br />CJJ(Sory review to assist the contractor in compliance with
<br />applicable fire safety codes. This review is not intended
<br />to bra a final approval of the submitted plans, It is the
<br />contractor's sole responsibility to ensure that the plans are in
<br />complete compliance with all applicable NFPA codes and
<br />local ordinances, In the event that further examination or
<br />site inspection reveals areas of non - compliance, it shall be
<br />the contractor's sale responsibility, at their sole expense to
<br />bring those areas in compliance, The City assumes no
<br />responsibility for the contractor's failure to be in compliance
<br />with all applicable NFPA Codes and local ordinances,
<br />WIRE LEGEND
<br />MOUNTING
<br />HEIGHTS
<br />SUGGESTED WIRE TYPE
<br />COLOR CODE
<br />NOTES:
<br />1. USE FPLP TYPE WIRE FOR RUNS IN PLENUM SPACE.
<br />2. USE FPLR TYPE WIRE FOR VERTICAL THRU -FLOOR RUNS,
<br />3. USE FPL WIRE WHICH IS RATED FOR WET LOCATIONS, FOR ALL
<br />UNDERGROUND RUNS; OR AS REQUIRED BY CODE NFPA 70.
<br />4. THHN WIRE IS ACCEPTABLE FOR USE AS SHOWN ON LEGEND.
<br />A
<br />I
<br />18/2 TWISTED PAIR FPL
<br />YELLOW
<br />FIRE ALARM
<br />FIRE ALARM
<br />FIRE ALARM MUST
<br />BE IN CONDUIT AUDIBLE
<br />DEVICE OPNLY
<br />AUDIBLE /VISUAL DEVICE
<br />VISUAL DEVICE ONLY UP TO
<br />7' -0" AFF
<br />TS
<br />80" AFF
<br />80" AFF
<br />`
<br />90" AFF
<br />TO BOTTOM
<br />TO BOTTOM
<br />MANUAL STATION
<br />TO TOP
<br />OF STROBE
<br />OF STROBE
<br />T
<br />OF DEVICE
<br />48" AFF
<br />TO TOP OF
<br />ACTIVATION
<br />FINISHED FLOOR
<br />FINISHED FLOOR
<br />FINISHED FLOOR
<br />FINISHED (FLOOR
<br />e
<br />TYPICAL ELEVATION DETAIL
<br />TYPICAL ELEVATION DETAIL
<br />TYPICAL ELEVATION DETAIL
<br />TYPICAL ELEVATION DETAIL
<br />OF AUDIBLE /VISUAL ALARM DEVICE
<br />OF VISUAL ALARM DEVICE
<br />OF MANUAL PULL STATION
<br />OF AUIDIBLE DEVICE
<br />A.Js;vil7'fE:l FtANOIS) 11AVE)1EEN RE4?`EW'
<br />)'f Z1 PIT`S Hl
<br />LS TARE MARSHAL, S OFFICE
<br />('lease be advised this review of plans submitted is a
<br />CJJ(Sory review to assist the contractor in compliance with
<br />applicable fire safety codes. This review is not intended
<br />to bra a final approval of the submitted plans, It is the
<br />contractor's sole responsibility to ensure that the plans are in
<br />complete compliance with all applicable NFPA codes and
<br />local ordinances, In the event that further examination or
<br />site inspection reveals areas of non - compliance, it shall be
<br />the contractor's sale responsibility, at their sole expense to
<br />bring those areas in compliance, The City assumes no
<br />responsibility for the contractor's failure to be in compliance
<br />with all applicable NFPA Codes and local ordinances,
<br />WIRE LEGEND
<br />SYM
<br />DESCRIPTION
<br />SUGGESTED WIRE TYPE
<br />COLOR CODE
<br />NOTES:
<br />1. USE FPLP TYPE WIRE FOR RUNS IN PLENUM SPACE.
<br />2. USE FPLR TYPE WIRE FOR VERTICAL THRU -FLOOR RUNS,
<br />3. USE FPL WIRE WHICH IS RATED FOR WET LOCATIONS, FOR ALL
<br />UNDERGROUND RUNS; OR AS REQUIRED BY CODE NFPA 70.
<br />4. THHN WIRE IS ACCEPTABLE FOR USE AS SHOWN ON LEGEND.
<br />A
<br />SLC (ANALOG LOOP)
<br />18/2 TWISTED PAIR FPL
<br />YELLOW
<br />C
<br />STROBE ONLY or CHIME /STROBE CIRCUIT
<br />14/2 FPL / THHN
<br />RED
<br />NAC
<br />NOTIFICATION APPLIANCE CIRCUIT
<br />FS
<br />FLOW SWITCH
<br />TS
<br />TAMPER SWITCH
<br />CODE REFERENCES
<br />THE FOLLOWING CODES HAVE BEEN REFERENCED, AND APPLIED WHEREAF NECESSARY:
<br />NFPA 72 (2007) NATIONAL FIRE ALARM CODE
<br />NFPA 70 (2008) NATIONAL ELECTRIC CODE (NEC)
<br />NFPA 13 (2007) STANDARD ON SPRINKLER SYSTEMS
<br />NFPA 101 (2009) LIFE SAFETY CODE
<br />NFPA 92A (2009) STANDARD FOR SMOKE CONTROL SYSTEMS UTILIZING BARRIERS AND PRESSURE
<br />DIFFERENCES.
<br />NFPA 92B (2009) STANDARD FOR SMOKE MANAGEMENT SYSTEMS IN MALLS, ATRIA AND LARGE SPACES
<br />FBC (2010) FLORIDA BUILDING CODE
<br />FFPC (2010) FLORIDA FIRE PROTECTION CODE
<br />SCOPE OF WORK
<br />1. REPLACING AN EXISTING MXL FIRE ALARM PANEL TO AN XLS FIRE
<br />ALARM PANEL, REPLACING IONIZATOIN SMOKE DETECTORS TO PHOTOELECTRIC
<br />SMOKE DETECTORS, AND REPLACING EXISTING NOTIFICATION DEVICES WITH NEW
<br />NOTIFICATION DEVICES.
<br />2. PROGRAM, TEST, AND CERTIFY THE COMPLETED FIRE ALARM SYSTEM,
<br />ABBREVIATIONS
<br />F.B.O.
<br />FURNISHED BY OTHERS
<br />WP
<br />WEATHERPROOF
<br />H.O.
<br />HIGH OUTPUT
<br />FPL
<br />FIRE POWER LIMITED
<br />CD
<br />CANDELA
<br />AFF
<br />ABOVE FINISHED FLOOR
<br />SLC
<br />SIGNALING LINE CIRCUIT
<br />NAC
<br />NOTIFICATION APPLIANCE CIRCUIT
<br />FS
<br />FLOW SWITCH
<br />TS
<br />TAMPER SWITCH
<br />THE DRAWING AND DESIGN HEREIN SHALL NOT BE DUPLICATED,
<br />USED OR DISCLOSED TO OTHERS FOR PROCUREMENT OR OTHER
<br />PURPOSE (EXCEPT AS OTHERWISE AUTHORIZED BY CONTRACT)
<br />WITHOUT WRITTEN PERMISSION OF SIEMENS BUILDING TECHNO-
<br />LOGIE3, INC.. FIRE SAFETY DIVISION. ALL OTHER REPRODUCTIONS
<br />SHALL BEAR THIS NOTICE,
<br />R E V I S I O N S
<br />No. I Revision I By I Cate
<br />OSHPO NUMBER:
<br />PROFESSIONAL ENGINEERS APPROVAL STAMP:
<br />FREUD ENTERPRISES
<br />CONSULTINC,£Nc Nu
<br />//
<br />880 PEEP LS
<br />Voke 9"��jy95Q ��FC }� Jyi
<br />No 32578
<br />sA
<br />.�,
<br />CEQRCE FRED P,E. r
<br />1e7��i/��\
<br />G�
<br />J I -/I Il
<br />DESIGN ENGINEERS:
<br />CONTRACTOR'S NAME & ADDRESS:
<br />Siemens Industries, Inc.
<br />Building Technologies Division
<br />TAMPA BRANCH
<br />8403 Benjamin Road
<br />Tampa, Florida 33634
<br />Tel (813) 261 -8700 Fax (813) 890 -8055
<br />Florida State EF License No EF2000416
<br />U L. Certificate ID No 603961 -030
<br />PRODUCT MANUFACTURER: SIEMENS
<br />Siemens Indusifies, Inc,
<br />Building Technologies Division
<br />TAMPA BRANCH
<br />8403 Benjamin Road
<br />Tampa, Florida 33634
<br />Tel(813)261 -8700 Fax(813)890 -8055
<br />Florida State EF License No. EF2000416
<br />U.L. Certificate ID No. 603961 -030
<br />JOB NAME & LOCATION (STREET ADDRESS)
<br />Zephyrhills
<br />Healthcare
<br />and
<br />Rehab
<br />7350 Dairy Rd.
<br />Zephyrhills, FI 33541
<br />SHEET CONTENTS:
<br />INSTALLATION TYPE
<br />3 NEW INSTALLATION
<br />[3 DESIGN/BUILD
<br />0 PER CONTRACT DOCUMENT
<br />0 EXISTING BASE JOB # N/A
<br />0 OTHERS
<br />SYSTEM SALES REP.:
<br />John Bourdeau
<br />PROJECT MANAGER:
<br />DRAWN BY:
<br />Guillermo Grande
<br />CAD FILENAME:
<br />SCALE.
<br />DATE DRAWN:
<br />PLOT DATE:
<br />December 10. 2013
<br />SHEET OF
<br />1
<br />5
<br />JOB NUMBER
<br />5200368848
<br />
|