PA hcar <br />U10l't hyrhillb Healt e & Rehab <br />GENERAL NOTES <br />1, ALL SMOKE DETECTOR LOCATIONS ARE DIAGRAMMATIC. THE FOLLOWING RULES MUST BE OBSERVED <br />FOR SMOKE DETECTOR PLACEMENT. <br />A. SMOKE DETECTORS SHALL NOT BE INSTALLED CLOSER THAN 3' FROM AN AIR CONDITIONING <br />VENT PER NFPA 72 (2007 EDITION). <br />B. IN ROOMS SMALLER THAN 30'x30' THE DETECTOR SHALL BE CENTERED IN THE ROOM IF <br />POSSIBLE BY OBSERVING THE ABOVE RULE. C. IN ROOMS WHERE MULTIPLE DETECTORS ARE <br />SHOWN, ONE OF THE FOLLOWING SHALL APPLY PER NFPA 72 (2007 EDITION): <br />1) THE DISTANCE BETWEEN DETECTORS SHALL NOT EXCEED THEIR LISTED SPACING, AND <br />THERE SHALL BE DETECTORS WITHIN A DISTANCE OF ONE -HALF THE LISTED SPACING, <br />MEASURED AT A RIGHT ANGLE, FROM ALL WALLS OR PARTITIONS EXTENDING TO WITHIN <br />460MM (18 IN.) OF THE CEILING. <br />2) ALL POINTS ON THE CEILING SHALL HAVE A DETECTOR WITHIN A DISTANCE EQUAL <br />TO 0.7 TIMES THE LISTED SPACING. <br />2. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NEC ARTICLE 760, LOCAL CODES, NFPA <br />72 (2007 EDITION), AND /OR AUTHORITY HAVING JURISDICTION, ALL EQUIPMENT SHALL BE UL LISTED <br />ALL DEVICES SHALL BE COMPATIBLE WITH THE CONTROL PANELS, SYSTEM IS POWER LIMITED PER <br />NEC 760 AND UL 864 REQUIREMENTS. <br />3. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS <br />CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS. THE ELECTRICAL <br />CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE <br />ALARM BACK BOXES AND JUNCTION BOXES BEFORE COMPLETION OF THEIR INSTALLATION. <br />4. ELECTRICAL CONTRACTOR MUST SET ADDRESSES FOR ADDRESSABLE DEVICES PRIOR TO INSTALLING <br />THE DEVICE. FOR SMOKE DETECTORS, DO NOT MARK ID NUMBERS ON DEVICES LABEL BASE ONLY <br />5. THE DESIGN INSTALLATION COMPLIES WITH FBC11 -4 -28.3, REFER TO SPECIFICATION SHEETS <br />AND /OR INSTALLATION MANUALS. <br />6. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. AUDIBLE /VISUAL AND INITIATING <br />CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE. <br />7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE AND TYPE, CONDUCTORS SHALL BE <br />PERMANENTLY AND UNIQUELY MARKED AT FACP, JUNCTION BOXES, POWER EXTENDERS AND DEVICES <br />FOR FUTURE IDENTIFICATION. <br />8. MINIMUM CONDUIT SIZE WILL BE 3/4 ". CONDUIT SHALL BE NO MORE THAN 40% FILLED PER NEC <br />REQUIREMENTS. <br />9. ALL 'WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF <br />SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM, <br />10. UNDERGROUND WIRING IS ACCEPTABLE PROVIDED N.E.C. REQUIREMENTS FOR UNDERGROUND WIRING <br />IS MET, <br />11, INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS <br />BUILT" PURPOSES TO SIEMENS. <br />12. THE 120voc POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH <br />ARTICLE 725 AND 760 OF NFPA 70 (2008 EDITION), N.E.C. AND NFPA 72; IN REFERENCE TO <br />DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM <br />PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. <br />SEQUENCE OF OPERATION <br />13. THE FIRE ALARM CONTROL PANEL SHALL NOT BE USED TO POWER ANY UNAUTHORIZED EXTERNAL <br />DEVICE PER NFPA 72; DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION <br />CLEAN -UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE <br />AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. <br />14. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN -UP BY ALL TRADES SHALL BE <br />CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 (2007 EDITION) CHAPTER 7. FAILURE TO <br />COMPLY WITH THIS NOTE WILL VOID ALL WARRANTIES. <br />15. FIRE ALARM COMPONENTS AND DEVICES MUST BE RATED FOR TEMPERATURE AND HUMIDITY IN THE ENVIRONMENT <br />IN WHICH IT IS LOCATED. <br />16, DAMPER MOTOR AND FAN SHUTDOWN CONNECTIONS (IF ANY) ARE TO BE COORDINATED IN FIELD WITH HVAC <br />CONTRACTOR. <br />17. FIRE ALARM POWER SUPPLIES AND ALL REMOTE SUPPLIES MUST BE CONNECTED TO BUILDING POWER OR <br />COLD -WATER GROUND VIA 1 GREEN #12 THHN OR EQUIVALENT. <br />18. ALL SURGE /TRANSIENT SUPPRESSORS MUST BE CONNECTED TO BUILDING COLD -WATER GROUND. USE SURGE <br />SUPPRESSION ON ALL CIRCUIT CONDUCTORS LEAVING AND ENTERING THE BUILDING. SURGE SUPPRESSION SHALL <br />BE SUITABLE FOR THE INTENDED USE. CIRCUITS SHALL BE PROTECTED FROM INDUCED TRANSIENT VOLTAGE. <br />19. VERIFY MOUNTING LOCATIONS FOR THE FIRE ALARM CONTROL PANEL, REMOTE PANEL, SIGNAL EXTENDER, AND <br />ANNUNCIATOR PANEL WITH ELECTRICAL CONTRACTOR. <br />20. THE TRI -D IS A DUAL INPUT MODULE WITH A SINGLE ADDRESS. THE FACP ANNUNCIATES EACH INPUT SEPARATELY. <br />21. HEAT DETECTORS MUST BE WITHIN 24" OF SPRINKLER HEAD IN ELEVATOR MACHINE ROOM. SMOKE DETECTORS IN <br />THE ELEVATOR MACHINE ROOM SHALL RECALL THE ELEVATOR TO THE DESIGNATED LANDING. IF THE ELEVATOR <br />MACHINE ROOM IS AT THE DESIGNATED LANDING THEN THE ELEVATOR SHALL BE RECALLED TO AN ALTERNATE <br />LANDING. <br />22. WHERE AUDIBLE APPLIANCE ARE INSTALLED TO PROVIDE SIGNALS FOR SLEEPING AREAS, THEY SHALL HAVE A <br />SOUND LEVEL OF AT LEAST 15 dB ABOVE THE AVERAGE AMBIENT SOUND LEVEL OR 5 dB ABOVE THE MAXIMUM <br />SOUND LEVEL HAVING A DURATION OF AT LEAST 60 SECONDS OR A LEVEL OF AT LEAST 75 dBA, WHICHEVER IS <br />GREATER, U E P L W L E I O G PI D S EPIN F, SING THE A- WEIGHTED SCALE <br />(dBA). rA SOUND LEVEL OF 75dBA SHALL BE ACHIEVED AT ALL SLEEPING AREAS. Q <br />23. CIRCU'TS LEAVING THE FIRE ALARM CONTROL AND ANY REMOTE PANELS MUST BE INSTALLED TO BE PROTECTED <br />FROM PHYSICAL DAMAGE, AS WELL AS ATTACK FROM FIRE BY PROVIDING AS ATTACK FROM FIRE BY PROVIDING 2 <br />HOUR RATED PROTECTION AS PER NFPA 72 6.9.4.3. (2007 EDITION). <br />24. THE 20 VAC CIRCUIT NUMBER FOR THE FIRE ALARM PANELS SHALL BE CONFIRMED IN THE FIELD, USING THE <br />FOLLCENING INFORMATION: <br />A. PER NFPA 72 SECTION 4.4.1.4 (2007 ED.) <br />1) THE CIRCUIT BREAKER SHALL HAVE A RED MARKING, SHALL BE ACCESSIBLE ONLY BY <br />AUTHORIZED PERSONNEL, AND SHALL BE IDENTIFIED AS "FIRE ALARM CIRCUIT ", <br />2) THE LOCATION OF THE CIRCUIT DISCONNECT MEANS (CIRCUIT BREAKER) SHALL BE PERMANENTLY <br />IDENTIFIED ON THE FIRE ALARM PANEL, <br />B. THE MAIN FIRE ALARM PANEL REQUIRES AN AC INPUT CURRENT OF 3.5 AMPS PER EACH PSC -12 AND <br />EACH PSX -12 POWER SUPPLY. <br />C THE PAD -3 POWER EXTENDER PANELS REQUIRE AN AC INPUT CURRENT OF 2.5 AMPS. <br />D. 1*HE BREAKER FOR THE FIRE ALARM CIRCUIT SHALL NOT BE GREATER THAN 20 AMPS AND NOT LOADED <br />ABOVE 80% OF ITS VALUE. <br />E. ALL A.C. POWER FOR THE FIRE ALARM PANELS SHALL BE PROVIDED FROM LIFE SAFETY <br />(EMERGENCY) BRANCH CIRCUITS. INFORMATION REGARDING THE CORRECT BRANCH CIRCUIT SHALL BE <br />PROVIDED BY THE INSTALLER SHALL BE INCLUDED IN THE AS -BUILT DRAWING SET, <br />1. ACTIVATION OF ANY AUTOMATIC SMOKE DETECTOR, AUTOMATIC HEAT DETECTOR, OR SPRINKLER WATER -FLOW <br />SWITCH SHALL CAUSE THE FOLLOWING EVENTS, ACTIONS, AND INDICATIONS: <br />A. DISPLAY A CUSTOM MESSAGE DESCRIBING THE DEVICE ORIGINATING THE ALARM CONDITION AT THE FIRE ALARM CONTROL PANEL <br />AND STORE THE EVENT IN THE HISTORY LOG OF THE PANEL. <br />B. SOUND AN ALERT TONE AT THE FIRE ALARM CONTROL PANEL UNTIL THE ALARM CONDITION IS ACKNOWLEDGED. <br />D. ACTIVATE AUDION /VISUAL ALARM CIRCUITS AS PROGRAMMED, UNTIL PANEL IS RESET. <br />E. ACTIVATE RELAYS TO PERFORM THE FOLLOWING ACTIONS: <br />F. ACTIVATE DIALER TO CALL OFF -SITE MONITORING STATION. <br />2. ACTIVATION OF ANY MANUAL PULL STATION SHALL CAUSE THE EVENTS, ACTIONS, AND INDICATIONS; AS DESCRIBED NUMBER 1 ABOVE, <br />EXCEPT FOR THE ACTIONS AS DESCRIBED IN NOTE (E). <br />3. ACTIVATION OF ANY SUPERVISORY DEVICE WITHIN THE SYSTEM SHALL CAUSE THE FOLLOWING ACTIONS AND INDICATIONS: <br />A. ACTIVATE THE SUPERVISORY LIGHT AND SOUNDER AT THE FIRE ALARM CONTROL PANEL AND ANNUNCIATORS, IF ANY. <br />B. DISPLAY A CUSTOM MESSAGE DESCRIBING THE LOCATION OF THE DEVICE INITIATING THE EVENT. <br />C. ANY DUCT MOUNTED SMOKE DETECTORS SHALL, CAUSE THE SHUTDOWN OF THE ASSOCIATED AIR <br />HANDLER OR CLOSURE OF THE ASSOCIATED DAMPER. SYSTEM WILL SHOW A SUPERVISORY ALARM. <br />D. ACTIVATE DIALER TO CALL OFF -SITE MONITORING STATION. <br />4. ACTIVATION OF ANY TROUBLE CONDITION SHALL CAUSE THE FOLLOWING EVENTS, ACTIONS AND INDICATIONS. <br />A. DISPLAY A CUSTOM MESSAGE DESCRIBING THE TROUBLE CONDITION AT THE FIRE ALARM CONTROL CONTROL PANEL AND STORE <br />THE EVENT IN THE HISTORY LOG OF THE PANEL. <br />B. SOUND AN ALERT TONE AT THE FIRE ALARM CONTROL PANEL UNTIL THE TROUBLE CONDITION IS ACKNOWLEDGED, <br />C. ACTIVATE THE COMMON TROUBLE RELAY FOR OFF -SITE MONITORING STATION. <br />SYMBOL LEGEND <br />SYM <br />DESCRIPTION <br />MODEL <br />NOTES <br />FACP <br />FIRE ALARM CONTROL PANEL <br />XLS <br />(SUPPLIED BY SIEMENS) <br />PWR <br />AUXILIARY SIGNAL POWER BOOSTER <br />FIRE ALARM <br />(SUPPLIED BY SIEMENS) <br />FA_N_N1 <br />REMOTE ANNUNCIATOR PANEL <br />AUDIBLE /VISUAL DEVICE <br />(SUPPLIED BY SIEMENS) <br />7' -0" AFF <br />PHOTOELECTRIC DETECTOR WYITH STANDARD BASE <br />FDOT <br />(SUPPLIED BY SIEMENS) <br />© <br />DUAL ACTION MANUAL PULL 'STATION <br />MSI - LOB <br />EXISTING TO REMAIN <br />DM <br />ADDRESSABLE INTERFACE MOUDULE W/ RELAY <br />TRI -R <br />EXISTING TO REMAIN <br />T <br />CHIME /STROBE SELECT CD MALL MOUNT <br />CH -MZ <br />(SUPPLIED BY SIEMENS) <br />48" AFF <br />STROBE SELECT CD <br />ZR -MC <br />(SUPPLIED BY SIEMENS) <br />TO TOP OF <br />FLOW SWITCH <br />BY OTHERS <br />EXISTING TO REMAIN <br />ACTIVATION <br />TAMPER SWITCH <br />BY OTHERS <br />EXISTING TO REMAIN <br />FINISHED FLOOR <br />DUCT DETECTOR <br />AD2 -P <br />EXISTING TO REMAIN <br />® <br />HEAT DETECTOR <br />FPT -11 <br />EXISTING TO REMAIN <br />TYPICAL ELEVATION DETAIL <br />TYPICAL ELEVATION DETAIL <br />OF AUDIBLE /VISUAL ALARM DEVICE <br />OF VISUAL ALARM DEVICE <br />OF MANUAL PULL STATION <br />OF AUIDIBLE DEVICE <br />NOTE: SEE PRODUCT INSTALL - ATION INSTRUCTIONS FOR SPECIFIC MOUNTING, WIRING AND SETTINGS DETAILS FOR EACH DEVICE. <br />A.Js;vil7'fE:l FtANOIS) 11AVE)1EEN RE4?`EW' <br />)'f Z1 PIT`S Hl <br />LS TARE MARSHAL, S OFFICE <br />('lease be advised this review of plans submitted is a <br />CJJ(Sory review to assist the contractor in compliance with <br />applicable fire safety codes. This review is not intended <br />to bra a final approval of the submitted plans, It is the <br />contractor's sole responsibility to ensure that the plans are in <br />complete compliance with all applicable NFPA codes and <br />local ordinances, In the event that further examination or <br />site inspection reveals areas of non - compliance, it shall be <br />the contractor's sale responsibility, at their sole expense to <br />bring those areas in compliance, The City assumes no <br />responsibility for the contractor's failure to be in compliance <br />with all applicable NFPA Codes and local ordinances, <br />WIRE LEGEND <br />MOUNTING <br />HEIGHTS <br />SUGGESTED WIRE TYPE <br />COLOR CODE <br />NOTES: <br />1. USE FPLP TYPE WIRE FOR RUNS IN PLENUM SPACE. <br />2. USE FPLR TYPE WIRE FOR VERTICAL THRU -FLOOR RUNS, <br />3. USE FPL WIRE WHICH IS RATED FOR WET LOCATIONS, FOR ALL <br />UNDERGROUND RUNS; OR AS REQUIRED BY CODE NFPA 70. <br />4. THHN WIRE IS ACCEPTABLE FOR USE AS SHOWN ON LEGEND. <br />A <br />I <br />18/2 TWISTED PAIR FPL <br />YELLOW <br />FIRE ALARM <br />FIRE ALARM <br />FIRE ALARM MUST <br />BE IN CONDUIT AUDIBLE <br />DEVICE OPNLY <br />AUDIBLE /VISUAL DEVICE <br />VISUAL DEVICE ONLY UP TO <br />7' -0" AFF <br />TS <br />80" AFF <br />80" AFF <br />` <br />90" AFF <br />TO BOTTOM <br />TO BOTTOM <br />MANUAL STATION <br />TO TOP <br />OF STROBE <br />OF STROBE <br />T <br />OF DEVICE <br />48" AFF <br />TO TOP OF <br />ACTIVATION <br />FINISHED FLOOR <br />FINISHED FLOOR <br />FINISHED FLOOR <br />FINISHED (FLOOR <br />e <br />TYPICAL ELEVATION DETAIL <br />TYPICAL ELEVATION DETAIL <br />TYPICAL ELEVATION DETAIL <br />TYPICAL ELEVATION DETAIL <br />OF AUDIBLE /VISUAL ALARM DEVICE <br />OF VISUAL ALARM DEVICE <br />OF MANUAL PULL STATION <br />OF AUIDIBLE DEVICE <br />A.Js;vil7'fE:l FtANOIS) 11AVE)1EEN RE4?`EW' <br />)'f Z1 PIT`S Hl <br />LS TARE MARSHAL, S OFFICE <br />('lease be advised this review of plans submitted is a <br />CJJ(Sory review to assist the contractor in compliance with <br />applicable fire safety codes. This review is not intended <br />to bra a final approval of the submitted plans, It is the <br />contractor's sole responsibility to ensure that the plans are in <br />complete compliance with all applicable NFPA codes and <br />local ordinances, In the event that further examination or <br />site inspection reveals areas of non - compliance, it shall be <br />the contractor's sale responsibility, at their sole expense to <br />bring those areas in compliance, The City assumes no <br />responsibility for the contractor's failure to be in compliance <br />with all applicable NFPA Codes and local ordinances, <br />WIRE LEGEND <br />SYM <br />DESCRIPTION <br />SUGGESTED WIRE TYPE <br />COLOR CODE <br />NOTES: <br />1. USE FPLP TYPE WIRE FOR RUNS IN PLENUM SPACE. <br />2. USE FPLR TYPE WIRE FOR VERTICAL THRU -FLOOR RUNS, <br />3. USE FPL WIRE WHICH IS RATED FOR WET LOCATIONS, FOR ALL <br />UNDERGROUND RUNS; OR AS REQUIRED BY CODE NFPA 70. <br />4. THHN WIRE IS ACCEPTABLE FOR USE AS SHOWN ON LEGEND. <br />A <br />SLC (ANALOG LOOP) <br />18/2 TWISTED PAIR FPL <br />YELLOW <br />C <br />STROBE ONLY or CHIME /STROBE CIRCUIT <br />14/2 FPL / THHN <br />RED <br />NAC <br />NOTIFICATION APPLIANCE CIRCUIT <br />FS <br />FLOW SWITCH <br />TS <br />TAMPER SWITCH <br />CODE REFERENCES <br />THE FOLLOWING CODES HAVE BEEN REFERENCED, AND APPLIED WHEREAF NECESSARY: <br />NFPA 72 (2007) NATIONAL FIRE ALARM CODE <br />NFPA 70 (2008) NATIONAL ELECTRIC CODE (NEC) <br />NFPA 13 (2007) STANDARD ON SPRINKLER SYSTEMS <br />NFPA 101 (2009) LIFE SAFETY CODE <br />NFPA 92A (2009) STANDARD FOR SMOKE CONTROL SYSTEMS UTILIZING BARRIERS AND PRESSURE <br />DIFFERENCES. <br />NFPA 92B (2009) STANDARD FOR SMOKE MANAGEMENT SYSTEMS IN MALLS, ATRIA AND LARGE SPACES <br />FBC (2010) FLORIDA BUILDING CODE <br />FFPC (2010) FLORIDA FIRE PROTECTION CODE <br />SCOPE OF WORK <br />1. REPLACING AN EXISTING MXL FIRE ALARM PANEL TO AN XLS FIRE <br />ALARM PANEL, REPLACING IONIZATOIN SMOKE DETECTORS TO PHOTOELECTRIC <br />SMOKE DETECTORS, AND REPLACING EXISTING NOTIFICATION DEVICES WITH NEW <br />NOTIFICATION DEVICES. <br />2. PROGRAM, TEST, AND CERTIFY THE COMPLETED FIRE ALARM SYSTEM, <br />ABBREVIATIONS <br />F.B.O. <br />FURNISHED BY OTHERS <br />WP <br />WEATHERPROOF <br />H.O. <br />HIGH OUTPUT <br />FPL <br />FIRE POWER LIMITED <br />CD <br />CANDELA <br />AFF <br />ABOVE FINISHED FLOOR <br />SLC <br />SIGNALING LINE CIRCUIT <br />NAC <br />NOTIFICATION APPLIANCE CIRCUIT <br />FS <br />FLOW SWITCH <br />TS <br />TAMPER SWITCH <br />THE DRAWING AND DESIGN HEREIN SHALL NOT BE DUPLICATED, <br />USED OR DISCLOSED TO OTHERS FOR PROCUREMENT OR OTHER <br />PURPOSE (EXCEPT AS OTHERWISE AUTHORIZED BY CONTRACT) <br />WITHOUT WRITTEN PERMISSION OF SIEMENS BUILDING TECHNO- <br />LOGIE3, INC.. FIRE SAFETY DIVISION. ALL OTHER REPRODUCTIONS <br />SHALL BEAR THIS NOTICE, <br />R E V I S I O N S <br />No. I Revision I By I Cate <br />OSHPO NUMBER: <br />PROFESSIONAL ENGINEERS APPROVAL STAMP: <br />FREUD ENTERPRISES <br />CONSULTINC,£Nc Nu <br />// <br />880 PEEP LS <br />Voke 9"��jy95Q ��FC }� Jyi <br />No 32578 <br />sA <br />.�, <br />CEQRCE FRED P,E. r <br />1e7��i/��\ <br />G� <br />J I -/I Il <br />DESIGN ENGINEERS: <br />CONTRACTOR'S NAME & ADDRESS: <br />Siemens Industries, Inc. <br />Building Technologies Division <br />TAMPA BRANCH <br />8403 Benjamin Road <br />Tampa, Florida 33634 <br />Tel (813) 261 -8700 Fax (813) 890 -8055 <br />Florida State EF License No EF2000416 <br />U L. Certificate ID No 603961 -030 <br />PRODUCT MANUFACTURER: SIEMENS <br />Siemens Indusifies, Inc, <br />Building Technologies Division <br />TAMPA BRANCH <br />8403 Benjamin Road <br />Tampa, Florida 33634 <br />Tel(813)261 -8700 Fax(813)890 -8055 <br />Florida State EF License No. EF2000416 <br />U.L. Certificate ID No. 603961 -030 <br />JOB NAME & LOCATION (STREET ADDRESS) <br />Zephyrhills <br />Healthcare <br />and <br />Rehab <br />7350 Dairy Rd. <br />Zephyrhills, FI 33541 <br />SHEET CONTENTS: <br />INSTALLATION TYPE <br />3 NEW INSTALLATION <br />[3 DESIGN/BUILD <br />0 PER CONTRACT DOCUMENT <br />0 EXISTING BASE JOB # N/A <br />0 OTHERS <br />SYSTEM SALES REP.: <br />John Bourdeau <br />PROJECT MANAGER: <br />DRAWN BY: <br />Guillermo Grande <br />CAD FILENAME: <br />SCALE. <br />DATE DRAWN: <br />PLOT DATE: <br />December 10. 2013 <br />SHEET OF <br />1 <br />5 <br />JOB NUMBER <br />5200368848 <br />