Laserfiche WebLink
�1 - j '�•��4 <br /> v;> <br /> 8365 Gunn Highway <br /> Tampa, Florida 33626-1608 <br /> Phone (813) 448-0225 <br /> C O N S U L T I N G www.cea-enaineers.com <br /> ENGINEERING <br /> ASSOCIATES, INC. REG: EB-0003962 <br /> October 27, 2014 <br /> Ms. Amy Weber, AIA, LEED GA <br /> Harvard Jolly, Inc. <br /> 2714 Dr. MLK Jr. St. North <br /> St. Petersburg, FL 33704 <br /> RE: Zephyrhills Public Library <br /> CEA Job No.: #13008 <br /> Dear Amy, <br /> As requested, we have reviewed NFPA 101-12.3.2, Protection From Hazards. <br /> Mechanical Room 118 houses AHU-1 and AHU-2. AHU-1 includes a 7.5 HP motor, its variable <br /> frequency drive, disconnect, and controls. AHU-2 includes a 7.5 motor, its variable frequency <br /> drive, disconnect, and controls. Mechanical Room 118 does not contain a high-pressure boiler, <br /> refrigerating machinery, large transformers, or other service equipment subject to explosion. <br /> The rooms shall not be used for storage. <br /> The requirements of NFPA 101-12.3.2 do not apply to this room. <br /> If you have any comments or need additional information, please do not hesitate to call. <br /> Sincerely, <br /> CONSULTING ENGINEERING ASSOCIATES, INC. <br /> �...y�.�.s..��.�� <br /> W. ells, III, PE, LEED AP <br /> esident �o�2T) �y <br /> L 49347 <br /> Attachments <br /> \\Cea-fileserver\cea\CEA Projects\Year 2013\13008-Zephyrhills Library\Correspondence\Letters\13008-Oct 27 2014.1et.docx <br />