_ STROBE Operating Specifications
<br /> The strobe shall be a System Sensor SpectrAlert Advance . Standard operating temperature: 32°F to 120°F (0°C to
<br /> Model listed to UL 1971 and shall be approved for fire 49oC�
<br /> protective service. The strobe shall be wired as a primary-sig-
<br /> naling notification appliance and comply with the Americans ' K Series operating temperature: —40°F to 151°F (-40°C
<br /> with Disabilities Act requirements for visible signaling appii- to 66°C).
<br /> ances, flashing at 1 Hz over the strobe's entire operating volt- • Humidity range: 10% to 93% non-condensing (indoor
<br /> , age range.The strobe light shall consist of a xenon flash tube products).
<br /> and associated lens/reflector system. • Strobe flash rate: 1 flash per second.
<br /> HORN/STROBE COMBINATION • Nominal voltage: regulated 12 VDC/FWR or regulated 24
<br /> VDC/FWR. NOTE: Full Wave Rectified(FWR) voltage is a
<br /> The horn/strobe shall be a System Sensor SpectrAlert non-regulated, time-varyrng power source thaf rs used on
<br /> Advance Model listed to UL 1971 and UL 464 and some power supply and panel outputs.
<br /> shall be approved for fire protective service. The horn/strobe � Operating voltage range:8 V to 17.5 V(12 V nominal);or
<br /> shall be wired as a primary-signaling notification appliance 16 V to 33 V(24 V nominal). NOTE:P,S, PC,and SC prod-
<br /> and comply with the Americans with Disabilities Act require- ucts will operate at 12 V nominal only for 15 cd and 15/75
<br /> ments for visible signaling appliances,flashing at 1 Hz over the
<br /> strobe's entire operating voltage range. The strobe light shall cd.
<br /> consist of a xenon flash tube and associated lens/reflector sys- • Input terminal wire gauge: 12 to 18 AWG (3.31 to 0.821
<br /> tem.The horn shall have three audibility options and an option mmz).
<br /> to switch between a Temporal 3 pattern and a Non-Temporal • Ceiling-mount dimensions(including lens): 6.8" diame-
<br /> (continuous) pattern.These options are set by a multiple posi- ter x 2.5"deep(17.3 cm diameter x 6.4 cm deep).
<br /> tion switch.On four-wire products,the strobe shall be powered . yyall-mount dimensions(including lens):5.6" H x 4.7"W
<br /> independently of the sounder.The horn on horn/strobe modeis x 2.5"D(14.2 cm H x 11.9 cm W x 6.4 cm D).
<br /> shall operate on a coded or non-coded power supply.
<br /> • Horn dimensions: 5.6" H x 4.7" W x 1.3" D (14.2 cm H x
<br /> OUTDOOR PRODUCTS 11.9 cm W x 3.3 cm D).
<br /> SpectrAlert Advance outdoor horns, strobes and horn/strobes
<br /> shall be i�stea for outdoor use by u� and snan operate Agency Listings and Approvals
<br /> between —40°F and 151°F (-�0°C and 66°C). The products The listings and approvals below apply to SpectrAlert Advance
<br /> shall be listed for use with a System Sensor outdoor/weather- Selectable Output Notification Devices. In some cases, certain
<br /> proof backbox with half-inch and three-fourths-inch conduit modules may not be listed by certain approval agencies, or
<br /> entries. listing may be in process. Consult factory for latest listing sta-
<br /> SYNCHRONIZATION MODULE tus.
<br /> The module shall be a System Sensor Sync•Circuit MDL3R or • UL Listed: S4011 (HR_, HW_, P2_, P4_, PC2_,
<br /> MDL3W listed to UL 464 and shall be approved for fire protec- PC4_ models); S5512 (models SCR, SCRH, SCW,
<br /> tive service.The module shall synchronize SpectrAlert strobes SCWH, SR, SRH, SW, SWH); S3593 (SCRHK, SCRK,
<br /> at 1 Hz and horns at Temporal 3. Also, while operating the SRHK, SRK).
<br /> strobes, the module shall silence the horns on horn/strobe • ULC Listed: S4011 (HRA, HRKA); S5512 (typically "A"
<br /> models over a single pair of wires. The module shall mount to models, with exception of outdoor strobes). See Canadran
<br /> a 4.688"x 4.688"x 2.125" (11.906 x 11.906 x 5.398 cm)back- data sheet for lrstrngs and specificatrons.
<br /> box. The module shall also control two Style Y (class B) cir- . FM approved
<br /> cuits or one Style Z (Class A) circuit. The module shall . MEA:452-05-E
<br /> synchronize multiple zones. Daisy-chaining two or more syn-
<br /> chronization modules together will synchronize all the zones ' CSFM: 7125-1653:0186 (SCR, SCRH, SCW, SCWH, SR,
<br /> they controL The module shall not operate on a coded power SRH, SW, SWH);7300-1653:0188(P2_, P4_, PC2_, PC4_
<br /> supply. modules); 7135-1653:0189 (HR, HRK, HW); 7300-
<br /> 1653:0187(SCRHK, SCRK, SRHK,SRK).
<br /> Strobe Current Draw, Horn Current Draw,
<br /> UL Maximum (mA RMS) UL Maximum (mA RMS)
<br /> 8-17.5 V 16-33 V Sound $-'1�•5 V 16-33 V
<br /> Candela Pattern dB
<br /> DC FWR DC FWR DC FWR DC FWR
<br /> 15 123 128 66 71 Temporal High 57 55 69 75
<br /> 15/75 142 148 77 81 Temporal Medium 44 49 58 69
<br /> Standard 30 NA N!A 94 96 Temporal Low 38 44 44 48
<br /> Candela 75 NA NA 158 153 Non-temporal High 57 56 69 75
<br /> Range g5 NA NA 181 176 Non-temporal Medium 42 50 60 69
<br /> 110 NA NA 202 195 Non-temporal Low 41 44 50 50
<br /> 115 NA NA 210 205 oded High 57 55 9 75
<br /> 135 NA NA 8 2 7 Coded Medium 44 51 56 69
<br /> High 150 NA NA 246 220 Coded Low 40 46 52 50
<br /> Candela
<br /> Range »� NA NA 281 251
<br /> 185 NA NA 286 258
<br /> Page 2 ot 4—DN-7087:C1•11/9/11