Laserfiche WebLink
�' • � � . � • • � � " <br /> • AE D G ph <br /> z0000 <br /> 15000 <br /> "ti <br /> � 10000 <br /> .� <br /> 5000 <br /> d 8am 9am l�am llam 12pm lpm 2pm 3pm 4pm Spm 6pm 7pm $pm <br /> --Hourly Loads —Average <br /> � � � � � <br /> System equipment selettion wili be made using the following de +ued values. <br /> Glass (E) 123 sq. ft. <br /> Glass (5) 17 sq. ft. <br /> Glass (N) 17 sq. ft. <br /> Glass (W) 86 sq. ft. <br /> Summer Outdoor 91°F <br /> Summer Wet Bulb 77°F <br /> 5ummer Indoor 75°F <br /> Summer Design Grains 50°l0 <br /> Winter Outdoor 40°F <br /> Winter Indoor 70°F <br /> Sensible Caoling 2b,751 Btuh <br /> Latent Cooling 5,878 Btuh <br /> Required Cooling Airflow 1,226 CFM <br /> Sensible Hea�ing 24,625 Btuh <br /> Required Heating Airfl4w 320 CFM <br /> AH calculations are iaased upan appraved hvac industry standa ds and procedures,and comply wit#�aU iocai, <br /> state and federal code requirements.Aii computed results are stimates.Product provided by Energy Design <br /> 5ystems and Idea Tree <br />