Laserfiche WebLink
� ! ' • � ' • • ' � ' <br /> ' AED G aph <br /> 15000 � �------ ---- <br /> � 10000 ------ — ----- ---------- --� — — <br /> , a <br /> m <br /> , a <br /> � J <br /> 5000 �_ _ �_---- — ---.-------------��_____��_.__ <br /> I <br /> � 0 -----�---------------------------,---- ----------- --------------------------- <br /> � 8am � 9am � l0am llam 12pm lpm 2pm 3pm 4pm � Spm � 6pm 7pm 8pm <br /> � — Hourly Loads —Average <br /> . <br /> � � a � <br /> System equipment selection wili be made using the following de ived values. <br /> Glass (E) 119 sq. ft. <br /> Glass (S) 17 sq. ft. <br /> Glass (N) 17 sq. ft. <br /> Glass (W) 83 sq. ft. <br /> Summer Outdoor 91°F <br /> Summer Wet Bulb 77°F <br /> Summer Indoor 75°F <br /> Summer Design Grains 50% <br /> Winter Outdoor 40°F <br /> Winter Indoor 70°F <br /> Sensible Cooling 25,989 Btuh <br /> Latent Cooling 5,674 Btuh <br /> Required Cooling Airflow 1,181 CFM <br /> Sensible Heating 23,811 Btuh <br /> Required Heating Airflow 309 CFM <br /> Afl calculations are based upan approved hvac indusiry standar s and procedures,and comply with all local, <br /> state and federal code requirements.All computed results are E timates.Product provided by Energy Design <br /> Systems and Idea Tree <br />