Walgreens 5604-R14 June 24,2014 <br /> driers are factory-installed as standard. An area shall be Iprovided for replacement suction line driers. <br /> Phase monitor <br /> Phase monitor shall provide 100% protection for motors nd compressors against problems caused by phase loss, <br /> phase imbalance, and phase reversal. Phase monitor is equipped with an LED that provides an ON or FAULT indicator. <br /> There are no field adjustments. The module will automati�cally reset from a fault condition. <br /> Electric Heaters <br /> Electric heat modules shall be available for installation wi hin basic unit. Electric heater elements shall be constructed of <br /> heavy-duty nickel chromium elements internally delta co nected for 240 volt, wye connected for 480 and 600 volt. <br /> Staging shall be achieved through ReliaTel. Each heater package shall have automatically reset high limit control <br /> operating through heating element contactors. All heater shall be individually fused from the factory, where required, <br /> and shall meet all NEC and CEC requirements when proQerly installed Power assemblies shall provide single point <br /> connection. Electric heat modules shall be UL listed or C A certified. <br /> Through the Base Electrical with Disconnect Switch <br /> This 3-pole, molded case, disconnect switch with provisi ns for through the base electrical connections are available. <br /> The disconnect switch will be installed in the unit in a wat r tight enclosure with access through a swinging door.Wiring <br /> will be provided from the switch to the unit high voltage t rminal block. The switch will be UUCSA agency recognized. <br /> Note: The disconnect switch will be sized per NEC and L guidelines but will not be used in place of unit overcurrent <br /> protection. <br /> Economizer <br /> This accessory shall be available with or without baromet ic relief. The assembly includes fully modulating 0-100 <br /> percent motor and dampers, minimum position setting, p�eset linkage, wiring harness with plug, spring return actuator <br /> and fixed dry bulb control. The barometric relief shall pro�ide a pressure operated damper that shall be gravity closing <br /> and shall prohibit entrance of outside air during the equip�ent off cycle. Optional solid state or differential enthalpy <br /> control shall be available for either factory or field installat on. The economizer arrives in the shipping position and shall <br /> be moved to the operating position by the installing contr ctor. <br /> Motorized Outside Air Dampers <br /> Manually set outdoor air dampers shall provide up to 50 p rcent outside air. Once set, outdoor air dampers shall open to <br /> set position when indoor fan starts. The damper shall clo�e to the full closed position when indoor fan shuts down. <br /> Frostat <br /> This option is to be utilized as a safety device. The Frost t opens when temperatures on the evaporator coil fall below <br /> 10°F. The temperature will need to rise to 50°F before clo�sing This option should be utilized in low airflow or high <br /> outside air applications. (Cooling with Electric Heat Only.) <br /> T.rane Single Zone Variable Air Volume Control Sequ nce of Operation (Precedent 17 Plus) <br /> General Standbv Mode <br /> During normal occupied periods, when there is no space ooling or heating demands, the user will be able to choose <br /> Continuous or Cycling supply fan operation. During this p riod, if the supply fan is operating due to a Continuous Fan <br /> Mode selection or due to a ventilation request, the supply fan will operate at 50% of the user selected, application <br /> specific, maximum airflow. The unit controls will be compatible with BACnet and LonTalk Building Automation System <br /> communication interfaces. <br /> Cooling Operation <br /> Default Oqeration. <br /> During Cooling operation, the control will monitor the Sp ce Temperature and Space Cooling setpoint and with a PI <br /> contro <br /> algorithm determine if active cooling capacity is required.As the Space Temperature deviates from the Space Cooling <br /> Setpoint, <br /> the unit controller will calculate an active Discharge Air C�ooling setpoint that the economizer(if installed) and <br /> compressor outputs I <br /> will be controlled to meet. This active Discharge Air Cooling setpoint will be calculated between the Space Cooling <br /> setpoint and a <br /> user adjustable minimum (65F Default for Single Zone Variable Air Volume Control). Once the control determines that <br /> a discharge <br /> air temperature equal to the user selected minimum (65F Default) is required to meet the space cooling demand, if the <br /> space <br /> demand continues to increase, the supply fan speed will be allowed to increase above its minimum speed <br /> proportionally to meet <br /> FLD=Fumished by Trane U.S.Inc./Installed by Equipmlent Submittal Page 8 of 30 <br /> Others <br />